Operating instructions
50
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
6
x
Parameter settings
6.8
Rotary switch setting: Time Program
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Party
The heating circuit operates at the target room temperature set in the [T-Room 1 Setpoint]
parameter for the set period of time. If the [Automatic 1] or [Automatic 2] timer programmes
are active, the heating cycle is extended or started early. (Target room temperature - see
section 3.4.7).
The hot water generation is not affected.
E
E
00:00 - 06:00
00:00
1 h
Away
The heating circuit operates at the target room temperature set in the [T-Absence] parameter
for the set period of time.
The hot water generation is not affected.
E
E
00:00 - 06:00
00:00
1 h
Vacation
The heating circuit operates at the target room temperature set in the [T-Absence] parameter
permanently (24 h per day).
A calendar function can be used to enter a time period for the absence.
E
E
Date on first
day
-
Date on last
day:
-
1 Day
Holiday
A calendar function can be used to enter a time period for presence.
During this time, the system operates exclusively in accordance with the "Sunday" settings
in [DHW Program 1] and [HC Program 1].
E
E
Date on first
day
-
Date on last
day:
-
1 Day
HC Program 1
In this menu we can parametrise the 1st. timer programme for the heating circuit. 3 switching
cycles with a resolution of 15 minutes can be set. A separate entry for each weekday is pos-
sible. Format: (On) hh:mm - hh:mm (Off)
Also, the cycles can be parametrised from Monday to Friday, Saturday to Sunday and Mon-
day to Sunday.
E
E
see
chapter 3.4.7
see
15 min
HC Program 2
In this menu we can parametrise the 2nd. timer programme for the heating circuit. 3 switch-
ing cycles with a resolution of 15 minutes can be set. A separate entry for each weekday is
possible. Format: (On) hh:mm - hh:mm (Off)
Also, the cycles can be parametrised from Monday to Friday, Saturday to Sunday and Mon-
day to Sunday.
E
E
see
chapter 3.4.7
see
15 min
DHW Program 1
In this menu we can parametrise the 1st. timer programme for hot water generation. 3 switch-
ing cycles with a resolution of 15 minutes can be set. A separate entry for each weekday is
possible. Format: (On) hh:mm - hh:mm (Off)
Also, the cycles can be parametrised from Monday to Friday, Saturday to Sunday and Mon-
day to Sunday.
E
E
see
chapter 3.4.7
see
15 min
DHW Program 2
In this menu we can parametrise the 2nd. timer programme for hot water generation.
3 switching cycles with a resolution of 15 minutes can be set. A separate entry for each
weekday is possible. Format: (On) hh:mm - hh:mm (Off)
Also, the cycles can be parametrised from Monday to Friday, Saturday to Sunday and Mon-
day to Sunday.
E
E
see
chapter 3.4.7
see
15 min
Circulation Time
In this menu we can parametrise a timer programme for the circulation pump. 3 switching
cycles with a resolution of 15 minutes can be set. A separate entry for each weekday is pos-
sible. Format: (On) hh:mm - hh:mm (Off)
Also, the cycles can be parametrised from Monday to Friday, Saturday to Sunday and Mon-
day to Sunday.
E
E
see
chapter 3.4.7
see
15 min
Tab. 6-10 Parameter in rotary switch setting "Time Program"
6.9
Rotary switch setting: Remote Param
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Bus - Scan
Off: No function
On: Controller checks which RoCon devices are connected to the system using the CAN bus
lines. Devices that are detected are displayed with their type and device ID (see chapter 4.1,
example: MM#8 = Mixer module with device ID 8).
The selection and confirmation of a device with the rotary switch (brief pressing of the button
places a check mark in the selection box) activates the terminal function.
→
The control unit then operates as a remote control for the selected device
(see chapter 3.4.9).
E
E
Off
On
Off
-
No selection
Activation switches to the local device.
E
E
-
Contr BM1/BE1 #X
Activation switches to the Daikin Altherma EHS(X/H) with the device ID X (see section 6.12,
parameter [BUS ID HS]).
E
E
-
Mix Valve #X
Activation switches to the mixer module with the device ID X (see section 6.13.1, parameter
[HC Assignment]).
E
E
-
Tab. 6-11 Parameter in rotary switch setting "Remote Param"