8
|
Piping installation
Installer reference guide
72
EBLA04~E23V3 + EDLA04~E23V3
Daikin Altherma 3 M
4P685228-1A – 2022.05
▪
Closed circuit.
Use the outdoor unit ONLY in a closed water system. Using the
system in an open water system will lead to excessive corrosion.
▪
Piping length.
It is recommended to avoid long runs of piping between the
domestic hot water tank and the hot water end point (shower, bath,…) and to
avoid dead ends.
▪
Piping diameter.
Select the water piping diameter in relation to the required
water flow and the available external static pressure of the pump.
For the external static pressure curves of the outdoor unit, see the technical
data. A
subset
of the latest technical data is available on the regional Daikin
website (publicly accessible). The
full set
of latest technical data is available on
the Daikin Business Portal (authentication required).
▪
Water flow.
You can find the minimum required water flow for unit operation in
the following table. In all cases, this flow needs to be guaranteed. When the flow
is lower, the unit will stop operation and display error 7H.
If operation is…
Then the minimum required flow rate
is…
Cooling
10 l/min
Heating
6 l/min
BUH operation
12 l/min
Heating defrost
12 l/min
DHW
25 l/min
▪
Field supply components – Water and glycol.
Only use materials that are
compatible with the water (and, if applicable, glycol) used in the system, and
with the materials used in the outdoor unit.
▪
Field supply components – Water pressure and temperature.
Check that all
components in the field piping can withstand the water pressure and water
temperature.
▪
Water pressure.
The maximum water pressure is 4 bar. Provide adequate
safeguards in the water circuit to ensure that the maximum pressure is NOT
exceeded.
▪
Water temperature.
All installed piping and piping accessories (valve,
connections,…) MUST withstand the following temperatures:
INFORMATION
The following figure is an example and may NOT completely match your system