6
|
Application guidelines
Installer reference guide
34
EBLA04~E23V3 + EDLA04~E23V3
Daikin Altherma 3 M
4P685228-1A – 2022.05
▪
The user interface connected to the outdoor unit decides the space operation
mode. Mind that the operation mode on each room thermostat must be set to
match the outdoor unit.
▪
The room thermostats are connected to the shut-off valves, and do NOT have to
be connected to the outdoor unit. The outdoor unit will supply leaving water all
the time, with the possibility to program a leaving water schedule.
Configuration
Setting
Value
Unit temperature control:
▪
#: [2.9]
▪
Code: [C-07]
0 (
Leaving water
): Unit operation is
decided based on the leaving water
temperature.
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7-02]
0 (
Single zone
): Main
Benefits
Compared with underfloor heating or radiators for one room:
▪
Comfort.
You can set the desired room temperature, including schedules, for
each room via the room thermostats.
Heat pump convectors – Multiple rooms
Setup
b
a
b
B
C
A
A
Main leaving water temperature zone
B
Room 1
C
Room 2
a
User interface (delivered as accessory)
b
Heat pump convectors (+ controllers)
▪
For more information about connecting the electrical wiring to the unit, see
"9.2 Connections to the outdoor unit"
90].
▪
The desired room temperature is set via the controller of the heat pump
convectors. There are different controllers and setups possible for the heat pump
convectors. For more information, see:
-
The installation manual of the heat pump convectors
-
The installation manual of the heat pump convector options
-
The addendum book for optional equipment
▪
The user interface connected to the outdoor unit decides the space operation
mode.