9
|
Electrical installation
Installer reference guide
100
EBLA04~E23V3 + EDLA04~E23V3
Daikin Altherma 3 M
4P685228-1A – 2022.05
1N~, 50 Hz
230 V AC
L
N
Q1DI
1
3
2
4
F1B
X6M
X
9M
.L
X
9M
.N
X
9M
.P
E
I
I
F1B
Overcurrent fuse (field supply). Recommended fuse: 2‑pole; 16 A; curve 400 V;
tripping class C.
Q1DI
Earth leakage circuit breaker (field supply)
X6M
Terminal (field supply)
N
L N
180°
X9M
3
Fix the cable with cable ties to the cable tie mountings.
9.2.4 External backup heater kit
For models without integrated backup heater, you can install the external backup
heater kit (EKLBUHCB6W1).
If you do so, then under certain conditions you also need to install a bypass valve
kit (EKMBHBP1).
See:
▪
"To connect the backup heater kit"
▪
▪
"To connect the bypass valve kit"
To connect the backup heater kit
The installation of the external backup heater kit is described in the installation
manual of the kit. However, certain parts of it are superseded by the information
described here. It concerns the following:
▪
To connect the backup heater kit power supply
▪
To connect the backup heater kit to the outdoor unit
Wires: See installation manual of the backup heater kit