Application guidelines
Installer reference guide
39
EBLA04~E23V3 + EDLA04~E23V3
Daikin Altherma 3 M
4P685228-1A – 2022.05
▪
The user interface connected to the outdoor unit decides the space operation
mode. Mind that the operation mode on each controller of the heat pump
convectors must be set to match the outdoor unit.
Configuration
Setting
Value
Unit temperature control:
▪
#: [2.9]
▪
Code: [C‑07]
2 (
Room thermostat
): Unit operation
is decided based on the ambient
temperature of the dedicated Human
Comfort Interface.
Note:
▪
Main room = dedicated Human
Comfort Interface used as room
thermostat functionality
▪
Other rooms = external room
thermostat functionality
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7‑02]
1 (
Dual zone
): Main + additional
In case of heat pump convectors:
External room thermostat for the
additional
zone:
▪
#: [3.A]
▪
Code: [C‑06]
1 (
1 contact
): When the used
external room thermostat or heat pump
convector can only send a thermo ON/
OFF condition. No separation between
heating or cooling demand.
Bizone kit installed
:
▪
#: [9.P.1]
▪
Code: [E‑0B]
2 (
Yes
)
:
A bizone kit is installed in order
to add an additional temperature zone.
Bizone system type
:
▪
#: [9.P.2]
▪
Code: [E‑0C]
0 (
Without hydraulic
separator / no direct pump
)
1 (
With hydraulic separator /
no direct pump
)
2 (
With hydraulic separator /
with direct pump
)
(See 3 system variations described
above)
Shut-off valve output
Set to follow the thermo demand of the
main zone.
Shut-off valve
If the main zone must be shut off during
cooling mode to prevent condensation
on the floor, set it accordingly.
See
216] for more information on configuration of the bizone kit.