Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.1.8.1
[2-0D]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
9.1.8.3
R/W
0: Fixed
1: WD heating, fixed cooling
2: Weather dependent
9.1.8.4
R/W
0: No
1: Yes
9.1.9
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
[2-0C]=0
25°C
[2-0C]=1
35°C
[2-0C]=2
40°C
9.1.9
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
[2-0C]=0
35°C
[2-0C]=1
45°C
[2-0C]=2
60°C
9.1.9
[0-02]
R/W
10~25°C, step: 1°C
15°C
9.1.9
[0-03]
R/W
-40~5°C, step: 1°C
-10°C
9.1.A
[0-04]
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0C]=0
18°C
[2-0C]=1
7°C
[2-0C]=2
18°C
9.1.A
[0-05]
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0C]=0
22°C
[2-0C]=1
15°C
[2-0C]=2
22°C
9.1.A
[0-06]
R/W
25~43°C, step: 1°C
35°C
9.1.A
[0-07]
R/W
10~25°C, step: 1°C
20°C
└─
Tank
9.1.B.1
[6-0D]
R/W
0: Reheat only
1: Sc reheat
2: Schedule only
9.1.B.2
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
9.1.B.3
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.1.B.4
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.1.B.5
[6-08]
R/W
2~20°C, step: 1°C
10°C
└─
Domestic hot water
9.2.1
[E-05]
[E-06]
[E-07]
R/W
E-05=0
No DHW
E-07 = 0
EKHWS/E, small volume
E-07 = 3
EKHWS/E, big volume
E-07 = 5
EKHWP/HYC
E-07 = 7
3rd party, small coil
E-07 = 8
3rd party, big coil
9.2.2
[D-02]
R/W
0: No DHW pump
1: Instant hot water
2: Disinfection
3: Circulation
4: Circulation and disinfection
9.2.4
[D-07]
R/W
0: No
1: Yes (DHW)
└─
Back up heater
9.3.1
[E-03]
R/O (*3)
R/W (*4)
0: No heater (*4)
1: External heater
2: 3V (*3)
9.3.2
[5-0D]
R/O(*3)
R/W(*4)
0: 230V, 1~ (*3)
1: 230V, 3~
2: 400V, 3~
9.3.3
[4-0A]
R/W
0: 1
1: 1/1+2
2: 1/2
3: 1/2 + 1/1+2 in emergency
9.3.4
[6-03]
R/W
0~10kW, step: 0,2kW
0kW (*4)
3kW (*3)
9.3.5
[6-04]
R/W (*4)
R/O (*3)
0~10kW, step: 0,2kW
0kW (*3)
9.3.6
[5-00]
R/W
0: No
1: Yes
9.3.7
[5-01]
R/W
-15~35°C, step: 1°C
0°C
9.3.8
[4-00]
R/W
0: Restricted
1: Allowed
2: Only DHW
Emitter type
Setpoint mode
Schedule
Leaving water value for high ambient temp. for LWT add zone
heating WD curve.
Leaving water value for low ambient temp. for LWT add zone
heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone
cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone
cooling WD curve.
High ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Heat up mode
Comfort setpoint
Eco setpoint
Reheat setpoint
Reheat hysteresis
Domestic hot water
DHW pump
Solar
BUH type
Voltage
Configuration
Capacity step 1
Additional capacity step 2
Equilibrium: Deactivate backup heater (or external backup heat sou
Equilibrium temperature
Operation
4P685235-1 - 2022.03
(*1) EBLA*_(*2) EDLA*_(*3) *23V3_(*4) *2V3