11
|
Configuration
Installer reference guide
207
EBLA04~E23V3 + EDLA04~E23V3
Daikin Altherma 3 M
4P685228-1A – 2022.05
#
Code
Description
[9.9.1]
[4-08]
Power consumption control
:
▪
0
No
: Disabled.
▪
1
Continuous
: Enabled: You can set one
power limitation value (in A or kW) to which
the system power consumption will be
limited for all the time.
▪
2
Inputs
: Enabled: You can set up to four
different power limitation values (in A or kW)
to which the system power consumption will
be limited when the corresponding digital
input asks.
[9.9.2]
[4-09]
Type
:
▪
0
Amp
: The limitation values are set in A.
▪
1
kW
: The limitation values are set in kW.
Limit when [9.9.1]=
Continuous
and [9.9.2]=
Amp
:
#
Code
Description
[9.9.3]
[5-05]
Limit
: Only applicable in case of full time
current limitation mode.
0 A~50 A
Limits when [9.9.1]=
Inputs
and [9.9.2]=
Amp
:
#
Code
Description
[9.9.4]
[5-05]
Limit 1
: 0 A~50 A
[9.9.5]
[5-06]
Limit 2
: 0 A~50 A
[9.9.6]
[5-07]
Limit 3
: 0 A~50 A
[9.9.7]
[5-08]
Limit 4
: 0 A~50 A
Limit when [9.9.1]=
Continuous
and [9.9.2]=
kW
:
#
Code
Description
[9.9.8]
[5-09]
Limit
: Only applicable in case of full time
power limitation mode.
0 kW~20 kW
Limits when [9.9.1]=
Inputs
and [9.9.2]=
kW
:
#
Code
Description
[9.9.9]
[5-09]
Limit 1
: 0 kW~20 kW
[9.9.A]
[5-0A]
Limit 2
: 0 kW~20 kW
[9.9.B]
[5-0B]
Limit 3
: 0 kW~20 kW
[9.9.C]
[5-0C]
Limit 4
: 0 kW~20 kW