9
|
Electrical installation
Installer reference guide
115
EBLA04~E23V3 + EDLA04~E23V3
Daikin Altherma 3 M
4P685228-1A – 2022.05
2
Connect the changeover to external heat source cable to the appropriate
terminals as shown in the illustration below.
A4P.X2
A4P.X1
L
N
A4P
a
X1
X2
X2M
X1
X2
180°
a
Installation of EKRP1HBAA is required.
3
Fix the cable with cable ties to the cable tie mountings.
9.2.12 To connect the power consumption digital inputs
Wires: 2 (per input signal)×0.75 mm²
Power limitation digital inputs: 12 V DC / 12 mA detection (voltage
supplied by PCB)
[9.9]
Power consumption control
.
1
Access the electrical connections. See
"9.2.1 To connect the electrical wiring
2
Connect the power consumption digital inputs cable to the appropriate
terminals as shown in the illustration below.
A8P.1
A8P.2
A8P.3
A8P.4
A8P.5
S6S (DI4)
S7S (DI3)
S8S (DI2)
S9S (DI1)