APPENDIX A BLOWER PERFORMANCE TABLES - HEAT PUMP
5 Ton Heat Pump
Standard Static Drive
Models: DRH0601D and DRH0603D
Down Flow
Horizontal Flow
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN WC
SCFM RPM BHP
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN WC
SCFM RPM BHP
T1
0.2
1299 614 0.16
T1
0.2
1326 653 0.22
0.4
1209 674 0.17
0.4
1234 717 0.24
0.6
1082 755 0.19
0.6
1104 803 0.27
0.8
933
836 0.21
0.8
952
890 0.30
1.0
835
889 0.23
1.0
852
946 0.32
T2
0.2
1967 862 0.62
T2
0.2
2007 885 0.64
0.4
1896 951 0.69
0.4
1935 931 0.67
0.6
1849 1022 0.74
0.6
1887 969 0.70
0.8
1786 948 0.69
0.8
1822 1009 0.73
1.0
1710 996 0.72
1.0
1745 1060 0.77
T3
0.2
1967 862 0.62
T3
0.2
2007 885 0.64
0.4
1896 951 0.69
0.4
1935 931 0.67
0.6
1849 1022 0.74
0.6
1887 969 0.70
0.8
1786 948 0.69
0.8
1822 1009 0.73
1.0
1710 996 0.72
1.0
1745 1060 0.77
T4
0.2
2189 902 0.81
T4
0.2
2234 960 0.86
0.4
2119 943 0.84
0.4
2162 1003 0.90
0.6
2059 979 0.88
0.6
2101 1042 0.93
0.8
2012 1009 0.90
0.8
2053 1073 0.96
1.0
1969 1048 0.94
1.0
2009 1115 1.00
T5
0.2
2254 923 0.88
T5
0.2
2300 982 0.93
0.4
2178 964 0.92
0.4
2222 1025 0.98
0.6
2127 997 0.95
0.6
2170 1061 1.01
0.8
2078 1029 0.98
0.8
2120 1095 1.04
1.0
2026 1060 1.01
1.0
2067 1128 1.07
Shaded area indicates air flow below 1200 SCFM (300 SCFM/ton)
that is not recommended for High Stage cooling or heating
5 Ton Heat Pump
Standard Static Drive
Models: DRH0604D and DRH0607D
Down Flow
Horizontal Flow
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN WC
SCFM RPM BHP
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN WC
SCFM RPM BHP
T1
0.2
1130 498 0.11
T1
0.2
1154 529 0.12
0.4
1046 551 0.12
0.4
1068 585 0.13
0.6
886 647 0.15
0.6
904 687 0.16
0.8
737 727 0.16
0.8
752 772 0.17
1.0
585 803 0.18
1.0
597 853 0.19
T2
0.2
1964 806 0.52
T2
0.2
2004 856 0.55
0.4
1877 857 0.55
0.4
1916 911 0.59
0.6
1786 909 0.58
0.6
1823 966 0.62
0.8
1711 970 0.62
0.8
1746 1031 0.66
1.0
1613 1028 0.66
1.0
1646 1093 0.70
T3
0.2
1964 806 0.52
T3
0.2
2004 856 0.55
0.4
1877 857 0.55
0.4
1916 911 0.59
0.6
1786 909 0.58
0.6
1823 966 0.62
0.8
1711 970 0.62
0.8
1746 1031 0.66
1.0
1613 1028 0.66
1.0
1646 1093 0.70
T4
0.2
2071 842 0.58
T4
0.2
2114 894 0.62
0.4
1987 888 0.61
0.4
2028 944 0.65
0.6
1903 937 0.65
0.6
1941 996 0.69
0.8
1838 995 0.69
0.8
1875 1057 0.73
1.0
1762 1041 0.72
1.0
1798 1106 0.76
T5
0.2
2173 873 0.64
T5
0.2
2217 928 0.68
0.4
2095 921 0.68
0.4
2138 979 0.72
0.6
2009 967 0.71
0.6
2050 1027 0.76
0.8
1933 1015 0.75
0.8
1973 1079 0.80
1.0
1867 1062 0.78
1.0
1905 1129 0.83
Shaded area indicates air flow below 1200 SCFM (300 SCFM/ton)
that is not recommended for High Stage cooling or heating