background image

14

Refrigeration System Checks

This unit is equipped with  thermal expansion  valves. 

Ensure the hold-down bolts on the compressor are secure 

and have not vibrated loose during shipment.  Check 

that the vibration grommets have been installed and 

visually check all piping for damage and leaks and repair 

if necessary.  The entire system has been factory charged 

and tested, making it unnecessary to field charge.  Factory 

refrigerant charge is shown on the unit’s nameplate.

To confirm charge levels or, if a leak occurs and charge 

needs to be added to the system, it is recommended to 

evacuate the system and recharge refrigerant to the unit’s 

nameplate specifications.  This unit has been rated in the 

cooling mode at the AHRI rated conditions of:  indoor (80°F 

db/67°F wb) and outdoor (95°F db).  While operating at this 

condition, the superheat should range from 9°F to 11°F for 

each refrigeration circuit measured at the suction service 

port located near the compressor.

Start-Up Procedure and Checklist

Begin with power turned off at all disconnects.

Air Conditioning  Start-Up Procedure

1.  Ensure the thermostat is set to OFF and Fan is set 

to Auto.

2. 

Inspect all registers and set them to the normal open 

position.

3.  Turn on the electrical supply at the disconnect.
4.  Turn the fan switch to the “ON” position. The blower 

should operate after a 7 second delay. 

5.  Turn the fan switch to “Auto” position. The blower 

should stop after a 60 second delay. 

6.  Set the thermostat to Cool mode and slowly 

lower the cooling temperature until the unit starts. 

The compressor, blower and fan should now be 

operating. Allow the unit to run 10 minutes, make 

sure cool air is being supplied by the unit. 

7.  Check that the compressor is operating correctly. 

The scroll compressors in these units MUST operate 

in the proper rotation. To ensure the compressors 

are operating in the correct direction, check the 

compressor discharge line pressure or temperature 

after the compressor is started. The discharge 

pressure and discharge line temperature should 

increase. If this does not occur and the compressor 

is producing an exceptional amount of noise,this 

indicates that there is a phasing issue. 

Perform the following to correct: 

 

 

7.1  Turn power to the unit OFF.

 

7.2  Switch any two leads of power supply at unit  

 

   

  Single Point Power Block.

 

7.3  Turn power to the unit ON.

 

7.4  Perform step 7 again.

 

8.  Turn the temperature setting to the highest position, 

stopping the unit. The indoor blower will continue to 

run for 60 seconds. 

9.  Turn the thermostat system switch to “OFF” and 

disconnect all power when servicing the unit.

 

 

NOTE: The compressor has 180 second re-start 

delay on timer to avoid short cycling.

WARNING

HIGH VOLTAGE!

Disconnect all power before 

servicing or installing this unit.  

Multiple power sources may be 

present.  Failure to do so may cause 

property damage, personal injury or 

death.

Heat Pump Start-Up Procedure 

10. 

Check the cooling mode for the heat pump in 

the same manner as above. The reversing valve 

is energized when the thermostat is placed in 

the cooling position. A clicking sound should be 

noticeable from the reversing valve. By lowering the 

temperature setting to call for cooling, the solenoid 

valve is energized. The compressor, blower and fan 

should then be running. After the cooling mode is 

checked out, turn the thermostat system switch to 

“OFF”. 

11. Turn the thermostat system switch to “HEAT” and fan 

switch to “AUTO”.

12. Slowly raise the heating temperature setting. When 

the heating first stage makes contact, stop raising 

the temperature setting.. The compressor, blower 

and fan should now be running with the reversing 

valve in the deenergized (heating) position. After 

giving the unit time to settle out, make sure the unit 

is supplying heated air.

 

Note:  If the outdoor ambient is above 80°F, the 

unit may trip on its high pressure cut out when on 

heating. The compressor should stop. The heating 

cycle must be thoroughly checked, so postpone 

the test to another day when conditions are more 

suitable but-DO NOT FAIL TO TEST. If the outdoor 

ambient is low and the unit operates properly on the 

heating cycle, you may check the pressure cutout 

operation by blocking off the indoor return air until 

the unit trips.

13. Once the heating has been confirmed, raise the 

temperature setting until the second stage heating 

makes contact. Supplemental resistance heat, if 

installed should now come on. Make sure it operates 

properly. 

14. For thermostats with emergency heat switch, set 

thermostat to Emergency Heat mode. The heat 

pump will stop, the blower will continue to run, all 

heaters will come on and the thermostat emergency 

heat light will come on. Confirm heaters operate 

normally.

Summary of Contents for DRC036

Page 1: ...pecified in this manual only licensed personnel should servise the equipment Improper installation adjustment servicing or repair of the equipment specified in this manual or attempting to install adj...

Page 2: ...ce CAUTION Sheet metal parts screws clips and similar items inherently have sharp edges and it is necessary that the installer and service personnel exercise caution WARNING Do not connect to or use a...

Page 3: ...ld also where applicable follow information presented in accepted industry guides such as the ASHRAE Handbooks The manufacturer assumes no responsibility for equipment installed in violation of any co...

Page 4: ...Installations Only To avoid possible property damage or personal injury the roof must have sufficient structural strength to carry the weight of the unit s and snow or water loads as required by local...

Page 5: ...ntenance and proper unit operation A clearance of 48 is recommended on all sides of the unit to facilitate possible parts replacement to allow service access and to insure proper ventilation and conde...

Page 6: ...struts mounted beneath unit base frame before setting unit on roof curb These struts are intended to protect unit base frame from fork lift damage Removal is accomplished by extracting the sheet meta...

Page 7: ...uit ampacity but less than or equal to the maximum overcurrent protection device DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE All line voltage connections must be made th...

Page 8: ...ols used by the service mechanic NOTE Refer to local codes for requirements These outlets can also be factory installed Units installed on Roof Tops Main power and low voltage wiring may enter the uni...

Page 9: ...nsions are shown in the roof curb installation manual If desired supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmissi...

Page 10: ...and install new filters Contractor Responsibility The installing contractor must be certain that All supply and return air ductwork is in place properly sealed and corresponds with installation instr...

Page 11: ...ce it is established that supply voltage will be maintained within the utilization range under all system conditions check and calculate if an unbalanced condition exists between phases Calculate perc...

Page 12: ...ng stage 1 operation Do not move wires YL and PU to the same taps Move WHITE WH wire from TB1 T2 to T3 to change blower speed during heating stage 1 operation Do not move wires WH and BR to the same t...

Page 13: ...rost O from board X X X X PU X 24V signal Range of AVAILABLE TAPS For wire color information and placement view DRC DRH Model Wiring PG 13 DRH OPERATION and WIRE RANGE CHART HI STATIC DRH OPERATIONS W...

Page 14: ...F 7 2 Switch any two leads of power supply at unit Single Point Power Block 7 3 Turn power to the unit ON 7 4 Perform step 7 again 8 Turn the temperature setting to the highest position stopping the u...

Page 15: ...then goes through the expansion device to the outdoor coil condenser on the cooling cycle where the liquid is evaporated and the vapor goes to the compressor The following figures show a schematic of...

Page 16: ...ly registers should be free of any obstructions The filters should be cleaned or replaced These few steps will help to keep the product up time to a maximum The Service section that follows should hel...

Page 17: ...dicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 3 Ton Cooler Standard Static Drive Models DRC0364D and DRC0367D Down Flow Horizontal Flow SPEED...

Page 18: ...0 1567 843 807 0 48 1 0 1599 84 859 0 52 Shaded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 4 Ton Cooler Standard Static Drive Models...

Page 19: ...1 07 Shaded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 5 Ton Cooler Standard Static Drive Models DRC0604D and DRC0607D Down Flow Hor...

Page 20: ...91 0 8 2125 89 1066 0 99 1 0 2011 1033 0 96 1 0 2051 78 1113 1 03 T3 65 0 2 2226 892 0 69 T3 65 0 2 2211 885 0 68 0 4 2143 931 0 72 0 4 2128 938 0 73 0 6 2052 973 0 75 0 6 2034 988 0 76 0 8 1950 1027...

Page 21: ...or heating APPENDIX A BLOWER PERFORMANCE TABLES AC 3 Ton Cooler High Static Drive Models DRC0363W DRC0364W DRC0367W Horizontal Flow SPEED TAP EXTERNAL STATIC PRESSURE ESP IN W C SCFM RPM BHP SPEED TAP...

Page 22: ...1672 1373 1 31 2 0 1541 1418 1 35 2 0 1541 1418 1 35 Shaded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 4 Ton Cooler High Static Dri...

Page 23: ...68 Shaded area indicates air flow below 1500 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 5 Ton Cooler High Static Drive Models DRC0603W DRC0604W DRC0607W Horizontal Flo...

Page 24: ...dicates air flow below 1800 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 6 Ton Cooler High Static Drive Models DRC0723W DRC0724W DRC0727W Horizontal Flow SPEED TAP EXTER...

Page 25: ...icates air flow below 900 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 3 Ton Heat Pump Standard Static Drive Models DRH0364D and DRH0367D Down Flow Horizontal Flow SPEED...

Page 26: ...ded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 4 Ton Heat Pump Standard Static Drive Models DRH0484D and DRH0487D Down Flow Horizont...

Page 27: ...1128 1 07 Shaded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 5 Ton Heat Pump Standard Static Drive Models DRH0604D and DRH0607D Down...

Page 28: ...0 8 2083 979 0 91 0 8 2126 1066 0 99 1 0 2011 1033 0 96 1 0 2052 1113 1 03 T3 0 2 2226 892 0 69 T3 0 2 2211 885 0 68 0 4 2143 931 0 72 0 4 2128 938 0 73 0 6 2052 973 0 75 0 6 2034 988 0 76 0 8 1950 10...

Page 29: ...1233 0 91 2 0 1174 1233 0 91 Shaded area indicates air flow below 900 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 3 Ton Heat Pump High Static Drive Models DRH0363W DRH...

Page 30: ...1 18 2 0 1547 1289 1 23 2 0 1547 1289 1 23 Shaded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 4 Ton Heat Pump High Static Drive Model...

Page 31: ...1901 1390 1 57 Shaded area indicates air flow below 1500 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 5 Ton Heat Pump High Static Drive Models DRH0603W DRH0604W DRH0607...

Page 32: ...ates air flow below 1800 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating Max BPH 2 3 6 Ton Heat Pump High Static Drive Models DRH0723W DRH0724W DRH0727W Horizontal Flow SPE...

Page 33: ...8 7 57 3 62 2 60 70 1 7 1 5 47 5 53 2 50 60 9 6 8 7 1 7 1 5 59 5 64 1 60 70 10 1 15 4 3 14 4 20 0 5 10 6 15 4 3 0 5 14 9 20 10 6 15 4 3 16 20 0 5 11 3 15 4 3 0 5 16 6 20 18 2 20 4 3 23 5 25 0 5 18 8...

Page 34: ...9 6 8 7 72 5 79 3 80 80 1 7 1 5 62 6 70 3 70 80 9 6 8 7 1 7 1 5 74 6 81 2 80 90 23 5 23 5 35 35 9 6 8 7 33 1 32 2 45 45 1 7 1 5 25 2 25 0 35 35 9 6 8 7 1 7 1 5 34 8 33 7 45 45 23 5 23 5 35 35 9 6 8 7...

Page 35: ...0 3 5 0 6 31 7 35 8 08 15 3 5 11 6 15 0 6 8 68 15 3 5 0 6 12 2 15 8 51 15 3 5 12 9 15 0 6 9 26 15 3 5 0 6 13 6 15 14 5 15 3 5 18 9 20 0 6 15 3 20 3 5 0 6 19 7 20 20 5 25 3 5 24 9 25 0 6 21 3 25 3 5 0...

Page 36: ...40 8 50 50 35 7 39 7 45 45 9 6 8 7 47 7 50 6 50 60 1 7 1 5 37 8 41 6 45 45 9 6 8 7 1 7 1 5 49 8 52 4 50 60 48 7 54 7 50 60 9 6 8 7 60 7 65 6 70 70 1 7 1 5 50 8 56 6 60 60 9 6 8 7 1 7 1 5 62 8 67 5 70...

Page 37: ...32 3 36 3 45 45 9 6 8 7 44 3 47 2 50 50 1 7 1 5 34 4 38 2 45 45 9 6 8 7 1 7 1 5 46 4 49 1 50 50 45 3 51 4 50 60 9 6 8 7 57 3 62 2 60 70 1 7 1 5 47 5 53 2 50 60 9 6 8 7 1 7 1 5 59 5 64 1 60 70 58 1 66...

Page 38: ...15 3 5 0 6 14 7 20 14 5 15 3 5 18 9 20 0 6 15 3 20 3 5 0 6 19 7 20 20 5 25 3 5 24 9 25 0 6 21 3 25 3 5 0 6 25 7 30 26 6 30 3 5 30 9 35 0 6 27 3 30 3 5 0 6 31 7 35 38 6 40 3 5 43 45 0 6 39 3 40 3 5 0 6...

Page 39: ...9 6 8 7 1 7 1 5 44 8 45 7 50 50 46 5 50 5 50 60 9 6 8 7 56 1 59 2 60 60 1 7 1 5 48 2 52 0 50 60 9 6 8 7 1 7 1 5 57 8 60 7 60 70 59 5 65 6 60 70 9 6 8 7 69 1 74 3 70 80 1 7 1 5 61 2 67 1 70 70 9 6 8 7...

Page 40: ...80 80 82 0 88 9 90 90 9 6 8 7 91 6 97 6 100 100 1 7 1 5 83 7 90 4 90 100 9 6 8 7 1 7 1 5 93 3 99 1 100 100 105 115 110 125 9 6 8 7 114 124 125 125 1 7 1 5 106 116 110 125 9 6 8 7 1 7 1 5 116 125 125 1...

Page 41: ...15 4 3 0 5 16 9 20 19 6 20 4 3 23 9 25 0 5 20 1 25 4 3 0 5 24 4 25 27 1 30 4 3 31 4 35 0 5 27 6 30 4 3 0 5 31 9 35 34 7 35 4 3 39 40 0 5 35 2 40 4 3 0 5 39 5 40 42 2 45 4 3 46 5 50 0 5 42 7 45 4 3 0 5...

Page 42: ...1 7 1 5 32 4 32 2 45 45 9 6 8 7 1 7 1 5 42 0 40 9 50 50 43 7 45 7 50 50 9 6 8 7 53 3 54 4 60 60 1 7 1 5 45 4 47 2 50 50 9 6 8 7 1 7 1 5 55 0 55 9 60 60 56 7 60 7 60 70 9 6 8 7 66 3 69 4 70 70 1 7 1 5...

Page 43: ...0 5 35 5 40 38 2 40 4 3 42 5 45 0 5 38 7 40 4 3 0 5 43 45 45 7 50 4 3 50 60 0 5 46 2 50 4 3 0 5 50 5 60 12 2 15 3 5 15 7 20 0 6 12 8 15 3 5 0 6 16 3 20 18 2 20 3 5 21 7 25 0 6 18 8 20 3 5 0 6 22 3 25...

Page 44: ...3 80 80 9 6 8 7 1 7 1 5 82 0 87 0 90 90 83 5 91 5 90 100 9 6 8 7 93 1 100 100 110 1 7 1 5 85 2 93 0 90 100 9 6 8 7 1 7 1 5 94 8 102 100 110 107 118 110 125 9 6 8 7 116 127 125 150 1 7 1 5 108 120 110...

Page 45: ...16 5 20 18 4 20 3 5 21 9 25 0 6 19 20 3 5 0 6 22 5 25 24 4 25 3 5 27 9 30 0 6 25 30 3 5 0 6 28 5 30 30 4 35 3 5 33 9 35 0 6 31 35 3 5 0 6 34 5 35 36 5 40 3 5 40 40 0 6 37 1 40 3 5 0 6 40 6 45 48 5 50...

Page 46: ...ILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal duct covers 48 5 16 74 A 47 5 8 73 3 8 Mo...

Page 47: ...5 15 EH D S20 20 EH D S05 5 EH D S10 10 EH D S15 15 EH D S21 20 EH D S31 30 EH D S05 5 EH D S10 10 EH D S15 15 EH D S20 20 EH D S30 30 6 ton AC HP HI Static 3000 1950 1625 5 ton AC HI Static 5 ton HP...

Page 48: ...AT THE FACTORY AND BLACK WIRE TO COM TERMINAL FOR 208V SUPPLY POWER MOVE ORANGE WIRE FROM 240V TAP TO THE 208V TAP FUSE BLOCKS 1 2 ARE OPTIONAL IF OPTIONAL SAFETY EQUIPMENT SUCH AS A PHASE MONITOR FLO...

Page 49: ...RED WIRE ON THE JUMPER PLUG AND WIRE A NORMALLY CLOSED DRY CONTACT IN SERIES WITH THE CUT WIRE 24 VAC ALARM OUTPUT FROM OPTIONAL ECONOMIZER CONTROL MODULE NOTES 4 3 2 1 5 6A BLACK BLUE BLUE WITH PINK...

Page 50: ...S IN SERIES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT THE RED WIRE ON THE JUMPER PLUG AND WIRE A NORMALLY CLOSED DRY CONTACT IN SERI...

Page 51: ...OPTIONAL HIGH VOLTAGE OPTIONAL LOW VOLTAGE CHASSIS GROUND FIELD WIRING FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE EARTH GROUND COMPONENT LEGEND PB L1 GND L2 LINE VOLTAGE FB1 F1 F1 BK RD 208 230V 1PH 60Hz...

Page 52: ...LECTRIC HEAT IS INSTALLED PLUG IN NEW HARNESS FROM ELECTRIC HEATER KIT TR1 PRIMARY HIGH VOLTAGE CONNECTIONS ORANGE WIRE CONNECTED TO 240 460 575V TAP AT THE FACTORY AND BLACK WIRE TO COM TERMINAL FOR...

Page 53: ...ORS ONLY USE N E C CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS IF OPTIONAL ECONOMIZER IS INSTALLED REMOVE ECON PLM JUMPER AND PLUG IN NEW HARNESS FROM ECONOMIZER KIT IF OPTIONAL ELECTRIC HEAT I...

Page 54: ...54...

Page 55: ...55...

Page 56: ...the feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and...

Reviews: