APPENDIX A BLOWER PERFORMANCE TABLES - HEAT PUMP
3 Ton Heat Pump
High Static Drive
Models: DRH0363W, DRH0364W, DRH0367W
Down Flow
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN W.C.
SCFM RPM BHP SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
N W.C.
SCFM RPM BHP
T1
C
0.2
866 507 0.10
T6
H
0.2
-
-
-
0.4
713 603 0.12
0.4
-
-
-
0.6
569 679 0.14
0.6
1489 825 0.43
0.8
396 743 0.15
0.8
1397 886 0.46
1.0
218 780 0.16
1.0
1275 956 0.50
1.2
-
-
-
1.2
1173 1009 0.53
1.4
-
-
-
1.4
1087 1054 0.55
1.6
-
-
-
1.6
991 1104 0.58
1.8
-
-
-
1.8
914 1148 0.60
2.0
-
-
-
2.0
831 1187 0.62
T2
C
0.2
1170 597 0.18
T7
H
0.2
-
-
-
0.4
1083 662 0.20
0.4
-
-
-
0.6
928 742 0.22
0.6
-
-
-
0.8
808 805 0.24
0.8
-
-
-
1.0
712 865 0.26
1.0
1399 969 0.55
1.2
574 923 0.27
1.2
1287 1023 0.58
1.4
428 969 0.29
1.4
1191 1072 0.61
1.6
272 995 0.30
1.6
1111 1117 0.64
1.8
-
-
-
1.8
1020 1164 0.67
2.0
-
-
-
2.0
948 1207 0.69
T3
C
0.2
-
-
-
T8
H
0.2
-
-
-
0.4
-
-
-
0.4
-
-
-
0.6
1489 825 0.43
0.6
-
-
-
0.8
1397 886 0.46
0.8
-
-
-
1.0
1275 956 0.50
1.0
1476 977 0.62
1.2
1173 1009 0.53
1.2
1365 1039 0.66
1.4
1087 1054 0.55
1.4
1274 1084 0.68
1.6
991 1104 0.58
1.6
1186 1129 0.71
1.8
914 1148 0.60
1.8
1103 1175 0.74
2.0
831 1187 0.62
2.0
1019 1219 0.77
T4
C
0.2
-
-
-
T9
H
0.2
-
-
-
0.4
-
-
-
0.4
-
-
-
0.6
-
-
-
0.6
-
-
-
0.8
-
-
-
0.8
-
-
-
1.0
1476 977 0.62
1.0
-
-
-
1.2
1365 1039 0.66
1.2
1438 1048 0.72
1.4
1274 1084 0.68
1.4
1348 1099 0.76
1.6
1186 1129 0.71
1.6
1260 1143 0.79
1.8
1103 1175 0.74
1.8
1188 1184 0.82
2.0
1019 1219 0.77
2.0
1100 1228 0.85
T5
C
0.2
-
-
-
T10
H
0.2
-
-
-
0.4
-
-
-
0.4
-
-
-
0.6
-
-
-
0.6
-
-
-
0.8
-
-
-
0.8
-
-
-
1.0
-
-
-
1.0
-
-
-
1.2
-
-
-
1.2
-
-
-
1.4
1439 1112 0.82
1.4
1439 1112 0.82
1.6
1358 1157 0.85
1.6
1358 1157 0.85
1.8
1279 1195 0.88
1.8
1279 1195 0.88
2.0
1174 1233 0.91
2.0
1174 1233 0.91
Shaded area indicates air flow below 900 SCFM (300 SCFM/ton)
that is not recommended for High Stage cooling or heating
3 Ton Heat Pump
High Static Drive
Models: DRH0363W, DRH0364W, DRH0367W
Horizontal Flow
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN W.C.
SCFM RPM BHP SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
N W.C.
SCFM RPM BHP
T1
C
0.2
884 539 0.11
T6
H
0.2
-
-
-
0.4
728 641 0.13
0.4
-
-
-
0.6
581 722 0.15
0.6
-
-
-
0.8
404 790 0.16
0.8
1426 941 0.49
1.0
222 830 0.17
1.0
1301 1016 0.53
1.2
-
-
-
1.2
1197 1072 0.56
1.4
-
-
-
1.4
1109 1120 0.59
1.6
-
-
-
1.6
1011 1173 0.61
1.8
-
-
-
1.8
933 1220 0.64
2.0
-
-
-
2.0
848 1261 0.66
T2
C
0.2
1194 634 0.19
T7
H
0.2
-
-
-
0.4
1105 703 0.21
0.4
-
-
-
0.6
947 788 0.23
0.6
-
-
-
0.8
824 855 0.25
0.8
-
-
-
1.0
727 920 0.27
1.0
1428 1030 0.59
1.2
586 982 0.29
1.2
1313 1087 0.62
1.4
437 1031 0.31
1.4
1215 1139 0.65
1.6
278 1059 0.32
1.6
1134 1187 0.68
1.8
-
-
-
1.8
1041 1237 0.71
2.0
-
-
-
2.0
967 1282 0.73
T3
C
0.2
-
-
-
T8
H
0.2
-
-
-
0.4
-
-
-
0.4
-
-
-
0.6
-
-
-
0.6
-
-
-
0.8
1426 941 0.49
0.8
-
-
-
1.0
1301 1016 0.53
1.0
-
-
-
1.2
1197 1072 0.56
1.2
1393 1104 0.70
1.4
1109 1120 0.59
1.4
1300 1152 0.73
1.6
1011 1173 0.61
1.6
1210 1200 0.76
1.8
933 1220 0.64
1.8
1126 1248 0.79
2.0
848 1261 0.66
2.0
1040 1295 0.82
T4
C
0.2
-
-
-
T9
H
0.2
-
-
-
0.4
-
-
-
0.4
-
-
-
0.6
-
-
-
0.6
-
-
-
0.8
-
-
-
0.8
-
-
-
1.0
-
-
-
1.0
-
-
-
1.2
1393 1104 0.70
1.2
1467 1114 0.77
1.4
1300 1152 0.73
1.4
1375 1168 0.81
1.6
1210 1200 0.76
1.6
1286 1214 0.84
1.8
1126 1248 0.79
1.8
1212 1258 0.87
2.0
1040 1295 0.82
2.0
1122 1305 0.90
T5
C
0.2
-
-
-
T10
H
0.2
-
-
-
0.4
-
-
-
0.4
-
-
-
0.6
-
-
-
0.6
-
-
-
0.8
-
-
-
0.8
-
-
-
1.0
-
-
-
1.0
-
-
-
1.2
-
-
-
1.2
-
-
-
1.4
1468 1181 0.87
1.4
1468 1181 0.87
1.6
1386 1229 0.91
1.6
1386 1229 0.91
1.8
1305 1270 0.94
1.8
1305 1270 0.94
2.0
1198 1310 0.97
2.0
1198 1310 0.97
Shaded area indicates air flow below 900 SCFM (300 SCFM/ton)
that is not recommended for High Stage cooling or heating