APPENDIX A BLOWER PERFORMANCE TABLES - AC
5 Ton Cooler
Standard Static Drive
Models: DRC0601D and DRC0603D
Down Flow
Horizontal Flow
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN WC
SCFM RPM BHP
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN WC
SCFM RPM BHP
T1
0.2
1111 557 0.14
T1
0.2
1134 592 0.15
0.4
987 639 0.16
0.4
1007 680 0.17
0.6
816 734 0.19
0.6
832 781 0.20
0.8
714 795 0.20
0.8
729 846 0.22
1.0
589 859 0.22
1.0
602 913 0.23
T2
0.2
2079 886 0.72
T2
0.2
2121 942 0.76
0.4
2010 929 0.75
0.4
2051 989 0.80
0.6
1958 964 0.78
0.6
1998 1026 0.83
0.8
1919 994 0.80
0.8
1958 1057 0.86
1.0
1839 1033 0.84
1.0
1877 1099 0.89
T3
0.2
1731 761 0.43
T3
0.2
1766 809 0.46
0.4
1675 805 0.46
0.4
1709 856 0.49
0.6
1607 847 0.48
0.6
1640 901 0.51
0.8
1526 898 0.51
0.8
1557 956 0.55
1.0
1429 962 0.55
1.0
1458 1023 0.58
T4
0.2
2143 886 0.76
T4
0.2
2187 942 0.81
0.4
2064 929 0.80
0.4
2106 989 0.85
0.6
2010 964 0.83
0.6
2051 1026 0.88
0.8
1966 994 0.85
0.8
2006 1057 0.91
1.0
1903 1033 0.89
1.0
1942 1099 0.94
T5
0.2
2254 923 0.88
T5
0.2
2300 982 0.93
0.4
2178 964 0.92
0.4
2222 1025 0.98
0.6
2127 997 0.95
0.6
2170 1061 1.01
0.8
2078 1029 0.98
0.8
2120 1095 1.04
1.0
2026 1060 1.01
1.0
2067 1128 1.07
Shaded area indicates air flow below 1200 SCFM (300 SCFM/ton)
that is not recommended for High Stage cooling or heating
5 Ton Cooler
Standard Static Drive
Models:
DRC0604D and DRC0607D
Down Flow
Horizontal Flow
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN WC
SCFM RPM BHP
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN WC
SCFM RPM BHP
T1
0.2
1030 579 0.13
T1
0.2
1063 560 0.13
0.4
879 671 0.15
0.4
936 652 0.15
0.6
700 765 0.17
0.6
770 750 0.17
0.8
538 853 0.19
0.8
614 824 0.19
1.0
461 847 0.19
1.0
471 901 0.20
T2
0.2
1963 872 0.56
T2
0.2
1998 818 0.53
0.4
1861 927 0.60
0.4
1898 878 0.56
0.6
1775 972 0.62
0.6
1809 937 0.60
0.8
1688 1021 0.66
0.8
1715 992 0.64
1.0
1584 1080 0.69
1.0
1667 1036 0.67
T3
0.2
1804 820 0.46
T3
0.2
1846 771 0.43
0.4
1695 879 0.49
0.4
1744 832 0.47
0.6
1610 931 0.52
0.6
1643 897 0.50
0.8
1516 988 0.55
0.8
1585 944 0.53
1.0
1417 1053 0.59
1.0
1480 1010 0.56
T4
0.2
2037 897 0.62
T4
0.2
2073 839 0.58
0.4
1935 951 0.66
0.4
1977 896 0.62
0.6
1847 997 0.69
0.6
1883 952 0.66
0.8
1768 1039 0.72
0.8
1794 1006 0.69
1.0
1665 1093 0.75
1.0
1747 1049 0.72
T5
0.2
2110 921 0.68
T5
0.2
2141 856 0.63
0.4
2010 974 0.72
0.4
2052 912 0.67
0.6
1912 1024 0.76
0.6
1961 969 0.71
0.8
1841 1060 0.78
0.8
1870 1023 0.75
1.0
1749 1108 0.82
1.0
1794 1070 0.79
Shaded area indicates air flow below 1500 SCFM (300 SCFM/ton) that
is not recommended for High Stage cooling or heating