APPENDIX A BLOWER PERFORMANCE TABLES - HEAT PUMP
3 Ton Heat Pump
Standard Static Drive
Models: DRH0361D and DRH0363D
Down Flow
Horizontal Flow
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN WC
SCFM RPM BHP
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN WC
SCFM RPM BHP
T1
0.2
876
539 0.04
T1
0.2
903
556 0.04
0.4
-
- 0.00
0.4
-
- 0.00
0.6
-
- 0.00
0.6
-
- 0.00
0.8
-
- 0.00
0.8
-
- 0.00
1.0
-
- 0.00
1.0
-
- 0.00
T2
0.2
1494 754 0.36
T2
0.2
1540 778 0.37
0.4
1429 801 0.38
0.4
1473 826 0.39
0.6
1347 855 0.41
0.6
1389 882 0.42
0.8
1235 920 0.44
0.8
1274 948 0.45
1.0
1096 988 0.47
1.0
1130 1019 0.48
T3
0.2
1121 620 0.18
T3
0.2
1156 639 0.18
0.4
1013 690 0.20
0.4
1044 711 0.20
0.6
854
776 0.22
0.6
880
800 0.23
0.8
727
846 0.24
0.8
749
872 0.25
1.0
616
910 0.26
1.0
635
938 0.27
T4
0.2
1315 699 0.27
T4
0.2
1356 721 0.27
0.4
1223 755 0.29
0.4
1261 778 0.30
0.6
1106 826 0.31
0.6
1140 852 0.32
0.8
972
898 0.34
0.8
1002 926 0.35
1.0
861
961 0.37
1.0
888
991 0.38
T5
0.2
1599 788 0.42
T5
0.2
1649 812 0.44
0.4
1529 831 0.45
0.4
1577 857 0.46
0.6
1460 878 0.47
0.6
1505 905 0.48
0.8
1357 940 0.50
0.8
1399 970 0.52
1.0
1238 1004 0.54
1.0
1277 1035 0.55
Shaded area indicates air flow below 900 SCFM (300 SCFM/ton) that
is not recommended for High Stage cooling or heating
3 Ton Heat Pump
Standard Static Drive
Models: DRH0364D and DRH0367D
Down Flow
Horizontal Flow
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN WC
SCFM RPM BHP
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN WC
SCFM RPM BHP
T1
0.2
866
507 0.09
T1
0.2
884
539 0.10
0.4
713
603 0.11
0.4
728
641 0.11
0.6
569
679 0.12
0.6
581
722 0.13
0.8
396
743 0.13
0.8
404
790 0.14
1.0
218
780 0.14
1.0
222
830 0.15
T2
0.2
1379 649 0.23
T2
0.2
1407 690 0.25
0.4
1284 712 0.25
0.4
1310 757 0.27
0.6
1169 783 0.28
0.6
1193 832 0.30
0.8
1055 848 0.30
0.8
1077 901 0.32
1.0
949
901 0.32
1.0
968
957 0.34
T3
0.2
1170 597 0.15
T3
0.2
1194 634 0.16
0.4
1083 662 0.17
0.4
1105 703 0.18
0.6
928
742 0.19
0.6
947
788 0.20
0.8
808
805 0.20
0.8
824
855 0.21
1.0
712
865 0.22
1.0
727
920 0.23
T4
0.2
1379 649 0.23
T4
0.2
1407 690 0.25
0.4
1284 712 0.25
0.4
1310 757 0.27
0.6
1169 783 0.28
0.6
1193 832 0.30
0.8
1055 848 0.30
0.8
1077 901 0.32
1.0
949
901 0.32
1.0
968
957 0.34
T5
0.2
1476 675 0.28
T5
0.2
-
-
-
0.4
1388 744 0.31
0.4
1416 791 0.33
0.6
1322 794 0.33
0.6
1349 844 0.35
0.8
1178 869 0.36
0.8
1202 923 0.38
1.0
1076 923 0.38
1.0
1098 981 0.41
Shaded area indicates air flow below 1200 SCFM (300 SCFM/ton)
that is not recommended for High Stage cooling or heating