22
APPENDIX A BLOWER PERFORMANCE TABLES - AC
4 Ton Cooler
High Static Drive
Models: DRC0483W, DRC0484W, DRC0487W
Down Flow
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN W.C.
SCFM RPM BHP SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
N W.C.
SCFM RPM BHP
T1
C
0.2
949 553 0.12
T6
H
0.2
1991 870 0.59
0.4
773 658 0.14
0.4
1878 923 0.63
0.6
609 738 0.16
0.6
1777 974 0.66
0.8
414 822 0.18
0.8
1675 1029 0.70
1.0
-
-
-
1.0
1580 1083 0.73
1.2
-
-
-
1.2
1484 1136 0.77
1.4
-
-
-
1.4
1365 1194 0.81
1.6
-
-
-
1.6
1258 1243 0.84
1.8
-
-
-
1.8
1161 1288 0.87
2.0
-
-
-
2.0
1045 1341 0.91
T2
C
0.2
1512 715 0.31
T7
H
0.2
-
-
-
0.4
1380 783 0.34
0.4
1988 955 0.72
0.6
1260 855 0.37
0.6
1891 1003 0.75
0.8
1139 923 0.40
0.8
1791 1054 0.79
1.0
1009 988 0.42
1.0
1691 1110 0.83
1.2
893 1045 0.45
1.2
1606 1159 0.87
1.4
753 1113 0.48
1.4
1513 1211 0.91
1.6
511 1207 0.52
1.6
1389 1269 0.95
1.8
629 1159 0.50
1.8
1283 1314 0.98
2.0
-
-
-
2.0
1191 1357 1.02
T3
C
0.2
-
-
-
T8
H
0.2
-
-
-
0.4
1988 955 0.72
0.4
-
-
-
0.6
1891 1003 0.75
0.6
1999 1036 0.85
0.8
1791 1054 0.79
0.8
1900 1085 0.89
1.0
1691 1110 0.83
1.0
1802 1140 0.94
1.2
1606 1159 0.87
1.2
1714 1191 0.98
1.4
1513 1211 0.91
1.4
1623 1237 1.02
1.6
1389 1269 0.95
1.6
1519 1292 1.06
1.8
1283 1314 0.98
1.8
1407 1340 1.10
2.0
1191 1357 1.02
2.0
1313 1385 1.14
T4
C
0.2
-
-
-
T9
H
0.2
-
-
-
0.4
-
-
-
0.4
-
-
-
0.6
-
-
-
0.6
-
-
-
0.8
-
-
-
0.8
-
-
-
1.0
1914 1162 1.02
1.0
1914 1162 1.02
1.2
1827 1211 1.07
1.2
1827 1211 1.07
1.4
1747 1254 1.10
1.4
1747 1254 1.10
1.6
1655 1304 1.15
1.6
1655 1304 1.15
1.8
1542 1356 1.19
1.8
1542 1356 1.19
2.0
1444 1398 1.23
2.0
1444 1398 1.23
T5
C
0.2
-
-
-
T10
H
0.2
-
-
-
0.4
-
-
-
0.4
-
-
-
0.6
-
-
-
0.6
-
-
-
0.8
-
-
-
0.8
-
-
-
1.0
-
-
-
1.0
-
-
-
1.2
1932 1233 1.17
1.2
1932 1233 1.17
1.4
1849 1276 1.22
1.4
1849 1276 1.22
1.6
1770 1321 1.26
1.6
1770 1321 1.26
1.8
1672 1373 1.31
1.8
1672 1373 1.31
2.0
1541 1418 1.35
2.0
1541 1418 1.35
Shaded area indicates air flow below 1200 SCFM (300 SCFM/ton)
that is not recommended for High Stage cooling or heating
4 Ton Cooler
High Static Drive
Models: DRC0483W, DRC0484W, DRC0487W
Horizontal Flow
SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
IN W.C.
SCFM RPM BHP SPEED
TAP
EXTERNAL
STATIC
PRESSURE
(ESP),
N W.C.
SCFM RPM BHP
T1
C
0.2
991 541 0.12
T6
H
0.2
-
-
-
0.4
806 646 0.14
0.4
1928 895 0.61
0.6
652 737 0.16
0.6
1853 938 0.64
0.8
473 826 0.18
0.8
1758 989 0.67
1.0
-
-
-
1.0
1676 1038 0.70
1.2
-
-
-
1.2
1576 1100 0.75
1.4
-
-
-
1.4
1452 1165 0.79
1.6
-
-
-
1.6
1337 1220 0.83
1.8
-
-
-
1.8
1250 1268 0.86
2.0
-
-
-
2.0
1165 1314 0.89
T2
C
0.2
1547 698 0.30
T7
H
0.2
-
-
-
0.4
1451 754 0.32
0.4
-
-
-
0.6
1343 817 0.35
0.6
1965 970 0.73
0.8
1203 903 0.39
0.8
1885 1014 0.76
1.0
1076 972 0.42
1.0
1797 1063 0.80
1.2
964 1032 0.44
1.2
1707 1114 0.84
1.4
808 1115 0.48
1.4
1600 1180 0.88
1.6
696 1164 0.50
1.6
1483 1239 0.93
1.8
907 1206 0.52
1.8
1383 1291 0.97
2.0
460 1247 0.53
2.0
1293 1330 1.00
T3
C
0.2
-
-
-
T8
H
0.2
-
-
-
0.4
-
-
-
0.4
-
-
-
0.6
1965 970 0.73
0.6
-
-
-
0.8
1885 1014 0.76
0.8
1999 1041 0.86
1.0
1797 1063 0.80
1.0
1912 1090 0.90
1.2
1707 1114 0.84
1.2
1834 1133 0.93
1.4
1600 1180 0.88
1.4
1736 1190 0.98
1.6
1483 1239 0.93
1.6
1634 1251 1.03
1.8
1383 1291 0.97
1.8
1516 1304 1.07
2.0
1293 1330 1.00
2.0
1419 1350 1.11
T4
C
0.2
-
-
-
T9
H
0.2
-
-
-
0.4
-
-
-
0.4
-
-
-
0.6
-
-
-
0.6
-
-
-
0.8
-
-
-
0.8
-
-
-
1.0
-
-
-
1.0
-
-
-
1.2
1944 1154 1.02
1.2
1944 1154 1.02
1.4
1863 1205 1.06
1.4
1863 1205 1.06
1.6
1765 1265 1.11
1.6
1765 1265 1.11
1.8
1656 1318 1.16
1.8
1656 1318 1.16
2.0
1544 1366 1.20
2.0
1544 1366 1.20
T5
C
0.2
-
-
-
T10
H
0.2
-
-
-
0.4
-
-
-
0.4
-
-
-
0.6
-
-
-
0.6
-
-
-
0.8
-
-
-
0.8
-
-
-
1.0
-
-
-
1.0
-
-
-
1.2
-
-
-
1.2
-
-
-
1.4
1970 1223 1.16
1.4
1970 1223 1.16
1.6
1888 1273 1.21
1.6
1888 1273 1.21
1.8
1789 1328 1.26
1.8
1789 1328 1.26
2.0
1676 1382 1.32
2.0
1676 1382 1.32
Shaded area indicates air flow below 1200 SCFM (300 SCFM/ton)
that is not recommended for High Stage cooling or heating