APPENDIX A BLOWER PERFORMANCE TABLES - HEAT PUMP

6 Ton Cooler and Heat Pump

High Static Drive

Models: DRH0723W, DRH0724W, DRH0727W

Down Flow

SPEED 

TAP

EXTERNAL 

STATIC 

PRESSURE 

(ESP),  

IN W.C.

SCFM RPM BHP SPEED 

TAP

EXTERNAL 

STATIC 

PRESSURE 

(ESP),  

N W.C.

SCFM RPM BHP

T1

C

0.2

1384 673 0.22

T6

H

0.2

2615 1069 1.18

0.4

1262 751 0.25

0.4

2538 1108 1.23

0.6

1145 821 0.27

0.6

2448 1148 1.27

0.8

1017 899 0.30

0.8

2372 1195 1.32

1.0

884 968 0.32

1.0

2299 1246 1.38

1.2

756 1030 0.34

1.2

2224 1282 1.42

1.4

564 1069 0.36

1.4

2160 1326 1.47

1.6

442 1118 0.37

1.6

2092 1364 1.51

1.8

-

-

-

1.8

2021 1405 1.55

2.0

-

-

-

2.0

1946 1448 1.60

T2

C

0.2

2209 928 0.72

T7

H

0.2

2731 1111 1.34

0.4

2122 975 0.75

0.4

2655 1146 1.38

0.6

2013 1037 0.80

0.6

2570 1188 1.43

0.8

1925 1088 0.84

0.8

2483 1234 1.48

1.0

1848 1131 0.88

1.0

2410 1280 1.54

1.2

1762 1182 0.91

1.2

2337 1322 1.59

1.4

1675 1230 0.95

1.4

2290 1356 1.63

1.6

1584 1282 0.99

1.6

2219 1392 1.67

1.8

1486 1332 1.03

1.8

2156 1435 1.72

2.0

1399 1379 1.07

2.0

2085 1473 1.77

T3

C

0.2

2731 1111 1.34

T8

H

0.2

2815 1142 1.45

0.4

2655 1146 1.38

0.4

2741 1177 1.50

0.6

2570 1188 1.43

0.6

2668 1211 1.54

0.8

2483 1234 1.48

0.8

2585 1255 1.60

1.0

2410 1280 1.54

1.0

2507 1302 1.66

1.2

2337 1322 1.59

1.2

2436 1350 1.72

1.4

2290 1356 1.63

1.4

2369 1383 1.76

1.6

2219 1392 1.67

1.6

2320 1416 1.80

1.8

2156 1435 1.72

1.8

2255 1454 1.85

2.0

2085 1473 1.77

2.0

2188 1492 1.90

T4

C

0.2

2815 1142 1.45

T9

H

0.2

2903 1176 1.61

0.4

2741 1177 1.50

0.4

2829 1204 1.65

0.6

2668 1211 1.54

0.6

2769 1242 1.70

0.8

2585 1255 1.60

0.8

2681 1284 1.76

1.0

2507 1302 1.66

1.0

2601 1323 1.81

1.2

2436 1350 1.72

1.2

2530 1372 1.88

1.4

2369 1383 1.76

1.4

2466 1406 1.92

1.6

2320 1416 1.80

1.6

2424 1440 1.97

1.8

2255 1454 1.85

1.8

2356 1476 2.02

2.0

2188 1492 1.90

2.0

-

-

-

T5

C

0.2

2970 1200 1.74

T10

H

0.2

2970 1200 1.74

0.4

2905 1236 1.79

0.4

2905 1236 1.79

0.6

2841 1268 1.84

0.6

2841 1268 1.84

0.8

2759 1308 1.90

0.8

2759 1308 1.90

1.0

2681 1348 1.96

1.0

2681 1348 1.96

1.2

2606 1398 2.03

1.2

2606 1398 2.03

1.4

2550 1436 2.09

1.4

2550 1436 2.09

1.6

2485 1470 2.13

1.6

2485 1470 2.13

1.8

-

-

-

1.8

-

-

-

2.0

-

-

-

2.0

-

-

-

Shaded area indicates air flow below 1800 SCFM (300 SCFM/ton) 

that is not recommended for High Stage cooling or heating

Max BPH 2.3 

6 Ton Heat Pump

High Static Drive

Models: DRH0723W, DRH0724W, DRH0727W

Horizontal Flow

SPEED 

TAP

EXTERNAL 

STATIC 

PRESSURE 

(ESP),  

IN W.C.

SCFM RPM BHP SPEED 

TAP

EXTERNAL 

STATIC 

PRESSURE 

(ESP),  

N W.C.

SCFM RPM BHP

T1

C

0.2

1377 646 0.22

T6

H

0.2

2599 1065 1.18

0.4

1261 737 0.25

0.4

2545 1095 1.21

0.6

1130 818 0.27

0.6

2475 1130 1.25

0.8

1012 894 0.30

0.8

2400 1171 1.30

1.0

884 966 0.32

1.0

2333 1220 1.35

1.2

765 1026 0.34

1.2

2261 1271 1.41

1.4

638 1092 0.36

1.4

2216 1317 1.46

1.6

487 1113 0.37

1.6

2137 1372 1.52

1.8

-

-

-

1.8

2053 1421 1.57

2.0

-

2.0

1976 1461 1.62

T2

C

0.2

2205 917 0.71

T7

H

0.2

2690 1108 1.33

0.4

2137 957 0.74

0.4

2634 1140 1.37

0.6

2060 1007 0.78

0.6

2576 1165 1.40

0.8

1966 1062 0.82

0.8

2509 1206 1.45

1.0

1891 1128 0.87

1.0

2440 1251 1.50

1.2

1803 1184 0.92

1.2

2370 1297 1.56

1.4

1716 1234 0.95

1.4

2307 1348 1.62

1.6

1627 1283 0.99

1.6

2244 1390 1.67

1.8

1532 1336 1.03

1.8

2177 1441 1.73

2.0

1442 1386 1.07

2.0

2092 1484 1.78

T3

C

0.2

2690 1108 1.33

T8

H

0.2

2797 1137 1.45

0.4

2634 1140 1.37

0.4

2745 1163 1.48

0.6

2576 1165 1.40

0.6

2680 1194 1.52

0.8

2509 1206 1.45

0.8

2612 1231 1.57

1.0

2440 1251 1.50

1.0

2537 1272 1.62

1.2

2370 1297 1.56

1.2

2463 1316 1.68

1.4

2307 1348 1.62

1.4

2420 1357 1.73

1.6

2244 1390 1.67

1.6

2356 1397 1.78

1.8

2177 1441 1.73

1.8

2292 1444 1.84

2.0

2092 1484 1.78

2.0

2216 1491 1.90

T4

C

0.2

2797 1137 1.45

T9

H

0.2

2878 1159 1.59

0.4

2745 1163 1.48

0.4

2819 1189 1.63

0.6

2680 1194 1.52

0.6

2763 1218 1.67

0.8

2612 1231 1.57

0.8

2712 1250 1.71

1.0

2537 1272 1.62

1.0

2640 1288 1.76

1.2

2463 1316 1.68

1.2

2572 1330 1.82

1.4

2420 1357 1.73

1.4

2507 1375 1.88

1.6

2356 1397 1.78

1.6

2440 1426 1.95

1.8

2292 1444 1.84

1.8

2402 1460 2.00

2.0

2216 1491 1.90

2.0

-

-

-

T5

C

0.2

2961 1195 1.74

T10

H

0.2

2961 1195 1.74

0.4

2904 1226 1.78

0.4

2904 1226 1.78

0.6

2848 1253 1.82

0.6

2848 1253 1.82

0.8

2794 1276 1.85

0.8

2794 1276 1.85

1.0

2733 1315 1.91

1.0

2733 1315 1.91

1.2

2669 1358 1.97

1.2

2669 1358 1.97

1.4

2608 1394 2.02

1.4

2608 1394 2.02

1.6

2546 1441 2.09

1.6

2546 1441 2.09

1.8

2497 1483 2.15

1.8

2497 1483 2.15

2.0

-

-

-

2.0

-

-

-

Shaded area indicates air flow below 1800 SCFM (300 SCFM/ton) 

that is not recommended for High Stage cooling or heating

Max BPH 2.3 

Summary of Contents for DRC036

Page 1: ...pecified in this manual only licensed personnel should servise the equipment Improper installation adjustment servicing or repair of the equipment specified in this manual or attempting to install adj...

Page 2: ...ce CAUTION Sheet metal parts screws clips and similar items inherently have sharp edges and it is necessary that the installer and service personnel exercise caution WARNING Do not connect to or use a...

Page 3: ...ld also where applicable follow information presented in accepted industry guides such as the ASHRAE Handbooks The manufacturer assumes no responsibility for equipment installed in violation of any co...

Page 4: ...Installations Only To avoid possible property damage or personal injury the roof must have sufficient structural strength to carry the weight of the unit s and snow or water loads as required by local...

Page 5: ...ntenance and proper unit operation A clearance of 48 is recommended on all sides of the unit to facilitate possible parts replacement to allow service access and to insure proper ventilation and conde...

Page 6: ...struts mounted beneath unit base frame before setting unit on roof curb These struts are intended to protect unit base frame from fork lift damage Removal is accomplished by extracting the sheet meta...

Page 7: ...uit ampacity but less than or equal to the maximum overcurrent protection device DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE All line voltage connections must be made th...

Page 8: ...ols used by the service mechanic NOTE Refer to local codes for requirements These outlets can also be factory installed Units installed on Roof Tops Main power and low voltage wiring may enter the uni...

Page 9: ...nsions are shown in the roof curb installation manual If desired supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmissi...

Page 10: ...and install new filters Contractor Responsibility The installing contractor must be certain that All supply and return air ductwork is in place properly sealed and corresponds with installation instr...

Page 11: ...ce it is established that supply voltage will be maintained within the utilization range under all system conditions check and calculate if an unbalanced condition exists between phases Calculate perc...

Page 12: ...ng stage 1 operation Do not move wires YL and PU to the same taps Move WHITE WH wire from TB1 T2 to T3 to change blower speed during heating stage 1 operation Do not move wires WH and BR to the same t...

Page 13: ...rost O from board X X X X PU X 24V signal Range of AVAILABLE TAPS For wire color information and placement view DRC DRH Model Wiring PG 13 DRH OPERATION and WIRE RANGE CHART HI STATIC DRH OPERATIONS W...

Page 14: ...F 7 2 Switch any two leads of power supply at unit Single Point Power Block 7 3 Turn power to the unit ON 7 4 Perform step 7 again 8 Turn the temperature setting to the highest position stopping the u...

Page 15: ...then goes through the expansion device to the outdoor coil condenser on the cooling cycle where the liquid is evaporated and the vapor goes to the compressor The following figures show a schematic of...

Page 16: ...ly registers should be free of any obstructions The filters should be cleaned or replaced These few steps will help to keep the product up time to a maximum The Service section that follows should hel...

Page 17: ...dicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 3 Ton Cooler Standard Static Drive Models DRC0364D and DRC0367D Down Flow Horizontal Flow SPEED...

Page 18: ...0 1567 843 807 0 48 1 0 1599 84 859 0 52 Shaded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 4 Ton Cooler Standard Static Drive Models...

Page 19: ...1 07 Shaded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 5 Ton Cooler Standard Static Drive Models DRC0604D and DRC0607D Down Flow Hor...

Page 20: ...91 0 8 2125 89 1066 0 99 1 0 2011 1033 0 96 1 0 2051 78 1113 1 03 T3 65 0 2 2226 892 0 69 T3 65 0 2 2211 885 0 68 0 4 2143 931 0 72 0 4 2128 938 0 73 0 6 2052 973 0 75 0 6 2034 988 0 76 0 8 1950 1027...

Page 21: ...or heating APPENDIX A BLOWER PERFORMANCE TABLES AC 3 Ton Cooler High Static Drive Models DRC0363W DRC0364W DRC0367W Horizontal Flow SPEED TAP EXTERNAL STATIC PRESSURE ESP IN W C SCFM RPM BHP SPEED TAP...

Page 22: ...1672 1373 1 31 2 0 1541 1418 1 35 2 0 1541 1418 1 35 Shaded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 4 Ton Cooler High Static Dri...

Page 23: ...68 Shaded area indicates air flow below 1500 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 5 Ton Cooler High Static Drive Models DRC0603W DRC0604W DRC0607W Horizontal Flo...

Page 24: ...dicates air flow below 1800 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 6 Ton Cooler High Static Drive Models DRC0723W DRC0724W DRC0727W Horizontal Flow SPEED TAP EXTER...

Page 25: ...icates air flow below 900 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 3 Ton Heat Pump Standard Static Drive Models DRH0364D and DRH0367D Down Flow Horizontal Flow SPEED...

Page 26: ...ded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 4 Ton Heat Pump Standard Static Drive Models DRH0484D and DRH0487D Down Flow Horizont...

Page 27: ...1128 1 07 Shaded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 5 Ton Heat Pump Standard Static Drive Models DRH0604D and DRH0607D Down...

Page 28: ...0 8 2083 979 0 91 0 8 2126 1066 0 99 1 0 2011 1033 0 96 1 0 2052 1113 1 03 T3 0 2 2226 892 0 69 T3 0 2 2211 885 0 68 0 4 2143 931 0 72 0 4 2128 938 0 73 0 6 2052 973 0 75 0 6 2034 988 0 76 0 8 1950 10...

Page 29: ...1233 0 91 2 0 1174 1233 0 91 Shaded area indicates air flow below 900 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 3 Ton Heat Pump High Static Drive Models DRH0363W DRH...

Page 30: ...1 18 2 0 1547 1289 1 23 2 0 1547 1289 1 23 Shaded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 4 Ton Heat Pump High Static Drive Model...

Page 31: ...1901 1390 1 57 Shaded area indicates air flow below 1500 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 5 Ton Heat Pump High Static Drive Models DRH0603W DRH0604W DRH0607...

Page 32: ...ates air flow below 1800 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating Max BPH 2 3 6 Ton Heat Pump High Static Drive Models DRH0723W DRH0724W DRH0727W Horizontal Flow SPE...

Page 33: ...8 7 57 3 62 2 60 70 1 7 1 5 47 5 53 2 50 60 9 6 8 7 1 7 1 5 59 5 64 1 60 70 10 1 15 4 3 14 4 20 0 5 10 6 15 4 3 0 5 14 9 20 10 6 15 4 3 16 20 0 5 11 3 15 4 3 0 5 16 6 20 18 2 20 4 3 23 5 25 0 5 18 8...

Page 34: ...9 6 8 7 72 5 79 3 80 80 1 7 1 5 62 6 70 3 70 80 9 6 8 7 1 7 1 5 74 6 81 2 80 90 23 5 23 5 35 35 9 6 8 7 33 1 32 2 45 45 1 7 1 5 25 2 25 0 35 35 9 6 8 7 1 7 1 5 34 8 33 7 45 45 23 5 23 5 35 35 9 6 8 7...

Page 35: ...0 3 5 0 6 31 7 35 8 08 15 3 5 11 6 15 0 6 8 68 15 3 5 0 6 12 2 15 8 51 15 3 5 12 9 15 0 6 9 26 15 3 5 0 6 13 6 15 14 5 15 3 5 18 9 20 0 6 15 3 20 3 5 0 6 19 7 20 20 5 25 3 5 24 9 25 0 6 21 3 25 3 5 0...

Page 36: ...40 8 50 50 35 7 39 7 45 45 9 6 8 7 47 7 50 6 50 60 1 7 1 5 37 8 41 6 45 45 9 6 8 7 1 7 1 5 49 8 52 4 50 60 48 7 54 7 50 60 9 6 8 7 60 7 65 6 70 70 1 7 1 5 50 8 56 6 60 60 9 6 8 7 1 7 1 5 62 8 67 5 70...

Page 37: ...32 3 36 3 45 45 9 6 8 7 44 3 47 2 50 50 1 7 1 5 34 4 38 2 45 45 9 6 8 7 1 7 1 5 46 4 49 1 50 50 45 3 51 4 50 60 9 6 8 7 57 3 62 2 60 70 1 7 1 5 47 5 53 2 50 60 9 6 8 7 1 7 1 5 59 5 64 1 60 70 58 1 66...

Page 38: ...15 3 5 0 6 14 7 20 14 5 15 3 5 18 9 20 0 6 15 3 20 3 5 0 6 19 7 20 20 5 25 3 5 24 9 25 0 6 21 3 25 3 5 0 6 25 7 30 26 6 30 3 5 30 9 35 0 6 27 3 30 3 5 0 6 31 7 35 38 6 40 3 5 43 45 0 6 39 3 40 3 5 0 6...

Page 39: ...9 6 8 7 1 7 1 5 44 8 45 7 50 50 46 5 50 5 50 60 9 6 8 7 56 1 59 2 60 60 1 7 1 5 48 2 52 0 50 60 9 6 8 7 1 7 1 5 57 8 60 7 60 70 59 5 65 6 60 70 9 6 8 7 69 1 74 3 70 80 1 7 1 5 61 2 67 1 70 70 9 6 8 7...

Page 40: ...80 80 82 0 88 9 90 90 9 6 8 7 91 6 97 6 100 100 1 7 1 5 83 7 90 4 90 100 9 6 8 7 1 7 1 5 93 3 99 1 100 100 105 115 110 125 9 6 8 7 114 124 125 125 1 7 1 5 106 116 110 125 9 6 8 7 1 7 1 5 116 125 125 1...

Page 41: ...15 4 3 0 5 16 9 20 19 6 20 4 3 23 9 25 0 5 20 1 25 4 3 0 5 24 4 25 27 1 30 4 3 31 4 35 0 5 27 6 30 4 3 0 5 31 9 35 34 7 35 4 3 39 40 0 5 35 2 40 4 3 0 5 39 5 40 42 2 45 4 3 46 5 50 0 5 42 7 45 4 3 0 5...

Page 42: ...1 7 1 5 32 4 32 2 45 45 9 6 8 7 1 7 1 5 42 0 40 9 50 50 43 7 45 7 50 50 9 6 8 7 53 3 54 4 60 60 1 7 1 5 45 4 47 2 50 50 9 6 8 7 1 7 1 5 55 0 55 9 60 60 56 7 60 7 60 70 9 6 8 7 66 3 69 4 70 70 1 7 1 5...

Page 43: ...0 5 35 5 40 38 2 40 4 3 42 5 45 0 5 38 7 40 4 3 0 5 43 45 45 7 50 4 3 50 60 0 5 46 2 50 4 3 0 5 50 5 60 12 2 15 3 5 15 7 20 0 6 12 8 15 3 5 0 6 16 3 20 18 2 20 3 5 21 7 25 0 6 18 8 20 3 5 0 6 22 3 25...

Page 44: ...3 80 80 9 6 8 7 1 7 1 5 82 0 87 0 90 90 83 5 91 5 90 100 9 6 8 7 93 1 100 100 110 1 7 1 5 85 2 93 0 90 100 9 6 8 7 1 7 1 5 94 8 102 100 110 107 118 110 125 9 6 8 7 116 127 125 150 1 7 1 5 108 120 110...

Page 45: ...16 5 20 18 4 20 3 5 21 9 25 0 6 19 20 3 5 0 6 22 5 25 24 4 25 3 5 27 9 30 0 6 25 30 3 5 0 6 28 5 30 30 4 35 3 5 33 9 35 0 6 31 35 3 5 0 6 34 5 35 36 5 40 3 5 40 40 0 6 37 1 40 3 5 0 6 40 6 45 48 5 50...

Page 46: ...ILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal duct covers 48 5 16 74 A 47 5 8 73 3 8 Mo...

Page 47: ...5 15 EH D S20 20 EH D S05 5 EH D S10 10 EH D S15 15 EH D S21 20 EH D S31 30 EH D S05 5 EH D S10 10 EH D S15 15 EH D S20 20 EH D S30 30 6 ton AC HP HI Static 3000 1950 1625 5 ton AC HI Static 5 ton HP...

Page 48: ...AT THE FACTORY AND BLACK WIRE TO COM TERMINAL FOR 208V SUPPLY POWER MOVE ORANGE WIRE FROM 240V TAP TO THE 208V TAP FUSE BLOCKS 1 2 ARE OPTIONAL IF OPTIONAL SAFETY EQUIPMENT SUCH AS A PHASE MONITOR FLO...

Page 49: ...RED WIRE ON THE JUMPER PLUG AND WIRE A NORMALLY CLOSED DRY CONTACT IN SERIES WITH THE CUT WIRE 24 VAC ALARM OUTPUT FROM OPTIONAL ECONOMIZER CONTROL MODULE NOTES 4 3 2 1 5 6A BLACK BLUE BLUE WITH PINK...

Page 50: ...S IN SERIES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT THE RED WIRE ON THE JUMPER PLUG AND WIRE A NORMALLY CLOSED DRY CONTACT IN SERI...

Page 51: ...OPTIONAL HIGH VOLTAGE OPTIONAL LOW VOLTAGE CHASSIS GROUND FIELD WIRING FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE EARTH GROUND COMPONENT LEGEND PB L1 GND L2 LINE VOLTAGE FB1 F1 F1 BK RD 208 230V 1PH 60Hz...

Page 52: ...LECTRIC HEAT IS INSTALLED PLUG IN NEW HARNESS FROM ELECTRIC HEATER KIT TR1 PRIMARY HIGH VOLTAGE CONNECTIONS ORANGE WIRE CONNECTED TO 240 460 575V TAP AT THE FACTORY AND BLACK WIRE TO COM TERMINAL FOR...

Page 53: ...ORS ONLY USE N E C CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS IF OPTIONAL ECONOMIZER IS INSTALLED REMOVE ECON PLM JUMPER AND PLUG IN NEW HARNESS FROM ECONOMIZER KIT IF OPTIONAL ELECTRIC HEAT I...

Page 54: ...54...

Page 55: ...55...

Page 56: ...the feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and...

Reviews: