background image

11

Standard Static Drive Motors are set up to use motor 

speed taps T1-T5. Refer to Appendix A for blower 

performance at each speed tap.  

Fan speed for G (GR) is fixed at TB1-T1 and cannot be 

moved. 

Low Cool Y1, Yellow (YL) is movable and set to TB1-T1.

Low Heat W1, White (WH) is movable and set to TB1-T2.

High Cool Y2, Purple (PU) is movable and set to TB1-T3.

High Heat W2, Brown (BR) is movable and set to TB1-T3.

These wires can be moved together or separately and 

placed on any unoccupied terminal.

Note: YL can be moved to taps T2-T3 as long as YL does 

not share the tap with PU. WH can be moved to tap T3 as 

long as WH does not share the tap with BR.

High Static Motor Drive

Fan speed for G (GR), is fixed at TB1-T1 and cannot be 

moved.
Low Cool Y1, Yellow (YL) is movable and set to TB1-T1 
Low Heat W1, White (WH) is movable and set to TB1-T6
High Cool Y2, Purple (PU) is movable and set to TB1-T3
High Heat W2, Brown (BR) is movable and set to TB1-T8
These wires can be moved together or separately and 

placed on any unoccupied terminal.

Note: 

If operating the unit below 0.8” ESP move PU wire 

to T2.

Note: 

YL can be moved to taps T2-T3 as long as YL does 

not share tap with PU. WH can be moved to tap T7 as long 

as WH does not share the tap with BR
When Heat is called TB1-W1 will also call TB1-DH 

activating the second set of taps T6-T10. If cooling and 

heating is called at the same time heating will take priority 

and T6-T10 will be chosen by default.

Note: For proper operation Y2 and W2 should have a 

higher speed setting than the G, Y1 and W1 speed setting.

Utilization Voltage - 

The voltage of the line terminals 

of the equipment at which the equipment must give fully 

satisfactory performance. Once it is established that supply 

voltage will be maintained within the utilization range under 

all system conditions, check and calculate if an unbalanced 

condition exists between phases. Calculate percent voltage 

unbalance as follows: 

Three Phase Models Only

3) PERCENT VOLTAGE 

      UNBALANCE 

2) MAXIMUM VOLTAGE DEVIATIONS

FROM AVERAGE VOLTAGE

1) AVERAGE VOLTAGE

HOW TO USE THE FORMULA:

EXAMPLE: With voltage of 220, 216, and 213

1) Average Voltage = 220+216+213=649 / 3 = 216

2) Maximum Voltage Deviations from Average Voltage = 220 - 216 = 4

3) Percent Voltage Unbalance = 100 x 

  = 

=  1.8% 

Percent voltage unbalance MUST NOT exceed 2%

.

4

216

400

216

= 100 X

 

AIR FLOW ADJUSTMENTS

When the final adjustments are complete, the current 

draw of the motor should be checked and compared to 

the full load current rating of the motor. The amperage 

must not exceed the service factor stamped on the motor 

nameplate. 

If an economizer is installed, check the unit operating 

balance with the economizer at full outside air and at 

minimum outside air.

High stage airflow setting to be between 300 and 500 

CFM per ton, see Table below. For models with electric 

heat the total airflow must not be less than that required 

for operation of the electric heaters. See Appendix D for 

minimum airflow for specific electric heaters. 

NOTE: Never run CFM below 300 CFM per ton, 

evaporator freezing or poor unit performance is 

possible.

Minimum Nominal Maximum

DRC036 DRH036

900

1150

1500

DRC048 DRH048

1200

1500

2000

DRC060 DRH060

1500

1850

2500

DRC072 DRH072

1800

2200

3000

Model

High Stage Airflow Setting, CFM 

(without electric heat) 

Standard Static Drive Motor

Adjust the CFM for the unit by changing the position of 

the low voltage leads on the terminal block TB1. Refer to 

Appendix A for blower performance at each speed tap 

 

NOTE: If more than one lead is energized 

simultaneously, the motor will run at the higher 

numerical speed tap.

Summary of Contents for DRC036

Page 1: ...pecified in this manual only licensed personnel should servise the equipment Improper installation adjustment servicing or repair of the equipment specified in this manual or attempting to install adj...

Page 2: ...ce CAUTION Sheet metal parts screws clips and similar items inherently have sharp edges and it is necessary that the installer and service personnel exercise caution WARNING Do not connect to or use a...

Page 3: ...ld also where applicable follow information presented in accepted industry guides such as the ASHRAE Handbooks The manufacturer assumes no responsibility for equipment installed in violation of any co...

Page 4: ...Installations Only To avoid possible property damage or personal injury the roof must have sufficient structural strength to carry the weight of the unit s and snow or water loads as required by local...

Page 5: ...ntenance and proper unit operation A clearance of 48 is recommended on all sides of the unit to facilitate possible parts replacement to allow service access and to insure proper ventilation and conde...

Page 6: ...struts mounted beneath unit base frame before setting unit on roof curb These struts are intended to protect unit base frame from fork lift damage Removal is accomplished by extracting the sheet meta...

Page 7: ...uit ampacity but less than or equal to the maximum overcurrent protection device DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DATA PLATE All line voltage connections must be made th...

Page 8: ...ols used by the service mechanic NOTE Refer to local codes for requirements These outlets can also be factory installed Units installed on Roof Tops Main power and low voltage wiring may enter the uni...

Page 9: ...nsions are shown in the roof curb installation manual If desired supply and return duct connections to the unit may be made with flexible connections to reduce possible unit operating sound transmissi...

Page 10: ...and install new filters Contractor Responsibility The installing contractor must be certain that All supply and return air ductwork is in place properly sealed and corresponds with installation instr...

Page 11: ...ce it is established that supply voltage will be maintained within the utilization range under all system conditions check and calculate if an unbalanced condition exists between phases Calculate perc...

Page 12: ...ng stage 1 operation Do not move wires YL and PU to the same taps Move WHITE WH wire from TB1 T2 to T3 to change blower speed during heating stage 1 operation Do not move wires WH and BR to the same t...

Page 13: ...rost O from board X X X X PU X 24V signal Range of AVAILABLE TAPS For wire color information and placement view DRC DRH Model Wiring PG 13 DRH OPERATION and WIRE RANGE CHART HI STATIC DRH OPERATIONS W...

Page 14: ...F 7 2 Switch any two leads of power supply at unit Single Point Power Block 7 3 Turn power to the unit ON 7 4 Perform step 7 again 8 Turn the temperature setting to the highest position stopping the u...

Page 15: ...then goes through the expansion device to the outdoor coil condenser on the cooling cycle where the liquid is evaporated and the vapor goes to the compressor The following figures show a schematic of...

Page 16: ...ly registers should be free of any obstructions The filters should be cleaned or replaced These few steps will help to keep the product up time to a maximum The Service section that follows should hel...

Page 17: ...dicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 3 Ton Cooler Standard Static Drive Models DRC0364D and DRC0367D Down Flow Horizontal Flow SPEED...

Page 18: ...0 1567 843 807 0 48 1 0 1599 84 859 0 52 Shaded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 4 Ton Cooler Standard Static Drive Models...

Page 19: ...1 07 Shaded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 5 Ton Cooler Standard Static Drive Models DRC0604D and DRC0607D Down Flow Hor...

Page 20: ...91 0 8 2125 89 1066 0 99 1 0 2011 1033 0 96 1 0 2051 78 1113 1 03 T3 65 0 2 2226 892 0 69 T3 65 0 2 2211 885 0 68 0 4 2143 931 0 72 0 4 2128 938 0 73 0 6 2052 973 0 75 0 6 2034 988 0 76 0 8 1950 1027...

Page 21: ...or heating APPENDIX A BLOWER PERFORMANCE TABLES AC 3 Ton Cooler High Static Drive Models DRC0363W DRC0364W DRC0367W Horizontal Flow SPEED TAP EXTERNAL STATIC PRESSURE ESP IN W C SCFM RPM BHP SPEED TAP...

Page 22: ...1672 1373 1 31 2 0 1541 1418 1 35 2 0 1541 1418 1 35 Shaded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 4 Ton Cooler High Static Dri...

Page 23: ...68 Shaded area indicates air flow below 1500 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 5 Ton Cooler High Static Drive Models DRC0603W DRC0604W DRC0607W Horizontal Flo...

Page 24: ...dicates air flow below 1800 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 6 Ton Cooler High Static Drive Models DRC0723W DRC0724W DRC0727W Horizontal Flow SPEED TAP EXTER...

Page 25: ...icates air flow below 900 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 3 Ton Heat Pump Standard Static Drive Models DRH0364D and DRH0367D Down Flow Horizontal Flow SPEED...

Page 26: ...ded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 4 Ton Heat Pump Standard Static Drive Models DRH0484D and DRH0487D Down Flow Horizont...

Page 27: ...1128 1 07 Shaded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 5 Ton Heat Pump Standard Static Drive Models DRH0604D and DRH0607D Down...

Page 28: ...0 8 2083 979 0 91 0 8 2126 1066 0 99 1 0 2011 1033 0 96 1 0 2052 1113 1 03 T3 0 2 2226 892 0 69 T3 0 2 2211 885 0 68 0 4 2143 931 0 72 0 4 2128 938 0 73 0 6 2052 973 0 75 0 6 2034 988 0 76 0 8 1950 10...

Page 29: ...1233 0 91 2 0 1174 1233 0 91 Shaded area indicates air flow below 900 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 3 Ton Heat Pump High Static Drive Models DRH0363W DRH...

Page 30: ...1 18 2 0 1547 1289 1 23 2 0 1547 1289 1 23 Shaded area indicates air flow below 1200 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 4 Ton Heat Pump High Static Drive Model...

Page 31: ...1901 1390 1 57 Shaded area indicates air flow below 1500 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating 5 Ton Heat Pump High Static Drive Models DRH0603W DRH0604W DRH0607...

Page 32: ...ates air flow below 1800 SCFM 300 SCFM ton that is not recommended for High Stage cooling or heating Max BPH 2 3 6 Ton Heat Pump High Static Drive Models DRH0723W DRH0724W DRH0727W Horizontal Flow SPE...

Page 33: ...8 7 57 3 62 2 60 70 1 7 1 5 47 5 53 2 50 60 9 6 8 7 1 7 1 5 59 5 64 1 60 70 10 1 15 4 3 14 4 20 0 5 10 6 15 4 3 0 5 14 9 20 10 6 15 4 3 16 20 0 5 11 3 15 4 3 0 5 16 6 20 18 2 20 4 3 23 5 25 0 5 18 8...

Page 34: ...9 6 8 7 72 5 79 3 80 80 1 7 1 5 62 6 70 3 70 80 9 6 8 7 1 7 1 5 74 6 81 2 80 90 23 5 23 5 35 35 9 6 8 7 33 1 32 2 45 45 1 7 1 5 25 2 25 0 35 35 9 6 8 7 1 7 1 5 34 8 33 7 45 45 23 5 23 5 35 35 9 6 8 7...

Page 35: ...0 3 5 0 6 31 7 35 8 08 15 3 5 11 6 15 0 6 8 68 15 3 5 0 6 12 2 15 8 51 15 3 5 12 9 15 0 6 9 26 15 3 5 0 6 13 6 15 14 5 15 3 5 18 9 20 0 6 15 3 20 3 5 0 6 19 7 20 20 5 25 3 5 24 9 25 0 6 21 3 25 3 5 0...

Page 36: ...40 8 50 50 35 7 39 7 45 45 9 6 8 7 47 7 50 6 50 60 1 7 1 5 37 8 41 6 45 45 9 6 8 7 1 7 1 5 49 8 52 4 50 60 48 7 54 7 50 60 9 6 8 7 60 7 65 6 70 70 1 7 1 5 50 8 56 6 60 60 9 6 8 7 1 7 1 5 62 8 67 5 70...

Page 37: ...32 3 36 3 45 45 9 6 8 7 44 3 47 2 50 50 1 7 1 5 34 4 38 2 45 45 9 6 8 7 1 7 1 5 46 4 49 1 50 50 45 3 51 4 50 60 9 6 8 7 57 3 62 2 60 70 1 7 1 5 47 5 53 2 50 60 9 6 8 7 1 7 1 5 59 5 64 1 60 70 58 1 66...

Page 38: ...15 3 5 0 6 14 7 20 14 5 15 3 5 18 9 20 0 6 15 3 20 3 5 0 6 19 7 20 20 5 25 3 5 24 9 25 0 6 21 3 25 3 5 0 6 25 7 30 26 6 30 3 5 30 9 35 0 6 27 3 30 3 5 0 6 31 7 35 38 6 40 3 5 43 45 0 6 39 3 40 3 5 0 6...

Page 39: ...9 6 8 7 1 7 1 5 44 8 45 7 50 50 46 5 50 5 50 60 9 6 8 7 56 1 59 2 60 60 1 7 1 5 48 2 52 0 50 60 9 6 8 7 1 7 1 5 57 8 60 7 60 70 59 5 65 6 60 70 9 6 8 7 69 1 74 3 70 80 1 7 1 5 61 2 67 1 70 70 9 6 8 7...

Page 40: ...80 80 82 0 88 9 90 90 9 6 8 7 91 6 97 6 100 100 1 7 1 5 83 7 90 4 90 100 9 6 8 7 1 7 1 5 93 3 99 1 100 100 105 115 110 125 9 6 8 7 114 124 125 125 1 7 1 5 106 116 110 125 9 6 8 7 1 7 1 5 116 125 125 1...

Page 41: ...15 4 3 0 5 16 9 20 19 6 20 4 3 23 9 25 0 5 20 1 25 4 3 0 5 24 4 25 27 1 30 4 3 31 4 35 0 5 27 6 30 4 3 0 5 31 9 35 34 7 35 4 3 39 40 0 5 35 2 40 4 3 0 5 39 5 40 42 2 45 4 3 46 5 50 0 5 42 7 45 4 3 0 5...

Page 42: ...1 7 1 5 32 4 32 2 45 45 9 6 8 7 1 7 1 5 42 0 40 9 50 50 43 7 45 7 50 50 9 6 8 7 53 3 54 4 60 60 1 7 1 5 45 4 47 2 50 50 9 6 8 7 1 7 1 5 55 0 55 9 60 60 56 7 60 7 60 70 9 6 8 7 66 3 69 4 70 70 1 7 1 5...

Page 43: ...0 5 35 5 40 38 2 40 4 3 42 5 45 0 5 38 7 40 4 3 0 5 43 45 45 7 50 4 3 50 60 0 5 46 2 50 4 3 0 5 50 5 60 12 2 15 3 5 15 7 20 0 6 12 8 15 3 5 0 6 16 3 20 18 2 20 3 5 21 7 25 0 6 18 8 20 3 5 0 6 22 3 25...

Page 44: ...3 80 80 9 6 8 7 1 7 1 5 82 0 87 0 90 90 83 5 91 5 90 100 9 6 8 7 93 1 100 100 110 1 7 1 5 85 2 93 0 90 100 9 6 8 7 1 7 1 5 94 8 102 100 110 107 118 110 125 9 6 8 7 116 127 125 150 1 7 1 5 108 120 110...

Page 45: ...16 5 20 18 4 20 3 5 21 9 25 0 6 19 20 3 5 0 6 22 5 25 24 4 25 3 5 27 9 30 0 6 25 30 3 5 0 6 28 5 30 30 4 35 3 5 33 9 35 0 6 31 35 3 5 0 6 34 5 35 36 5 40 3 5 40 40 0 6 37 1 40 3 5 0 6 40 6 45 48 5 50...

Page 46: ...ILITIES RETURN 11 X 25 SUPPLY 12 X 17 Horizontal Discharge Vertical Discharge NOTE Refer to IOD 7082 included in the literature pack for installing horizontal duct covers 48 5 16 74 A 47 5 8 73 3 8 Mo...

Page 47: ...5 15 EH D S20 20 EH D S05 5 EH D S10 10 EH D S15 15 EH D S21 20 EH D S31 30 EH D S05 5 EH D S10 10 EH D S15 15 EH D S20 20 EH D S30 30 6 ton AC HP HI Static 3000 1950 1625 5 ton AC HI Static 5 ton HP...

Page 48: ...AT THE FACTORY AND BLACK WIRE TO COM TERMINAL FOR 208V SUPPLY POWER MOVE ORANGE WIRE FROM 240V TAP TO THE 208V TAP FUSE BLOCKS 1 2 ARE OPTIONAL IF OPTIONAL SAFETY EQUIPMENT SUCH AS A PHASE MONITOR FLO...

Page 49: ...RED WIRE ON THE JUMPER PLUG AND WIRE A NORMALLY CLOSED DRY CONTACT IN SERIES WITH THE CUT WIRE 24 VAC ALARM OUTPUT FROM OPTIONAL ECONOMIZER CONTROL MODULE NOTES 4 3 2 1 5 6A BLACK BLUE BLUE WITH PINK...

Page 50: ...S IN SERIES PLUG IN JUMPER PLUG AT THE LAST SAFETY DEVICE INSTALLED IF A THIRD PARTY SAFETY DEVICE IS FIELD INSTALLED CUT THE RED WIRE ON THE JUMPER PLUG AND WIRE A NORMALLY CLOSED DRY CONTACT IN SERI...

Page 51: ...OPTIONAL HIGH VOLTAGE OPTIONAL LOW VOLTAGE CHASSIS GROUND FIELD WIRING FACTORY WIRING HIGH VOLTAGE LOW VOLTAGE EARTH GROUND COMPONENT LEGEND PB L1 GND L2 LINE VOLTAGE FB1 F1 F1 BK RD 208 230V 1PH 60Hz...

Page 52: ...LECTRIC HEAT IS INSTALLED PLUG IN NEW HARNESS FROM ELECTRIC HEATER KIT TR1 PRIMARY HIGH VOLTAGE CONNECTIONS ORANGE WIRE CONNECTED TO 240 460 575V TAP AT THE FACTORY AND BLACK WIRE TO COM TERMINAL FOR...

Page 53: ...ORS ONLY USE N E C CLASS 2 WIRE FOR ALL LOW VOLTAGE FIELD CONNECTIONS IF OPTIONAL ECONOMIZER IS INSTALLED REMOVE ECON PLM JUMPER AND PLUG IN NEW HARNESS FROM ECONOMIZER KIT IF OPTIONAL ELECTRIC HEAT I...

Page 54: ...54...

Page 55: ...55...

Page 56: ...the feedback page PRODUCT REGISTRATION Thank you for your recent purchase Though not required to get the protection of the standard warranty registering your product is a relatively short process and...

Reviews: