background image

e

leCTrICal

 I

nsTallaTIon

Pre-Construction

The Rebel unit comes equipped with a Microtech III controller 

and can be used for sites that are still under construction. The 

following conditions must be met.

1 . 

Ductwork has to be installed.  The fan proving switch 

and furnace might not run correctly without the specified 

external static pressure

2 .  Filters must be installed .

3 . 

Follow furnace commissioning instructions found in the 

furnace section.

4 . 

After substantial completion of the construction process 

the unit is to be thoroughly cleaned. Special attention 

should be paid to the indoor DX coil and the furnace.  

Filters should be changed

5 . 

Furnace operation, rate, and temperature rise should be 

re-verified. See instructions found in the furnace section.

Lab Pressurization Applications

1 . 

Install a “T” fitting with a leak-tight removable cap in each 

tube near the sensor fitting. This facilitates connecting a 

manometer or pressure gauge if testing is required.

2 . 

Use different colored tubing for the controlled space 

pressure (high) and reference pressure (low) taps, or tag 

the tubes.

3 . 

Regardless whether the controlled space is positive or 

negative with respect to its reference, locate the high 

pressure tap in the controlled space (the setpoint can be 

set between -0.2" and 0.2" wc).

4 . 

Locate the reference pressure (low) tap in the area 

surrounding the controlled space. Not locating the 

reference tap to the sensor results in unsatisfactory 

operation .

5 . 

Locate both taps so they are not influenced by any source 

of moving air (velocity pressure). These sources may 

include air diffusers or doors between the high and low 

pressure areas .

6 . 

Route the building tap tube between the curb and the 

supply duct and feed it into the unit through the knockout 

in the bottom of the control panel.

7 . 

Connect the tube to the (high) fitting for sensor SPS2. 

Electrostatic Discharge (ESD) 

Disconnect Power to the Rebel Rooftop Unit prior to 
inspecting and/or repairing .

When inspecting / repairing Rebel Rooftop units the technician 

or building owner must take precautions to ground themselves to 

the unit.  This will prevent them from damaging the circuit boards 

mounted inside the inverter box and main control panel.
Electrostatic Discharge (ESD) can damage components in a 

manner that is not always readably detectable.  A static potential 

can easily be generated on a person that reaches 25 kVolts.  If 

this potential is discharged into one of the unit’s circuit boards it 

can degrade part of the current carrying conductors inside.  This 

is the conceptual equivalent of reducing 16 gage wires to 18.  

The component will still operate initially, but will have a much 

shorter life span due to overheating of the conductor.
In order to prevent ESD from the technician to the unit they must 

both be at the same potential.  First the technician must ground 

themselves to the unit; this can be achieved by touching any 

galvanized (not painted) section of the unit.  The unit’s base 

rail and refrigerant piping are both reliable options.  The next 

step is to attach a grounded wrist or ankle strap to the copper 

tubing.  This grounding strap must have direct contact with the 

technician’s skin.  Once this has been done the technician is free 

to work on electrical components in side the unit.
Although ESD is partially dependent on humidity, at levels above 

50% it is a greatly reduced risk, good practices should always be 

observed.

All Units

Wiring must comply with all applicable codes and ordinances. 

The warranty is voided if wiring is not in accordance with these 

specifications.
According to the National Electrical Code, a disconnecting 

means shall be located within sight of and readily accessible 

from the air conditioning equipment. The unit can be ordered 

with an optional factory mounted disconnect switch. This switch 

is not fused. Power leads must be over-current protected at the 

point of distribution. The maximum rated overcurrent protection 

device (MROPD) value appears on the unit nameplate.
All units are provided with internal power wiring for single point 

power connection. The power block or an optional disconnect 

switch is located within the main control panel. Field power 

leads are brought into the unit through knockouts in the bottom 

of the main control panel (see 

Figure 7

 and also 

Table 7

). 

Refer to the unit nameplate to determine the number of power 

connections.

  

NOTE: 

To wire entry points, refer to certified drawings for 

dimensions .

 DANGER

Hazardous voltage . Can cause severe injury or 
death .

 

Disconnect  electric  power  before  servicing  equipment. 

More  than  one  disconnect  may  be  required  to  de-

energize the unit.

IM 1125-6 • REBEL ROOFTOPS 12

 

www.DaikinApplied.com

e

leCTrICal

 I

nsTallaTIon

DOT-ITB-21-8041-AC

FPID: 437300-3-7B-01

Summary of Contents for DPS003

Page 1: ...1125 6 Group Applied Air Systems Part Number IM 1125 Date September 2014 Rebel Commercial Packaged Rooftop Systems Heating and Cooling Models DPS003 015A R 410A Refrigerant MicroTech III Unit Control...

Page 2: ...p Procedures 33 Service 34 Maintenance 34 Optional Hot Water Heat 43 Hot Water Heater Design 43 Optional Energy Recovery Wheel 44 Optional Outdoor Air Monitor 46 Thermal Dispersion Airflow Measurement...

Page 3: ...number electrical characteristics and refrigerant charge Hazard Identification Information Rooftop unit control configuration Manual bulletin number BACnet IP Comm Module IM 916 BACnet Integration IM...

Page 4: ...imum clearances around the unit and control panel Ventilation Clearance Below are minimum ventilation clearance recommendations The system designer must consider each application and provide adequate...

Page 5: ...ing or twisting of the machine If building construction allows sound and vibration into the occupied space locate the unit over a non critical area It is the responsibility of the system designer to m...

Page 6: ...b Detail A A 2 4 Nailer A A 2 0 Typ 14 0 or 24 0 4 0 3 9 28 55 Inside 9 69 Inside 28 69 Inside 44 38 Inside 57 5 Inside 19 1 9 5 Inside Supply Opening Return Opening Electrical Entrance 2 0 3 9 6 4 Ro...

Page 7: ...4 Nailer A A 2 0 Typ 4 0 14 0 or 24 0 34 88 Inside 48 38 Inside 81 5 Inside 13 5 Inside 30 5 Inside Supply Opening Return Opening Electrical Entrance 24 25 2 0 3 4 6 9 8 8 Roof Curb for ERW B Cabinet...

Page 8: ...Do not use a forklift to lift or maneuver the unit Failure to use a load rated crane or hoist assembly to lift or maneuver the unit can cause severe personal injury and property damage WARNING Use all...

Page 9: ...onnel Figure 5 Condensate Drain Connection Damper Assemblies The optional damper assemblies described in this section are ordered with factory installed actuators and linkages The following sections d...

Page 10: ...ow are pressure tap location and installation recommendations The installation must comply with local code requirements 1 Install a tee fitting with a leak tight removable cap in each tube near the se...

Page 11: ...connecting the reference tap to the sensor results in unsatisfactory operation 6 Use an outdoor static pressure tip Dwyer A306 or equivalent to minimize the adverse effects of wind Place some type of...

Page 12: ...r that is not always readably detectable A static potential can easily be generated on a person that reaches 25 kVolts If this potential is discharged into one of the unit s circuit boards it can degr...

Page 13: ...who are familiar with working on live equipment A representative of the owner or the operator of the equipment should be present during start up to receive instructions in the operation care and adjus...

Page 14: ...0 1 8 0 9 6 15 0 13 6 6 8 89 0 0 0 0 0 0 0 143 8 130 0 65 0 0 0 0 0 0 0 JT1G NA 1 2 0 1 8 0 9 7 5 11 9 10 8 5 4 68 0 8 6 7 8 3 9 143 8 130 0 65 0 67 5 73 7 37 1 JT1G JT71G 2 2 0 1 8 0 9 10 10 0 9 0 4...

Page 15: ...there are some consistent characteristics All units a single circuit with a single or tandem compressor All units use an electronic expansion valve EVI and a start up by pass solenoid valve SVB Figur...

Page 16: ...ronic expansion valve CV Check Valve REC Refrigerant Receiver IDF Indoor fan ODF Outdoor fan COMP1 Inverter compressor COMP2 Fixed speed compressor 7 1 2 thru 15 ton only SVR Bypass solenoid valve RHV...

Page 17: ...igerant are required inside the system during Mechanical Cooling or defrost and Mechanical Heating This is the results of the charge in operating temperatures in Cooling and Heating Mode The receiver...

Page 18: ...gure 15 Oil Separator Figure 16 Secondary Oil Separator Check Valve All Rebel Units will have check valves on each of the compressor discharge lines On large cabinet units 7 15 Tons two valves one on...

Page 19: ...any possible debris from entering critical components expansion valves compressors etc These screens are not bi direction and must be installed in a specific direction if replaced Please be aware that...

Page 20: ...ed for Standard during heating mode the EVI will modulate to fully open and remain in this position When configured for heating mode the EVI will modulate to maintain the Subcooling Set Point Figure 2...

Page 21: ...crease compressor life by preventing it from running outside of the operating envelope Suction Refrigerant Temperature All Rebel units will have a Suction Refrigerant Temperature Sensor SRT This senso...

Page 22: ...ill be unavailable and the supplemental heat will ramp stage up to meet the DAT set point Defrost Defrost is a temporary and infrequent period during normal heating operations on Rebel heat pumps The...

Page 23: ...to be over cooled by the DX coil Hot gas from the unit condenser will be routed to an indoor coil downstream of the DX coil to reheat the air Hot gas reheat valves Figure 25 will control how much hot...

Page 24: ...mediately transitions to Cooling if Dehumidification is initiated in Economizer state Dehumidification Termination Dehumidification is terminated if the selected variable Relative Humidity or Dew Poin...

Page 25: ...Fan Only state no sensible cooling is required but dehumidification mode will still be enabled if the dew point or humidity sensor is not satisfied Reheat set point varies from a maximum value defaul...

Page 26: ...Figure 27 Modulating Hot Gas Reheat Schematic IM 1125 6 REBEL ROOFTOPS 26 www DaikinApplied com Optional Modulating Hot Gas Reheat DOT ITB 21 8041 AC FPID 437300 3 7B 01...

Page 27: ...ages Heat 1 Heat 2 Heat 3 Heat 4 kW MBh Delta T1 Min cfm kW MBh Delta T1 Min cfm kW MBh Delta T1 Min cfm kW MBh Delta T1 Min cfm 003 1200 2 6 20478 15 8 316 12 40956 31 6 632 18 61434 47 4 948 004 160...

Page 28: ...apacities Figure 28 Gas Heat Section Figure 29 Field Gas Heat Connections Data Unit Size 003 006 007 015 Low Heat Med Heat High Heat Low Heat Med Heat High Heat Heating Input MBh 80 120 160 200 300 40...

Page 29: ...its equipped with gas heating must not be operated in an atmosphere contaminated with chemicals which will corrode the unit such as halogenated hydrocarbons chlorine cleaning solvents refrigerants swi...

Page 30: ...fan compartment between the furnace heat exchanger and the fan To access the switch the fan compartment door must be opened Be sure all power to the unit is disconnected before opening the fan compart...

Page 31: ...30 245 500 760 1450 2300 4100 8300 50 56 115 215 440 670 1270 2000 3600 7400 60 50 105 195 400 610 1150 1850 3250 6800 70 46 96 180 370 560 1050 1700 3000 6200 80 53 90 170 350 530 990 1600 2800 5800...

Page 32: ...rner output to match the unit discharge air temperature setting LP Conversion Staged Furnace Only Convert the furnace in this unit using the liquefied petroleum LP gas valve spring and burner nozzles...

Page 33: ...ck the burner fan wheel for binding rubbing or loose setscrews 2 Check power 3 Purge the gas lines 4 Leak check Using a rich soap water mixture and a brush check the gas lines for leaks Correct all le...

Page 34: ...enience Have this system inspected at regular intervals by a trained and experienced service technician The following service intervals are typical for average situations but will have to be adjusted...

Page 35: ...ied control OK 1 Flash Combustion fan motor energized pressure switch open 2 Flashes Combustion fan motor off pressure switch closed 3 Flashes Ignition lockout from too many trials 4 Flashes Ignition...

Page 36: ...Module for Modulating Gas Furnace Figure 37 Typical Modulating Gas Furnace Electrical Schematic with Sensor IM 1125 6 REBEL ROOFTOPS 36 www DaikinApplied com Optional Gas Heat DOT ITB 21 8041 AC FPID...

Page 37: ...formation example Description C Furnace series or model name for example C cabinet series CAb 400 Furnace size in 1000 s of BTU for example 400 kBTU nAt or LP Burner fuel type for example natural gas...

Reviews: