background image

     

Gas Pressure Requirements

The pressure furnished to the main gas valve must not exceed 

13.9" wc. When the supply pressure is above 13.9" wc, a high 

pressure regulator must precede the appliance gas pressure 

regulator. The inlet gas pressure must not exceed the maximum 

pressure rating of the high pressure regulator, and the outlet 

pressure must furnish gas to the appliance pressure regulator 

within the pressure range mentioned above.

Gas Piping 

Gas piping must be sized to provide the minimum required 

pressure at the burner when the burner is operating at maximum 

input. Consult your local utility on any questions on gas pressure 

available, allowing piping pressure drops, and local piping 

requirements .

The proper size piping must be run from the meter to the gas 

burner without reductions. Undersized piping will result in 

inadequate pressure at the burner. The pressure will be at its 

lowest when it is needed the most, at times of maximum demand. 

Therefore, it can cause intermittent hard-to-find problems because 

the problem may have left before the service technician has 

arrived. Avoid the use of bushings wherever possible.
Remove all burrs and obstructions from pipe. Do not bend pipe; 

use elbows or other pipe fittings to properly locate pipe.
A drip leg and a manual shut-off must be installed in the vertical 

line before each burner such that it will not freeze. Install unions 

so gas train components can be removed for service. All pipe 

threads must have a pipe dope which is resistant to the action of 

Propane gas. After installation, pressurize the piping as required 

and test all joints for tightness with a rich soap solution. Any 

bubbling is considered a leak and must be eliminated. Do not use 

a match or flame to locate leaks.   

    

Auxiliary Limit Switch Function

The auxiliary limit switch is a manually resetable switch and is 

designed to trip in the event of a supply fan failure. It should not 

trip during any other conditions. In the event of a blockage to the 

return or discharge air, the primary limit, which is an automatic-

reset type, is designed to trip.
Should there be a fan failure which results in the tripping of the 

auxiliary limit, the limit must be manually reset to resume function 

of the unit. 
On the Rebel A cabinet (3-6 ton), the auxiliary limit resides in 

the fan compartment between the furnace heat exchanger and 

the fan. To access the switch, the fan compartment door must 

be opened. Be sure all power to the unit is disconnected before 

opening the fan compartment door.

Figure 31: 3–6 Ton—Auxiliary Limit Switch 

        

Once the fan compartment door is opened the auxiliary limit 

switch can be found behind the supply fan on a bracket mounted 

to the cabinet wall.  
Depressing the red button on the auxiliary limit will reset the limit 

and allow the furnace to be powered. The furnace should now 

respond to a call for heat.

Figure 32: 7–15 Ton—Auxiliary Limit Switch  

      

Again, the red button must be depressed in order to reset the limit 

and allow the furnace to be powered.

 DANGER

If  you  do  not  follow  these  instructions  exactly,  a  fire  or 

explosion may result causing property damage, personal 
injury, or loss of life .

A .

 This appliance does not have a pilot. It is equipped with an 

ignition device which automatically lights the burner. Do not 

try to light the burner by hand.

B .

  Before  operating,  smell  all  around  the  appliance  area  for 

gas. Be sure to smell next to the floor because some gas is 

heavier than air and will settle on the floor.

WHAT TO DO IF YOU SMELL GAS:

• 

Do not try to light any appliance.

• 

Do not touch any electric switch, do not use any phone in 

your building. 

• 

Immediately  call  your  gas  supplier  from  a  neighbor’s 

phone. Follow the gas supplier’s instructions.

• 

If  you  cannot  reach  your  gas  supplier,  call  the  fire 

department .

C .

 Use only your hand to push in or turn the gas control knob. 

Never use tools. If the knob will not push in or turn by hand, 

don’t try to repair it, call a qualified service technician. Force 

or attempted repair may result in a fire or explosion.

D .

 Do not use this appliance if any part has been under water. 

Immediately call a qualified service technician to inspect the 

appliance and to replace any part of the control system and 

any gas control which has been under water.

 DANGER

The spark ignitor and ignition control are high voltage. Keep 

hands  and  tools  away  to  prevent  electrical  shock.  Shut  off 

electrical power before servicing any of the controls. Failure 

to adhere to this warning can result in personal injury or death.

View of supply fan 
with aux limit behind, 
mounted on a bracket 
off the cabinet wall

The auxiliary limit on the 
B cabinet (7-15 ton) is in 
the furnace compartment 
(vestibule) above the furnace

IM 1125-6 • REBEL ROOFTOPS 30

 

www.DaikinApplied.com

o

pTIonal

 g

as

 h

eaT

DOT-ITB-21-8041-AC

FPID: 437300-3-7B-01

Summary of Contents for DPS003

Page 1: ...1125 6 Group Applied Air Systems Part Number IM 1125 Date September 2014 Rebel Commercial Packaged Rooftop Systems Heating and Cooling Models DPS003 015A R 410A Refrigerant MicroTech III Unit Control...

Page 2: ...p Procedures 33 Service 34 Maintenance 34 Optional Hot Water Heat 43 Hot Water Heater Design 43 Optional Energy Recovery Wheel 44 Optional Outdoor Air Monitor 46 Thermal Dispersion Airflow Measurement...

Page 3: ...number electrical characteristics and refrigerant charge Hazard Identification Information Rooftop unit control configuration Manual bulletin number BACnet IP Comm Module IM 916 BACnet Integration IM...

Page 4: ...imum clearances around the unit and control panel Ventilation Clearance Below are minimum ventilation clearance recommendations The system designer must consider each application and provide adequate...

Page 5: ...ing or twisting of the machine If building construction allows sound and vibration into the occupied space locate the unit over a non critical area It is the responsibility of the system designer to m...

Page 6: ...b Detail A A 2 4 Nailer A A 2 0 Typ 14 0 or 24 0 4 0 3 9 28 55 Inside 9 69 Inside 28 69 Inside 44 38 Inside 57 5 Inside 19 1 9 5 Inside Supply Opening Return Opening Electrical Entrance 2 0 3 9 6 4 Ro...

Page 7: ...4 Nailer A A 2 0 Typ 4 0 14 0 or 24 0 34 88 Inside 48 38 Inside 81 5 Inside 13 5 Inside 30 5 Inside Supply Opening Return Opening Electrical Entrance 24 25 2 0 3 4 6 9 8 8 Roof Curb for ERW B Cabinet...

Page 8: ...Do not use a forklift to lift or maneuver the unit Failure to use a load rated crane or hoist assembly to lift or maneuver the unit can cause severe personal injury and property damage WARNING Use all...

Page 9: ...onnel Figure 5 Condensate Drain Connection Damper Assemblies The optional damper assemblies described in this section are ordered with factory installed actuators and linkages The following sections d...

Page 10: ...ow are pressure tap location and installation recommendations The installation must comply with local code requirements 1 Install a tee fitting with a leak tight removable cap in each tube near the se...

Page 11: ...connecting the reference tap to the sensor results in unsatisfactory operation 6 Use an outdoor static pressure tip Dwyer A306 or equivalent to minimize the adverse effects of wind Place some type of...

Page 12: ...r that is not always readably detectable A static potential can easily be generated on a person that reaches 25 kVolts If this potential is discharged into one of the unit s circuit boards it can degr...

Page 13: ...who are familiar with working on live equipment A representative of the owner or the operator of the equipment should be present during start up to receive instructions in the operation care and adjus...

Page 14: ...0 1 8 0 9 6 15 0 13 6 6 8 89 0 0 0 0 0 0 0 143 8 130 0 65 0 0 0 0 0 0 0 JT1G NA 1 2 0 1 8 0 9 7 5 11 9 10 8 5 4 68 0 8 6 7 8 3 9 143 8 130 0 65 0 67 5 73 7 37 1 JT1G JT71G 2 2 0 1 8 0 9 10 10 0 9 0 4...

Page 15: ...there are some consistent characteristics All units a single circuit with a single or tandem compressor All units use an electronic expansion valve EVI and a start up by pass solenoid valve SVB Figur...

Page 16: ...ronic expansion valve CV Check Valve REC Refrigerant Receiver IDF Indoor fan ODF Outdoor fan COMP1 Inverter compressor COMP2 Fixed speed compressor 7 1 2 thru 15 ton only SVR Bypass solenoid valve RHV...

Page 17: ...igerant are required inside the system during Mechanical Cooling or defrost and Mechanical Heating This is the results of the charge in operating temperatures in Cooling and Heating Mode The receiver...

Page 18: ...gure 15 Oil Separator Figure 16 Secondary Oil Separator Check Valve All Rebel Units will have check valves on each of the compressor discharge lines On large cabinet units 7 15 Tons two valves one on...

Page 19: ...any possible debris from entering critical components expansion valves compressors etc These screens are not bi direction and must be installed in a specific direction if replaced Please be aware that...

Page 20: ...ed for Standard during heating mode the EVI will modulate to fully open and remain in this position When configured for heating mode the EVI will modulate to maintain the Subcooling Set Point Figure 2...

Page 21: ...crease compressor life by preventing it from running outside of the operating envelope Suction Refrigerant Temperature All Rebel units will have a Suction Refrigerant Temperature Sensor SRT This senso...

Page 22: ...ill be unavailable and the supplemental heat will ramp stage up to meet the DAT set point Defrost Defrost is a temporary and infrequent period during normal heating operations on Rebel heat pumps The...

Page 23: ...to be over cooled by the DX coil Hot gas from the unit condenser will be routed to an indoor coil downstream of the DX coil to reheat the air Hot gas reheat valves Figure 25 will control how much hot...

Page 24: ...mediately transitions to Cooling if Dehumidification is initiated in Economizer state Dehumidification Termination Dehumidification is terminated if the selected variable Relative Humidity or Dew Poin...

Page 25: ...Fan Only state no sensible cooling is required but dehumidification mode will still be enabled if the dew point or humidity sensor is not satisfied Reheat set point varies from a maximum value defaul...

Page 26: ...Figure 27 Modulating Hot Gas Reheat Schematic IM 1125 6 REBEL ROOFTOPS 26 www DaikinApplied com Optional Modulating Hot Gas Reheat DOT ITB 21 8041 AC FPID 437300 3 7B 01...

Page 27: ...ages Heat 1 Heat 2 Heat 3 Heat 4 kW MBh Delta T1 Min cfm kW MBh Delta T1 Min cfm kW MBh Delta T1 Min cfm kW MBh Delta T1 Min cfm 003 1200 2 6 20478 15 8 316 12 40956 31 6 632 18 61434 47 4 948 004 160...

Page 28: ...apacities Figure 28 Gas Heat Section Figure 29 Field Gas Heat Connections Data Unit Size 003 006 007 015 Low Heat Med Heat High Heat Low Heat Med Heat High Heat Heating Input MBh 80 120 160 200 300 40...

Page 29: ...its equipped with gas heating must not be operated in an atmosphere contaminated with chemicals which will corrode the unit such as halogenated hydrocarbons chlorine cleaning solvents refrigerants swi...

Page 30: ...fan compartment between the furnace heat exchanger and the fan To access the switch the fan compartment door must be opened Be sure all power to the unit is disconnected before opening the fan compart...

Page 31: ...30 245 500 760 1450 2300 4100 8300 50 56 115 215 440 670 1270 2000 3600 7400 60 50 105 195 400 610 1150 1850 3250 6800 70 46 96 180 370 560 1050 1700 3000 6200 80 53 90 170 350 530 990 1600 2800 5800...

Page 32: ...rner output to match the unit discharge air temperature setting LP Conversion Staged Furnace Only Convert the furnace in this unit using the liquefied petroleum LP gas valve spring and burner nozzles...

Page 33: ...ck the burner fan wheel for binding rubbing or loose setscrews 2 Check power 3 Purge the gas lines 4 Leak check Using a rich soap water mixture and a brush check the gas lines for leaks Correct all le...

Page 34: ...enience Have this system inspected at regular intervals by a trained and experienced service technician The following service intervals are typical for average situations but will have to be adjusted...

Page 35: ...ied control OK 1 Flash Combustion fan motor energized pressure switch open 2 Flashes Combustion fan motor off pressure switch closed 3 Flashes Ignition lockout from too many trials 4 Flashes Ignition...

Page 36: ...Module for Modulating Gas Furnace Figure 37 Typical Modulating Gas Furnace Electrical Schematic with Sensor IM 1125 6 REBEL ROOFTOPS 36 www DaikinApplied com Optional Gas Heat DOT ITB 21 8041 AC FPID...

Page 37: ...formation example Description C Furnace series or model name for example C cabinet series CAb 400 Furnace size in 1000 s of BTU for example 400 kBTU nAt or LP Burner fuel type for example natural gas...

Reviews: