Electric Heater Design
If the 10th digit in the model number is an “E”, the rooftop
unit was furnished with a factory installed electric furnace
(Example, DPS010AHCE). The Rebel commercial rooftop units
are available with 4-stage heat output (see capacities in
. This packaged electric heat rooftop unit is designed for
outdoor non-residential installations only.
The electric heat design consists of a heating coil, DDC staging
control, and all operational safeties. The safety switches
include high-limit temperature switches and individual coil
fusing.
Electric Heating Capacity Data
Table 11:
DPS 003 – 015 Electric Heating Capacities
Electric Heater Data
1
Table 12: DPS 003 – 015 Electric Heater Data
(Maximum Temp. 60°F)
The high limit switch is an automatic reset switch. It opens the
control circuit and shuts the heater down when the temperature
reaches the high limit switch closes again allows the heater
to run when the temperature gets below dead band. There is
a second level of protection with an auxiliary high limit switch.
This switch opens up and shuts the heater down when the
temperature exceeds the set point. This switch requires a
manual reset .
Unit
Nom
cfm
Stages
Heat 1
Heat 2
Heat 3
Heat 4
kW
MBh
Delta
T
1
Min
cfm
kW
MBh
Delta
T
1
Min
cfm
kW MBh
Delta
T
1
Min
cfm
kW
MBh
Delta
T
1
Min
cfm
003 1200
2
6
20478
15 .8
316
12
40956
31 .6
632
18 61434 47 .4
948
—
—
—
—
004 1600
2
6
20478
11 .9
316
12
40956
23 .7
632
18 61434 35 .6
948
30
102390 59 .3 1580
005 2000
2
6
20478
9 .5
316
12
40956
19 .0
632
18 61434 28 .4
948
30
102390 47 .4 1580
006 2400
2, SCR
6
20 .5
7 .9
316
12
40 .9
15 .8
632
18
61 .4
23 .7
948
30
102 .4
39 .5 1580
007 3000
4, SCR
18
61 .4
19 .0
948
36
122 .9
37 .9 1896 54
184 .3
56 .9 2844 72 .0
2
245 .8
60 .0
3
3793
010 4000
4, SCR
18
61 .4
14 .2
948
36
122 .9
28 .4 1896 54
184 .3
42 .7 2844 72 .0
2
245 .8
56 .9 3793
012 4800
4, SCR
18
61 .4
11 .9
948
36
122 .9
23 .7 1896 54
184 .3
35 .6 2844 72 .0
2
245 .8
47 .4 3793
015 4800
4, SCR
18
61 .4
11 .9
948
36
122 .9
23 .7 1896 54
184 .3
35 .6 2844 72 .0
2
245 .8
47 .4 3793
NOTE:
1. Temperature is calculated at nominal air flow
2. Not available in 208 & 230 Volt
3. 60 degree max rise
kW
Voltage
Amps
kW
Voltage
Amps
kW
Voltage
Amps
6
208
16 .7
30
208
83 .3
72
208
199 .9
230
15 .1
230
75 .3
230
180 .7
475
7 .3
475
36 .5
475
87 .5
575
6 .0
575
30 .1
575
72 .3
12
208
33 .3
36
208
99 .9
230
30 .1
230
90 .4
475
14 .6
475
43 .8
575
12 .0
575
36 .1
18
208
50 .0
54
208
149 .9
230
45 .2
230
135 .6
475
21 .9
475
65 .6
575
18 .1
575
54 .2
NOTE:
1. Maximum temperature rise = 60º
o
pTIonal
e
leCTrIC
h
eaT
www.DaikinApplied.com
27