background image

The preferred entrance for power cables is through the bottom 

knockouts provided on the unit. If a side entrance is the only 

option, a hole may be drilled in the stationary upright. 
The minimum circuit ampacity (MCA) is shown on the unit 

nameplate . Refer to 

Table 7

 for the recommended number of 

power wires.
Copper wire is required for all conductors. Size wires in 

accordance with the ampacity tables in Article 310 of the 

National Electrical Code. If long wires are required, it may be 

necessary to increase the wire size to prevent excessive voltage 

drop. Wires should be sized for a maximum of 3% voltage drop. 

Supply voltage must not vary by more than 10% of nameplate. 

Phase voltage imbalance must not exceed 2%. (Calculate the 

average voltage of the three legs. The leg with voltage deviating 

the farthest from the average value must not be more than 

2% away.) Contact the local power company for correction of 

improper voltage or phase imbalance.

  

A ground lug is provided in the control panel. Size the grounding 

conductor in accordance with Table 250-95 of the National 

Electrical Code.
In compliance with the National Electrical Code, a 115 V factory 

mounted service receptacle outlet is provided. This outlet must 

be powered by a field connected 15 A, 115 V power supply. 

Leads are brought into the unit through the bottom of the main 

control panel.

Table 7: Recommended Field Power Wiring  

  

Field Control Wiring

The Rebel rooftop units are available with the following field 

control connections:

• 

Space sensor.

• 

Space sensor with setpoint adjustment.

•  Fan operation output .

• 

VAV box output.

•  Remote alarm output .

• 

External discharge air temperature reset.

• 

Outdoor air damper minimum position adjustment.

Descriptions of these field connections are included in the 

MicroTech III Unit Controller Manual (OM 1141).

  

Start-up and service of this equipment must be performed 
by trained and experienced technicians . 

It is highly 

recommended that the initial start-up and future service be 

performed by Daikin trained technicians who are familiar with 

working on live equipment. A representative of the owner or the 

operator of the equipment should be present during start-up to 

receive instructions in the operation, care and adjustment of the 

unit .

  

Before Start-Up

1 . 

Notify inspectors or representatives who may be required to 

be present during start-up of gas fuel equipment. These could 

include the gas utility company, city gas inspectors, heating 

inspectors, etc.

2 . 

Review the equipment and service literature and become 

familiar with the location and purpose of the furnace controls. 

Determine where the gas and power can be turned off at the 

unit and before the unit.

3 . 

Determine that power is connected to the unit and available.

4 . 

Determine that the gas piping, meter, and service regulator 

have been installed, tested, and meet the equipment 

requirements .

5 . 

Determine that proper instruments will be available for the 

start-up. A proper start-up requires the following: voltmeter, 

manometer or gauges with ranges for both manifold pressure 

and inlet gas pressure.    

 WARNING

Provide proper line voltage and phase balance .

Improper  line  voltage  or  excessive  phase  imbalance 

constitutes product abuse. It can cause severe damage 

to the unit’s electrical components.

Ampacity (MCA)

Number of Power 

Wires Per Phase

Wire Gauge

Insulation 

Temperature 

Rating (°C)

20

1

14

75

25

1

12

75

35

1

10

75

50

1

8

75

65

1

6

75

85

1

4

75

100

1

3

75

115

1

2

75

130

1

1

75

150

1

1/0

75

175

1

2/0

75

200

1

3/0

75

230

1

4/0

75

255

1

250

75

NOTE: 

 

1. All wire sizes assume separate conduit for each set of parallel conductors.

 

2. All wire sizes based on NEC Table 310-16 for 75°C THW wire (copper). Canadian 

 

    electrical code wire ampacities may vary.

 

3. All wire sizes assume no voltage drop for short power leads.

 WARNING

Electrical shock hazard . Can cause severe injury or 
death

 .

Connect  only  low  voltage  NEC  Class  II  circuits  to 

terminal block TB2.

 DANGER

Overheating or failure of the gas supply to shut off can 
cause equipment damage, severe personal injury or 
death .

 Turn off the manual gas valve to the appliance before 

shutting off the electrical supply.

e

leCTrICal

 I

nsTallaTIon

www.DaikinApplied.com 

13

 

IM 1125-6 • REBEL ROOFTOPS

DOT-ITB-21-8041-AC

FPID: 437300-3-7B-01

Summary of Contents for DPS003

Page 1: ...1125 6 Group Applied Air Systems Part Number IM 1125 Date September 2014 Rebel Commercial Packaged Rooftop Systems Heating and Cooling Models DPS003 015A R 410A Refrigerant MicroTech III Unit Control...

Page 2: ...p Procedures 33 Service 34 Maintenance 34 Optional Hot Water Heat 43 Hot Water Heater Design 43 Optional Energy Recovery Wheel 44 Optional Outdoor Air Monitor 46 Thermal Dispersion Airflow Measurement...

Page 3: ...number electrical characteristics and refrigerant charge Hazard Identification Information Rooftop unit control configuration Manual bulletin number BACnet IP Comm Module IM 916 BACnet Integration IM...

Page 4: ...imum clearances around the unit and control panel Ventilation Clearance Below are minimum ventilation clearance recommendations The system designer must consider each application and provide adequate...

Page 5: ...ing or twisting of the machine If building construction allows sound and vibration into the occupied space locate the unit over a non critical area It is the responsibility of the system designer to m...

Page 6: ...b Detail A A 2 4 Nailer A A 2 0 Typ 14 0 or 24 0 4 0 3 9 28 55 Inside 9 69 Inside 28 69 Inside 44 38 Inside 57 5 Inside 19 1 9 5 Inside Supply Opening Return Opening Electrical Entrance 2 0 3 9 6 4 Ro...

Page 7: ...4 Nailer A A 2 0 Typ 4 0 14 0 or 24 0 34 88 Inside 48 38 Inside 81 5 Inside 13 5 Inside 30 5 Inside Supply Opening Return Opening Electrical Entrance 24 25 2 0 3 4 6 9 8 8 Roof Curb for ERW B Cabinet...

Page 8: ...Do not use a forklift to lift or maneuver the unit Failure to use a load rated crane or hoist assembly to lift or maneuver the unit can cause severe personal injury and property damage WARNING Use all...

Page 9: ...onnel Figure 5 Condensate Drain Connection Damper Assemblies The optional damper assemblies described in this section are ordered with factory installed actuators and linkages The following sections d...

Page 10: ...ow are pressure tap location and installation recommendations The installation must comply with local code requirements 1 Install a tee fitting with a leak tight removable cap in each tube near the se...

Page 11: ...connecting the reference tap to the sensor results in unsatisfactory operation 6 Use an outdoor static pressure tip Dwyer A306 or equivalent to minimize the adverse effects of wind Place some type of...

Page 12: ...r that is not always readably detectable A static potential can easily be generated on a person that reaches 25 kVolts If this potential is discharged into one of the unit s circuit boards it can degr...

Page 13: ...who are familiar with working on live equipment A representative of the owner or the operator of the equipment should be present during start up to receive instructions in the operation care and adjus...

Page 14: ...0 1 8 0 9 6 15 0 13 6 6 8 89 0 0 0 0 0 0 0 143 8 130 0 65 0 0 0 0 0 0 0 JT1G NA 1 2 0 1 8 0 9 7 5 11 9 10 8 5 4 68 0 8 6 7 8 3 9 143 8 130 0 65 0 67 5 73 7 37 1 JT1G JT71G 2 2 0 1 8 0 9 10 10 0 9 0 4...

Page 15: ...there are some consistent characteristics All units a single circuit with a single or tandem compressor All units use an electronic expansion valve EVI and a start up by pass solenoid valve SVB Figur...

Page 16: ...ronic expansion valve CV Check Valve REC Refrigerant Receiver IDF Indoor fan ODF Outdoor fan COMP1 Inverter compressor COMP2 Fixed speed compressor 7 1 2 thru 15 ton only SVR Bypass solenoid valve RHV...

Page 17: ...igerant are required inside the system during Mechanical Cooling or defrost and Mechanical Heating This is the results of the charge in operating temperatures in Cooling and Heating Mode The receiver...

Page 18: ...gure 15 Oil Separator Figure 16 Secondary Oil Separator Check Valve All Rebel Units will have check valves on each of the compressor discharge lines On large cabinet units 7 15 Tons two valves one on...

Page 19: ...any possible debris from entering critical components expansion valves compressors etc These screens are not bi direction and must be installed in a specific direction if replaced Please be aware that...

Page 20: ...ed for Standard during heating mode the EVI will modulate to fully open and remain in this position When configured for heating mode the EVI will modulate to maintain the Subcooling Set Point Figure 2...

Page 21: ...crease compressor life by preventing it from running outside of the operating envelope Suction Refrigerant Temperature All Rebel units will have a Suction Refrigerant Temperature Sensor SRT This senso...

Page 22: ...ill be unavailable and the supplemental heat will ramp stage up to meet the DAT set point Defrost Defrost is a temporary and infrequent period during normal heating operations on Rebel heat pumps The...

Page 23: ...to be over cooled by the DX coil Hot gas from the unit condenser will be routed to an indoor coil downstream of the DX coil to reheat the air Hot gas reheat valves Figure 25 will control how much hot...

Page 24: ...mediately transitions to Cooling if Dehumidification is initiated in Economizer state Dehumidification Termination Dehumidification is terminated if the selected variable Relative Humidity or Dew Poin...

Page 25: ...Fan Only state no sensible cooling is required but dehumidification mode will still be enabled if the dew point or humidity sensor is not satisfied Reheat set point varies from a maximum value defaul...

Page 26: ...Figure 27 Modulating Hot Gas Reheat Schematic IM 1125 6 REBEL ROOFTOPS 26 www DaikinApplied com Optional Modulating Hot Gas Reheat DOT ITB 21 8041 AC FPID 437300 3 7B 01...

Page 27: ...ages Heat 1 Heat 2 Heat 3 Heat 4 kW MBh Delta T1 Min cfm kW MBh Delta T1 Min cfm kW MBh Delta T1 Min cfm kW MBh Delta T1 Min cfm 003 1200 2 6 20478 15 8 316 12 40956 31 6 632 18 61434 47 4 948 004 160...

Page 28: ...apacities Figure 28 Gas Heat Section Figure 29 Field Gas Heat Connections Data Unit Size 003 006 007 015 Low Heat Med Heat High Heat Low Heat Med Heat High Heat Heating Input MBh 80 120 160 200 300 40...

Page 29: ...its equipped with gas heating must not be operated in an atmosphere contaminated with chemicals which will corrode the unit such as halogenated hydrocarbons chlorine cleaning solvents refrigerants swi...

Page 30: ...fan compartment between the furnace heat exchanger and the fan To access the switch the fan compartment door must be opened Be sure all power to the unit is disconnected before opening the fan compart...

Page 31: ...30 245 500 760 1450 2300 4100 8300 50 56 115 215 440 670 1270 2000 3600 7400 60 50 105 195 400 610 1150 1850 3250 6800 70 46 96 180 370 560 1050 1700 3000 6200 80 53 90 170 350 530 990 1600 2800 5800...

Page 32: ...rner output to match the unit discharge air temperature setting LP Conversion Staged Furnace Only Convert the furnace in this unit using the liquefied petroleum LP gas valve spring and burner nozzles...

Page 33: ...ck the burner fan wheel for binding rubbing or loose setscrews 2 Check power 3 Purge the gas lines 4 Leak check Using a rich soap water mixture and a brush check the gas lines for leaks Correct all le...

Page 34: ...enience Have this system inspected at regular intervals by a trained and experienced service technician The following service intervals are typical for average situations but will have to be adjusted...

Page 35: ...ied control OK 1 Flash Combustion fan motor energized pressure switch open 2 Flashes Combustion fan motor off pressure switch closed 3 Flashes Ignition lockout from too many trials 4 Flashes Ignition...

Page 36: ...Module for Modulating Gas Furnace Figure 37 Typical Modulating Gas Furnace Electrical Schematic with Sensor IM 1125 6 REBEL ROOFTOPS 36 www DaikinApplied com Optional Gas Heat DOT ITB 21 8041 AC FPID...

Page 37: ...formation example Description C Furnace series or model name for example C cabinet series CAb 400 Furnace size in 1000 s of BTU for example 400 kBTU nAt or LP Burner fuel type for example natural gas...

Reviews: