Table 14: Capacity of Pipe Natural Gas (CFH)  

  

Table 15: Specific Gravity Other Than 0.60  

  

Table 16: Pressure Drop Other Than 0.3

"     

Gas Piping Routing Into Unit

On-The-Roof Piping

1 . 

Remove knockout on upright (refer to 

Figure 33

 or 

Figure 

34

).

2 . 

Route gas supply pipe through hole. Carefully plan pipe 

route and fitting locations to avoid interference with 

swinging of doors, etc.

3 . 

The Rebel unit does not have an option for gas piping 

through the curb.

Figure 33: Small Cabinet Gas Piping  

        

Figure 34: Large Cabinet Gas Piping  

          

With Pressure Drop of 0 .3"

 Wc & Specific Gravity Of 0.60

Pipe Length (ft .)

Pipe Size-inches (Ips)

½

¾

1

2

3

4

10

132

278

520

1050

1600

2050

4800

8500

17500

20

92

190

350

730

1100

2100

3300

5900

12000

30

73

152

285

590

890

1650

2700

4700

9700

40

63

130

245

500

760

1450

2300

4100

8300

50

56

115

215

440

670

1270

2000

3600

7400

60

50

105

195

400

610

1150

1850

3250

6800

70

46

96

180

370

560

1050

1700

3000

6200

80

53

90

170

350

530

990

1600

2800

5800

90

40

84

160

320

490

930

1500

2600

5400

100

38

79

150

305

460

870

1400

2500

5100

125

34

72

130

275

410

780

1250

2200

4500

150

31

64

120

250

380

710

1130

2000

4100

175

28

59

110

225

350

650

1050

1850

3800

200

26

55

100

210

320

610

980

1700

3500

NOTE: 

Use multiplier below for other gravities and pressure drops.

Specific Gravity

Multiplier

0 .50

1 .100

0 .60

1 .000

0 .70

0 .936

0 .80

0 .867

0 .90

0 .816

1 .00

0 .775

PROPANE-AIR

1 .10

0 .740

PROPANE

1 .55

0 .622

BUTANE

2 .00

0 .547

Pressure 

Drop

Multiplier

Pressure

Multiplier

0 .1

0 .577

1 .0

1 .83

0 .2

0 .815

2 .0

2 .58

0 .3

1 .000

3 .0

3 .16

0 .4

1 .16

4 .0

3 .65

0 .6

1 .42

6 .0

4 .47

0 .8

1 .64

8 .0

5 .15

Field Piping

Field Piping

o

pTIonal

 g

as

 h

eaT

www.DaikinApplied.com 

31

 

IM 1125-6 • REBEL ROOFTOPS

DOT-ITB-21-8041-AC

FPID: 437300-3-7B-01

Summary of Contents for DPS003

Page 1: ...1125 6 Group Applied Air Systems Part Number IM 1125 Date September 2014 Rebel Commercial Packaged Rooftop Systems Heating and Cooling Models DPS003 015A R 410A Refrigerant MicroTech III Unit Control...

Page 2: ...p Procedures 33 Service 34 Maintenance 34 Optional Hot Water Heat 43 Hot Water Heater Design 43 Optional Energy Recovery Wheel 44 Optional Outdoor Air Monitor 46 Thermal Dispersion Airflow Measurement...

Page 3: ...number electrical characteristics and refrigerant charge Hazard Identification Information Rooftop unit control configuration Manual bulletin number BACnet IP Comm Module IM 916 BACnet Integration IM...

Page 4: ...imum clearances around the unit and control panel Ventilation Clearance Below are minimum ventilation clearance recommendations The system designer must consider each application and provide adequate...

Page 5: ...ing or twisting of the machine If building construction allows sound and vibration into the occupied space locate the unit over a non critical area It is the responsibility of the system designer to m...

Page 6: ...b Detail A A 2 4 Nailer A A 2 0 Typ 14 0 or 24 0 4 0 3 9 28 55 Inside 9 69 Inside 28 69 Inside 44 38 Inside 57 5 Inside 19 1 9 5 Inside Supply Opening Return Opening Electrical Entrance 2 0 3 9 6 4 Ro...

Page 7: ...4 Nailer A A 2 0 Typ 4 0 14 0 or 24 0 34 88 Inside 48 38 Inside 81 5 Inside 13 5 Inside 30 5 Inside Supply Opening Return Opening Electrical Entrance 24 25 2 0 3 4 6 9 8 8 Roof Curb for ERW B Cabinet...

Page 8: ...Do not use a forklift to lift or maneuver the unit Failure to use a load rated crane or hoist assembly to lift or maneuver the unit can cause severe personal injury and property damage WARNING Use all...

Page 9: ...onnel Figure 5 Condensate Drain Connection Damper Assemblies The optional damper assemblies described in this section are ordered with factory installed actuators and linkages The following sections d...

Page 10: ...ow are pressure tap location and installation recommendations The installation must comply with local code requirements 1 Install a tee fitting with a leak tight removable cap in each tube near the se...

Page 11: ...connecting the reference tap to the sensor results in unsatisfactory operation 6 Use an outdoor static pressure tip Dwyer A306 or equivalent to minimize the adverse effects of wind Place some type of...

Page 12: ...r that is not always readably detectable A static potential can easily be generated on a person that reaches 25 kVolts If this potential is discharged into one of the unit s circuit boards it can degr...

Page 13: ...who are familiar with working on live equipment A representative of the owner or the operator of the equipment should be present during start up to receive instructions in the operation care and adjus...

Page 14: ...0 1 8 0 9 6 15 0 13 6 6 8 89 0 0 0 0 0 0 0 143 8 130 0 65 0 0 0 0 0 0 0 JT1G NA 1 2 0 1 8 0 9 7 5 11 9 10 8 5 4 68 0 8 6 7 8 3 9 143 8 130 0 65 0 67 5 73 7 37 1 JT1G JT71G 2 2 0 1 8 0 9 10 10 0 9 0 4...

Page 15: ...there are some consistent characteristics All units a single circuit with a single or tandem compressor All units use an electronic expansion valve EVI and a start up by pass solenoid valve SVB Figur...

Page 16: ...ronic expansion valve CV Check Valve REC Refrigerant Receiver IDF Indoor fan ODF Outdoor fan COMP1 Inverter compressor COMP2 Fixed speed compressor 7 1 2 thru 15 ton only SVR Bypass solenoid valve RHV...

Page 17: ...igerant are required inside the system during Mechanical Cooling or defrost and Mechanical Heating This is the results of the charge in operating temperatures in Cooling and Heating Mode The receiver...

Page 18: ...gure 15 Oil Separator Figure 16 Secondary Oil Separator Check Valve All Rebel Units will have check valves on each of the compressor discharge lines On large cabinet units 7 15 Tons two valves one on...

Page 19: ...any possible debris from entering critical components expansion valves compressors etc These screens are not bi direction and must be installed in a specific direction if replaced Please be aware that...

Page 20: ...ed for Standard during heating mode the EVI will modulate to fully open and remain in this position When configured for heating mode the EVI will modulate to maintain the Subcooling Set Point Figure 2...

Page 21: ...crease compressor life by preventing it from running outside of the operating envelope Suction Refrigerant Temperature All Rebel units will have a Suction Refrigerant Temperature Sensor SRT This senso...

Page 22: ...ill be unavailable and the supplemental heat will ramp stage up to meet the DAT set point Defrost Defrost is a temporary and infrequent period during normal heating operations on Rebel heat pumps The...

Page 23: ...to be over cooled by the DX coil Hot gas from the unit condenser will be routed to an indoor coil downstream of the DX coil to reheat the air Hot gas reheat valves Figure 25 will control how much hot...

Page 24: ...mediately transitions to Cooling if Dehumidification is initiated in Economizer state Dehumidification Termination Dehumidification is terminated if the selected variable Relative Humidity or Dew Poin...

Page 25: ...Fan Only state no sensible cooling is required but dehumidification mode will still be enabled if the dew point or humidity sensor is not satisfied Reheat set point varies from a maximum value defaul...

Page 26: ...Figure 27 Modulating Hot Gas Reheat Schematic IM 1125 6 REBEL ROOFTOPS 26 www DaikinApplied com Optional Modulating Hot Gas Reheat DOT ITB 21 8041 AC FPID 437300 3 7B 01...

Page 27: ...ages Heat 1 Heat 2 Heat 3 Heat 4 kW MBh Delta T1 Min cfm kW MBh Delta T1 Min cfm kW MBh Delta T1 Min cfm kW MBh Delta T1 Min cfm 003 1200 2 6 20478 15 8 316 12 40956 31 6 632 18 61434 47 4 948 004 160...

Page 28: ...apacities Figure 28 Gas Heat Section Figure 29 Field Gas Heat Connections Data Unit Size 003 006 007 015 Low Heat Med Heat High Heat Low Heat Med Heat High Heat Heating Input MBh 80 120 160 200 300 40...

Page 29: ...its equipped with gas heating must not be operated in an atmosphere contaminated with chemicals which will corrode the unit such as halogenated hydrocarbons chlorine cleaning solvents refrigerants swi...

Page 30: ...fan compartment between the furnace heat exchanger and the fan To access the switch the fan compartment door must be opened Be sure all power to the unit is disconnected before opening the fan compart...

Page 31: ...30 245 500 760 1450 2300 4100 8300 50 56 115 215 440 670 1270 2000 3600 7400 60 50 105 195 400 610 1150 1850 3250 6800 70 46 96 180 370 560 1050 1700 3000 6200 80 53 90 170 350 530 990 1600 2800 5800...

Page 32: ...rner output to match the unit discharge air temperature setting LP Conversion Staged Furnace Only Convert the furnace in this unit using the liquefied petroleum LP gas valve spring and burner nozzles...

Page 33: ...ck the burner fan wheel for binding rubbing or loose setscrews 2 Check power 3 Purge the gas lines 4 Leak check Using a rich soap water mixture and a brush check the gas lines for leaks Correct all le...

Page 34: ...enience Have this system inspected at regular intervals by a trained and experienced service technician The following service intervals are typical for average situations but will have to be adjusted...

Page 35: ...ied control OK 1 Flash Combustion fan motor energized pressure switch open 2 Flashes Combustion fan motor off pressure switch closed 3 Flashes Ignition lockout from too many trials 4 Flashes Ignition...

Page 36: ...Module for Modulating Gas Furnace Figure 37 Typical Modulating Gas Furnace Electrical Schematic with Sensor IM 1125 6 REBEL ROOFTOPS 36 www DaikinApplied com Optional Gas Heat DOT ITB 21 8041 AC FPID...

Page 37: ...formation example Description C Furnace series or model name for example C cabinet series CAb 400 Furnace size in 1000 s of BTU for example 400 kBTU nAt or LP Burner fuel type for example natural gas...

Reviews: