Control & Arrangement

In conjunction with dehumidification, MHGRH is used to raise 

the temperature of the cooled air to a desirable value. MHGRH 

is comprised of a parallel coil arrangement, with dual reheat 

valves (which operate in concert with one another) and a check 

valve. 
During Dehumidification control with modulating Hot Gas 

Reheat (MHGRH) an analog signal (0-10Vdc) is controlled as 

described below.

• 

A PI Loop is used to control the HGRH valves to maintain 

the Discharge Air Temperature from the reheat coil.

• 

Compressor staging during reheat (or dehumidification) 

will be controlled by the Leaving DX Coil Temperature. 

For increased dehumidification during reheat, the 

standard default compressor staging range is 45 - 52°F.

• 

When dehumidification is active in the Cooling state, the 

reheat set point equals the DAT Cooling Setpoint. For 

DAT units, this is the normal DAT set point resulting from 

any reset. For Zone Control units, this set point is the 

result of a PI Loop based on the Control Temperature.

• 

Communication with the reheat control valves is 

accomplished by providing a 0-10Vdc signal to a pair of 

interface boards which in turn supply the control signal to 

the reheat valves (step type).

• 

In the Fan Only state, no sensible cooling is required, 

but dehumidification mode will still be enabled if the 

dew point or humidity sensor is not satisfied. Reheat 

set point varies from a maximum value (default 65°F) 

when the Control Temperature is at or below the heating 

changeover setpoint to a minimum value (default 55°F) 

when the Control Temperature is at or above the cooling 

changeover setpoint. 

• 

In the reheat mode, the minimum position for the reheat 

valves is 1% (1.0 Vdc). The controller will modulate the 

reheat valves from this starting position. 

• 

Upon termination of dehumidification (reheat), the 

maximum ramp down or decay rate of the reheat control 

valves shall be 1% per sec (or 0.1V per sec).

• 

Upon termination of dehumidification (reheat), staging 

of compressor(s) is delayed for 1 minute after reheat 

capacity = 0% (0 Vdc).

• 

Every 24 hours, the reheat control valves will be driven to 

their maximum position (10Vdc) and then returned to their 

normal operating position (0Vdc). If unit is operating in 

cooling or dehumidification (reheat) at the prescribed time 

it will be deferred to the next time. 

• 

Dehumidification status can now be found under the 

MicroTech III main system menu. Reheat capacity (valve 

position) can also be found under the main system menu, 

display based on percentage (0-100%).  

o

pTIonal

 M

odulaTIng

 h

oT

 g

as

 r

eheaT

www.DaikinApplied.com 

25

 

IM 1125-6 • REBEL ROOFTOPS

DOT-ITB-21-8041-AC

FPID: 437300-3-7B-01

Summary of Contents for DPS003

Page 1: ...1125 6 Group Applied Air Systems Part Number IM 1125 Date September 2014 Rebel Commercial Packaged Rooftop Systems Heating and Cooling Models DPS003 015A R 410A Refrigerant MicroTech III Unit Control...

Page 2: ...p Procedures 33 Service 34 Maintenance 34 Optional Hot Water Heat 43 Hot Water Heater Design 43 Optional Energy Recovery Wheel 44 Optional Outdoor Air Monitor 46 Thermal Dispersion Airflow Measurement...

Page 3: ...number electrical characteristics and refrigerant charge Hazard Identification Information Rooftop unit control configuration Manual bulletin number BACnet IP Comm Module IM 916 BACnet Integration IM...

Page 4: ...imum clearances around the unit and control panel Ventilation Clearance Below are minimum ventilation clearance recommendations The system designer must consider each application and provide adequate...

Page 5: ...ing or twisting of the machine If building construction allows sound and vibration into the occupied space locate the unit over a non critical area It is the responsibility of the system designer to m...

Page 6: ...b Detail A A 2 4 Nailer A A 2 0 Typ 14 0 or 24 0 4 0 3 9 28 55 Inside 9 69 Inside 28 69 Inside 44 38 Inside 57 5 Inside 19 1 9 5 Inside Supply Opening Return Opening Electrical Entrance 2 0 3 9 6 4 Ro...

Page 7: ...4 Nailer A A 2 0 Typ 4 0 14 0 or 24 0 34 88 Inside 48 38 Inside 81 5 Inside 13 5 Inside 30 5 Inside Supply Opening Return Opening Electrical Entrance 24 25 2 0 3 4 6 9 8 8 Roof Curb for ERW B Cabinet...

Page 8: ...Do not use a forklift to lift or maneuver the unit Failure to use a load rated crane or hoist assembly to lift or maneuver the unit can cause severe personal injury and property damage WARNING Use all...

Page 9: ...onnel Figure 5 Condensate Drain Connection Damper Assemblies The optional damper assemblies described in this section are ordered with factory installed actuators and linkages The following sections d...

Page 10: ...ow are pressure tap location and installation recommendations The installation must comply with local code requirements 1 Install a tee fitting with a leak tight removable cap in each tube near the se...

Page 11: ...connecting the reference tap to the sensor results in unsatisfactory operation 6 Use an outdoor static pressure tip Dwyer A306 or equivalent to minimize the adverse effects of wind Place some type of...

Page 12: ...r that is not always readably detectable A static potential can easily be generated on a person that reaches 25 kVolts If this potential is discharged into one of the unit s circuit boards it can degr...

Page 13: ...who are familiar with working on live equipment A representative of the owner or the operator of the equipment should be present during start up to receive instructions in the operation care and adjus...

Page 14: ...0 1 8 0 9 6 15 0 13 6 6 8 89 0 0 0 0 0 0 0 143 8 130 0 65 0 0 0 0 0 0 0 JT1G NA 1 2 0 1 8 0 9 7 5 11 9 10 8 5 4 68 0 8 6 7 8 3 9 143 8 130 0 65 0 67 5 73 7 37 1 JT1G JT71G 2 2 0 1 8 0 9 10 10 0 9 0 4...

Page 15: ...there are some consistent characteristics All units a single circuit with a single or tandem compressor All units use an electronic expansion valve EVI and a start up by pass solenoid valve SVB Figur...

Page 16: ...ronic expansion valve CV Check Valve REC Refrigerant Receiver IDF Indoor fan ODF Outdoor fan COMP1 Inverter compressor COMP2 Fixed speed compressor 7 1 2 thru 15 ton only SVR Bypass solenoid valve RHV...

Page 17: ...igerant are required inside the system during Mechanical Cooling or defrost and Mechanical Heating This is the results of the charge in operating temperatures in Cooling and Heating Mode The receiver...

Page 18: ...gure 15 Oil Separator Figure 16 Secondary Oil Separator Check Valve All Rebel Units will have check valves on each of the compressor discharge lines On large cabinet units 7 15 Tons two valves one on...

Page 19: ...any possible debris from entering critical components expansion valves compressors etc These screens are not bi direction and must be installed in a specific direction if replaced Please be aware that...

Page 20: ...ed for Standard during heating mode the EVI will modulate to fully open and remain in this position When configured for heating mode the EVI will modulate to maintain the Subcooling Set Point Figure 2...

Page 21: ...crease compressor life by preventing it from running outside of the operating envelope Suction Refrigerant Temperature All Rebel units will have a Suction Refrigerant Temperature Sensor SRT This senso...

Page 22: ...ill be unavailable and the supplemental heat will ramp stage up to meet the DAT set point Defrost Defrost is a temporary and infrequent period during normal heating operations on Rebel heat pumps The...

Page 23: ...to be over cooled by the DX coil Hot gas from the unit condenser will be routed to an indoor coil downstream of the DX coil to reheat the air Hot gas reheat valves Figure 25 will control how much hot...

Page 24: ...mediately transitions to Cooling if Dehumidification is initiated in Economizer state Dehumidification Termination Dehumidification is terminated if the selected variable Relative Humidity or Dew Poin...

Page 25: ...Fan Only state no sensible cooling is required but dehumidification mode will still be enabled if the dew point or humidity sensor is not satisfied Reheat set point varies from a maximum value defaul...

Page 26: ...Figure 27 Modulating Hot Gas Reheat Schematic IM 1125 6 REBEL ROOFTOPS 26 www DaikinApplied com Optional Modulating Hot Gas Reheat DOT ITB 21 8041 AC FPID 437300 3 7B 01...

Page 27: ...ages Heat 1 Heat 2 Heat 3 Heat 4 kW MBh Delta T1 Min cfm kW MBh Delta T1 Min cfm kW MBh Delta T1 Min cfm kW MBh Delta T1 Min cfm 003 1200 2 6 20478 15 8 316 12 40956 31 6 632 18 61434 47 4 948 004 160...

Page 28: ...apacities Figure 28 Gas Heat Section Figure 29 Field Gas Heat Connections Data Unit Size 003 006 007 015 Low Heat Med Heat High Heat Low Heat Med Heat High Heat Heating Input MBh 80 120 160 200 300 40...

Page 29: ...its equipped with gas heating must not be operated in an atmosphere contaminated with chemicals which will corrode the unit such as halogenated hydrocarbons chlorine cleaning solvents refrigerants swi...

Page 30: ...fan compartment between the furnace heat exchanger and the fan To access the switch the fan compartment door must be opened Be sure all power to the unit is disconnected before opening the fan compart...

Page 31: ...30 245 500 760 1450 2300 4100 8300 50 56 115 215 440 670 1270 2000 3600 7400 60 50 105 195 400 610 1150 1850 3250 6800 70 46 96 180 370 560 1050 1700 3000 6200 80 53 90 170 350 530 990 1600 2800 5800...

Page 32: ...rner output to match the unit discharge air temperature setting LP Conversion Staged Furnace Only Convert the furnace in this unit using the liquefied petroleum LP gas valve spring and burner nozzles...

Page 33: ...ck the burner fan wheel for binding rubbing or loose setscrews 2 Check power 3 Purge the gas lines 4 Leak check Using a rich soap water mixture and a brush check the gas lines for leaks Correct all le...

Page 34: ...enience Have this system inspected at regular intervals by a trained and experienced service technician The following service intervals are typical for average situations but will have to be adjusted...

Page 35: ...ied control OK 1 Flash Combustion fan motor energized pressure switch open 2 Flashes Combustion fan motor off pressure switch closed 3 Flashes Ignition lockout from too many trials 4 Flashes Ignition...

Page 36: ...Module for Modulating Gas Furnace Figure 37 Typical Modulating Gas Furnace Electrical Schematic with Sensor IM 1125 6 REBEL ROOFTOPS 36 www DaikinApplied com Optional Gas Heat DOT ITB 21 8041 AC FPID...

Page 37: ...formation example Description C Furnace series or model name for example C cabinet series CAb 400 Furnace size in 1000 s of BTU for example 400 kBTU nAt or LP Burner fuel type for example natural gas...

Reviews: