Rigging and Handling
Rigging holes for shackles are integral on the unit base.
Use
four independent lines, securing one end of a line to a
unit base lifting point and the other end of the line to an
associated spreader bar lifting point
(see
). Figure 4
is an example of an instruction label shipped with each unit
Use spreader bars to prevent damage to the unit cabinet. Avoid
twisting or uneven lifting of the unit. The cable length from the
bracket to the hook should always be longer than the distance
between the outer lifting points.
Table 2: Unit Component Weights
Figure 4: Rigging Label
If the unit is stored at the construction site for an intermediate
period, take these additional precautions:
1 .
Support the unit well along the length of the base rail.
2 .
Level the unit (no twists or uneven ground surface).
3 .
Provide proper drainage around the unit to prevent
flooding of the equipment.
4 .
Provide adequate protection from vandalism, mechanical
contact, etc.
5 .
Securely close the doors.
6 .
Cover the supply and return air openings.
Table 3: Fan Assembly Weights
WARNING
Only trained and qualified personnel should be allowed
to rig loads or operate load rated cranes and/or hoist
assemblies. Do not use a forklift to lift or maneuver the
unit. Failure to use a load rated crane or hoist assembly
to lift or maneuver the unit can cause severe personal
injury and property damage.
WARNING
Use all lifting points. Improper lifting can cause property
damage, severe personal injury, or death.
CAUTION
Lifting points may not be symmetrical to the center
of gravity of the unit .
Ballast or unequal cable lengths
may be required.
CAUTION
Unit is equipped with fork slot reenforcement pieces.
These need to be removed before unit is set on the curb.
Size
003
004
005
006
007
010
012
015
Base Weight
1
1058
1058
1058
1058
1600
1600
1600
1600
Heat Pump
1058
1058
1058
1058
1600
1600
1600
1600
Electric Heat
45
45
45
45
100
100
100
100
Hot Water 2 Row
16 .5
16 .5
16 .5
16 .5
30
30
30
30
Hot Water 1 Row
20
20
20
20
31
31
31
31
Gas Heat
93
93
93
93
186
186
186
186
Hot Gas Re-heat
8
8
12
12
28
31
31
31
Economizer
163
163
163
163
308
308
308
308
Power Exhaust
201
201
201
201
346
346
346
346
High Capacity Coil
105
105
105
105
215
215
215
215
NOTE:
1. Includes standard cooling coil
REMOVE THE FORKLIFT
CHANNELS BEFORE
SETTING THE UNIT ON
THE ROOF CURB
USE SPREADER BAR
LIFT ONLY AS SHOWN
Diameter
Weight
12 Inch
35 lbs
14 Inch
38 lbs
16 Inch
55 lbs
18 Inch
87 lbs
20 Inch
91 lbs
22 Inch
115 lbs
IM 1125-6 • REBEL ROOFTOPS