Indoor Unit
Removal Procedure
87
4
Disengage the hooks of
the pipe retainer on the
back.
5
Pull auxiliary pipe
forward to an angle of
10 to 20 degrees.
Be careful to prevent pipe
deformation.
6
Disengage hooks
located right and left
side, and pull heat
exchanger forward.
The hooks are
symmetrically placed in
the right and the left.
Lift the heat exchanger
slightly upward to the right,
and the left hook comes to
be disengaged easily.
Step
Procedure
Points