SiBE01-503
Others
Others
107
1.3
Jumper Settings
1.3.1 When Two Units are Installed in One Room
How to set the different addresses.
When two indoor units are installed in one room, the two wireless remote controllers can be
set for different addresses.
PCB in the indoor unit
Remove the front panel.
Remove the electrical parts box (1-screw).
Slide the metallic cover to remove it. (4-claws on the electrical parts box.)
Cut the jumper
JA
on PCB.
Wireless remote controller
Cut the jumper
J4
.
1.3.2
Jumper Setting
(R4758)
Address
J4
CUT
EXIST
1
2
Metallic
cover
PCB
Electric
parts box
Claws (4 points)
Wireless
remote
controller
J4
CUT
2
ADDRESS: JA
EXIST
1
JA
JC
C1
C31
J30
JP11
ADDRESS
Jumper
(On indoor control PCB)
Function
When connected
(factory set)
When cut
JC
Power failure
recovery function
Auto re-start
Unit does not resume operation
after recovering from a power
failure. Timer ON-OFF settings
are cleared.
Summary of Contents for ARY20DV2
Page 1: ...SiBE01 503 SPLIT Pair D Series Applied Models zNon Inverter Pair Heat Pump ...
Page 5: ...SiBE01 503 iv Table of Contents Index i Drawings Flow Charts iii ...
Page 10: ...SiBE01 503 List of Function 1 Part 1 List of Function 1 Functions 2 ...
Page 13: ...Functions SiBE01 503 4 List of Function ...
Page 14: ...SiBE01 503 Specifications 5 Part 2 Specifications 1 Specifications 6 ...
Page 35: ...Control Specification SiBE01 503 26 Functions and Control ...
Page 59: ...Instructions SiBE01 503 50 System Configuration ...
Page 79: ...Check SiBE01 503 70 Service Diagnosis ...
Page 117: ...Others SiBE01 503 108 Others ...