SiBE01-503
Troubleshooting
Service Diagnosis
59
4.3
Freeze-up Protection Control
or
High Pressure Control
Remote
Controller
Display
A5
Method of
Malfunction
Detection
High pressure control
During heating operations, the temperature detected by the indoor heat exchanger
thermistor is used for the high pressure control (stop, outdoor fan stop, etc.)
Freeze-up protection control (operation halt) is activated during cooling operation according
to the temperature detected by the indoor unit heat exchanger thermistor.
Malfunction
Decision
Conditions
High pressure control
During heating operations, the temperature detected by the indoor heat exchanger
thermistor is above 63°C (FTYN models) or 65°C (ATY models).
Freeze-up protection
When the indoor unit heat exchanger temperature is below 0°C during cooling operation.
Supposed
Causes
Operation halt due to clogged air filter of the indoor unit.
Operation halt due to dust accumulation on the indoor unit heat exchanger.
Operation halt due to short-circuit.
Detection error due to faulty indoor unit heat exchanger thermistor.
Detection error due to faulty indoor unit PCB.
Summary of Contents for ARY20DV2
Page 1: ...SiBE01 503 SPLIT Pair D Series Applied Models zNon Inverter Pair Heat Pump ...
Page 5: ...SiBE01 503 iv Table of Contents Index i Drawings Flow Charts iii ...
Page 10: ...SiBE01 503 List of Function 1 Part 1 List of Function 1 Functions 2 ...
Page 13: ...Functions SiBE01 503 4 List of Function ...
Page 14: ...SiBE01 503 Specifications 5 Part 2 Specifications 1 Specifications 6 ...
Page 35: ...Control Specification SiBE01 503 26 Functions and Control ...
Page 59: ...Instructions SiBE01 503 50 System Configuration ...
Page 79: ...Check SiBE01 503 70 Service Diagnosis ...
Page 117: ...Others SiBE01 503 108 Others ...