Programme Dry Function
Outline
Programme dry function removes humidity while preventing the room temperature from
lowering.
Since the microcomputer controls both the temperature and air flow rate, the temperature
adjustment and fan adjustment buttons are inoperable in this mode.
Details of the
Control
The microcomputer automatically sets the target temperature and fan setting (L tap).
Target temperature is determined as follows.
Room temperature
≥
18°C: Target temperature = room temperature at startup
Room temperature
<
18°C: Target temperature = 18°C
Room temperature – target temperature
Compressor
ON
ON
OFF
OFF
L tap
L tap
OFF
Indoor unit fan
0˚C
–1˚C
(R4727)
6 min.
5 sec.
Fan OFF delay