8
|
Configuration
Installer reference guide
136
EHYH EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
#
Code
Description
[7.7.1.1]
[1‑00]
[1‑01]
[1‑02]
[1‑03]
Set weather-dependent heating
:
[1-03]
[1-02]
Ta
Tt
[1-00]
[1-01]
▪
T
t
: Target leaving water temperature (main)
▪
T
a
: Outdoor temperature
continued >>
#
Code
Description
[7.7.1.1]
[1‑00]
[1‑01]
[1‑02]
[1‑03]
<< continuation
▪
[1‑00]: Low outdoor ambient temperature. –
40°C~+5°C (default: –10°C)
▪
[1‑01]: High outdoor ambient temperature.
10°C~25°C (default: 15°C)
▪
[1‑02]: Desired leaving water temperature
when the outdoor temperature equals or
drops below the low ambient temperature.
[9‑01]°C~[9‑00]°C (default: 60°C).
Note:
This value should be higher than [1-03]
as for low outdoor temperatures warmer
water is required.
▪
[1‑03]: Desired leaving water temperature
when the outdoor temperature equals or
rises above the high ambient temperature.
[9‑01]°C~min(45, [9‑00])°C (default: 35°C).
Note:
This value should be lower than [1-02]
as for high outdoor temperatures less warm
water is required.
#
Code
Description
[7.7.1.2]
[1‑06]
[1‑07]
[1‑08]
[1‑09]
Only for EHYHBX08.
Set weather-
dependent cooling
:
[1-09]
[1-08]
Ta
Tt
[1-06]
[1-07]
▪
T
t
: Target leaving water temperature (main)
▪
T
a
: Outdoor temperature
continued >>