7
|
Installation
Installer reference guide
92
EHYH EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
a
X2
DANGER: RISK OF ELECTROCUTION
A fused spur or an unswitched socket MUST be located no more than 1 m from the
appliance.
CAUTION
For installation in damp rooms, a fixed connection is obligatory. When working on
the electrical circuit ALWAYS isolate the electric supply.
7.11.8 To connect the communication cable between gas boiler and indoor unit
1
Open the gas boiler.
2
Open the switch box cover of the gas boiler.
3
Remove one of the bigger knockout holes on the right side of the switch box
of the gas boiler.
4
Put the (larger) boiler connector through the knockout hole. Fix the cable in
the switch box by routing it behind the pre-mounted wires.