4/8
Breadcrumb Field code
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
Setting name
A.4.1
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
└─
Disinfection
A.4.4.1
[2-01]
R/W
0: No
1: Yes
A.4.4.2
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
A.4.4.3
[2-02]
R/W
0~23 hour, step: 1 hour
23
A.4.4.4
[2-03]
R/W
fixed value
60°C
A.4.4.5
[2-04]
R/W
40~60 min, step: 5 min
40 min
└─
Maximum setpoint
A.4.5
[6-0E]
R/W
[E-06]=1
[E-07] ≠
6:
40~75°C, step: 1°C,
75°C
[E-07] = 6: 40~60°C, step: 1°C,
60°C
[E-06]=0
40~65°C, step: 1°C,
65°C
└─
SP mode
A.4.6
R/W
0: Fixed
1: Weather dep.
└─
Weather dependent curve
A.4.7
[0-0B]
Weather-dependent curve
DHW setpoint for high ambient temp. for DHW
WD curve.
R/W
35~[6-0E]°C, step: 1°C
55°C
A.4.7
[0-0C]
Weather-dependent curve
DHW setpoint for low ambient temp. for DHW
WD curve.
R/W
45~[6-0E]°C, step: 1°C
60°C
A.4.7
[0-0D]
Weather-dependent curve
High ambient temp. for DHW WD curve.
R/W
10~25°C, step: 1°C
15°C
A.4.7
[0-0E]
Weather-dependent curve
Low ambient temp. for DHW WD curve.
R/W
-40~5°C, step: 1°C
-10°C
└─
Heat sources
└─
Boiler
A.5.2.2
[5-01]
R/W
-15~35°C, step: 1°C
5°C
└─
System operation
└─
Auto restart
A.6.1
[3-00]
R/W
0: No
1: Yes
└─
Pwr consumpt. Control
A.6.3.1
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
A.6.3.2
[4-09]
R/W
0: Current
1: Power
A.6.3.3
[5-05]
R/W
0~50 A, step: 1 A
50 A
A.6.3.4
[5-09]
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.5.1
[5-05]
Amp. limits for DI
Limit DI1
R/W
0~50 A, step: 1 A
50 A
A.6.3.5.2
[5-06]
Amp. limits for DI
Limit DI2
R/W
0~50 A, step: 1 A
50 A
A.6.3.5.3
[5-07]
Amp. limits for DI
Limit DI3
R/W
0~50 A, step: 1 A
50 A
A.6.3.5.4
[5-08]
Amp. limits for DI
Limit DI4
R/W
0~50 A, step: 1 A
50 A
A.6.3.6.1
[5-09]
kW limits for DI
Limit DI1
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.2
[5-0A]
kW limits for DI
Limit DI2
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.3
[5-0B]
kW limits for DI
Limit DI3
R/W
0~20 kW, step: 0,5 kW
20 kW
A.6.3.6.4
[5-0C]
kW limits for DI
Limit DI4
R/W
0~20 kW, step: 0,5 kW
20 kW
└─
Averaging time
A.6.4
[1-0A]
R/W
0: No averaging
1: 12 hours
2: 24 hours
3: 48 hours
4: 72 hours
└─
Ext amb. sensor offset
A.6.5
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
└─
Savings mode
A.6.7
[7-04]
R/W
0: Economical
1: Ecological
└─
Emergency
A.6.C
R/W
0: Manual
1: Automatic
└─
Overview settings
A.8
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
35°C
A.8
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
60°C
A.8
[0-02]
R/W
10~25°C, step: 1°C
15°C
A.8
[0-03]
R/W
-40~5°C, step: 1°C
-10°C
A.8
[0-04]
R/W
[9-07]~[9-08]°C, step: 1°C
8°C
A.8
[0-05]
R/W
[9-07]~[9-08]°C, step: 1°C
12°C
A.8
[0-06]
R/W
25~43°C, step: 1°C
35°C
A.8
[0-07]
R/W
10~25°C, step: 1°C
20°C
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Low ambient temp. for LWT add zone heating WD curve.
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
High ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
High ambient temp. for LWT add zone heating WD curve.
Equilibrium temp.
Mode
Type
Amp. value
kW value
Start time
Temperature target
Duration
Disinfection
Operation day
4P353731-1H - 2021.02
*HYHBH/X*AA/FV3