8
|
Configuration
Installer reference guide
125
EHYH EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
#
Code
Description
[A.2.1.7]
[C-07]
Unit temperature control:
▪
0 (
LWT control
): Unit operation is decided
based on the leaving water temperature
regardless the actual room temperature and/or
heating or cooling demand of the room.
▪
1 (
Ext RT control
): Unit operation is
decided by the external thermostat or
equivalent (e.g. heat pump convector).
▪
2 (
RT control
)(default): Unit operation is
decided based on the ambient temperature of
the user interface.
[A.2.1.B]
N/A
Only if there are 2 user interfaces (1 installed in
the room, 1 installed at the indoor unit):
a
b
▪
a: At unit
▪
b: In room as room thermostat
User interface location
:
▪
At unit
: this user interface is used to control
the unit. The other user interface is
automatically set to
In room
.
▪
In room
(default): this user interface acts as
room thermostat. The other user interface is
automatically set to
At unit