INSTRUCTION MANUAL DAAB AUTOMATIC CONTROLL UNIT EP104 4.08
50
Instruction manual edition 1 for EP104 version 4.08
Programmable input 5
No.
Name
Range
Factory Setting Ref.
page
P500
Channels in programmable input 6
0 - 1
1
0
Disabled
1
Activated (Only channels P560-P598 activated)
2
Battery operation, only together with frequency converter (Channels P560-P598 inactivated)
P560
Control function
0-5
0
0
Disabled
1
Open
2
Close
3
Stop
4
Open/close
5
Open/stop/close
S
P561 Type of control signal when activated
1 - 2
1
1
Pulse
2
Signal for as long as the input is activated
P562
Half operation
1 - 3
3
1
Motor 1
2
Motor 2
3
Motors 1 and 2
P563
Limited opening
0 - 1
0
0
Disabled
1
Opening according to set time in channel C412/C414 or number of degrees in L116/L126 if encoder
is used.
P570
Motor lock
0 - 1
0
0
Disabled
1
The barrier cannot be operated without a signal at programmable input 5. If the signal disappears the
barrier is stopped.
P575
Opening via input after activation during set time,
input will not open the barrier until it has been
activated for the set time.
0.0-9.9 seconds
0.0
P580
Keep opened
0 - 2
0
0
Disabled
1
Automatic closing disabled after the input is activated, reset by another control signal
2
Automatic closing disabled by a constant signal
P590
Interlock opening
0 - 1
0
0
Disabled
1
Opens the local door if P560 is set to open, and passes the signal on to the remote door
P596
Blocking disabled for local and remote doors. Works
only with a constant signal.
0 - 1
0
0
Disabled
1
Active
P598
Automatic closing disabled for remote door Only
works if there is a constant signal
0 - 1
0
0
Disabled
1
Active