INSTRUCTION MANUAL DAAB AUTOMATIC CONTROLL UNIT EP104 4.08
51
Instruction manual edition 1 for EP104 version 4.08
Programmable input 6
No.
Name
Range
Factory Setting Ref.
page
P600
Channels in programmable input 6
0 - 1
1
0
Disabled
1
Activated (Only channels P660-P698 activated)
2
Safety input (Only channels P640-P643 activated)
P640
Safety function when input is activated
0 – 3
1
0
Disabled
1
Reverse to fully open
2
Stop with automatic restart of automatic closing
3
Stop, wait for new control signal or time in C520 and thereafter automatic closing.
P641
Safety during run-on time or disengagement angle
in closing movement.
0 – 1
0
0
Disabled when both halves are in run-on or disengagement angle
1
Activated according to P640
P642
Protection in opening movement
0 - 4
1
0
Disabled
1
Reverse to fully closed
2
Stop with automatic restart of automatic closing
3
Stop, wait for new control signal or time in C520 and then automatic closing.
4
Stop with restart of opening
P643
Control of external protection connected to INP6
0 – 1
1
0
No check
1
Test of protection connected to INP6
P660
Control function
0-5
0
0
Disabled
1
Open
2
Close
3
Stop
4
Open/close
5
Open/stop/close
S
P661 Type of control signal when activated
1 - 2
1
1
Pulse
2
Signal for as long as the input is activated
P662
Half operation
1 - 3
3
1
Motor 1
2
Motor 2
3
Motors 1 and 2
P663
Limited opening
0 - 1
0
0
Disabled
1
Opening according to set time in channel C412/C414 or number of degrees in L116/L126 if encoder
is used.
P670
Motor lock
0 - 1
0
0
Disabled
1
The barrier cannot be operated without a signal at programmable input 6. If the signal disappears the
barrier is stopped.