INSTRUCTION MANUAL DAAB AUTOMATIC CONTROLL UNIT EP104 4.08
48
Instruction manual edition 1 for EP104 version 4.08
Programmable input 3
No.
Name
Range
Factory Setting Ref.
page
P300
Channels in programmable input 3
0 - 1
1
0
Disabled
1
Enabled
P360
Control function
0-5
0
0
Disabled
1
Open
2
Close
3
Stop
4
Open/close
5
Open/stop/close
S
P361 Type of control signal when activated
1 - 2
1
1
Pulse (hold-to-run mode not possible)
2
Signal for as long as the input is activated
P362
Half operation
1 - 3
3
1
Motor 1
2
Motor 2
3
Motors 1 and 2
P363
Limited opening
0 - 1
0
0
Disabled
1
Opening according to set time in channel C412/C414 or number of degrees in L116/L126 if encoder
is used.
P370
Motor lock
0 - 1
0
0
Disabled
1
The barrier cannot be operated without a signal at programmable input 3. If the signal disappears the
barrier is stopped.
P375
Opening via input after activation during set time,
input will not open the barrier until it has been
activated for the set time.
0.0-9.9 seconds
0.0
P380
Keep opened
0 - 2
0
0
Disabled
1
Automatic closing disabled after the input is activated, reset by another control signal
2
Automatic closing disabled by a constant signal
P390
Interlock opening
0 - 1
0
0
Disabled
1
Opens the local door if P360 is set to open, and passes the signal on to the remote door
P396
Blocking disabled for local and remote doors. Works
only with a constant signal.
0 - 1
0
0
Disabled
1
Active
P398
Automatic closing disabled for remote door Only
works if there is a constant signal
0 - 1
0
0
Disabled
1
Active