INSTRUCTION MANUAL DAAB AUTOMATIC CONTROLL UNIT EP104 4.08
54
Instruction manual edition 1 for EP104 version 4.08
Error
code
Meaning
Possible cause
E201
Motor protection triggered for motor 1
Motor is taking more than 1.5x motor current. Motor is
sluggish or stops. Faulty fuse? Phase failure in an incoming
phase? Break in cable to motor or motor winding? Check the
motor protection setting.
E202
Motor protection triggered for motor 2
E203
Motor protection triggered four times in a row,
control unit locked for 3 minutes
Is there an obstacle? Fault in electric motor? Check the
configuration of channels C252, C253, C262, C263.
E204
Current through motor 1, which is switched off
E205
Current through motor 2, which is switched off
E206
No current or low current in motor 1
The electric motor is running at less than half the motor
protection setting. Check the motor protection setting. Phase
failure in an incoming phase? Faulty fuse? Break in cable to
electric motor? Voltage drop in stop circuit/limit switch
circuit?
E207
No current or low current in motor 2
E221
Start load too low, motor 1
Check that the motor is correctly connected.
E222
Start load too low, motor 2
Check that the motor is correctly connected.
E223
Normal power too low, motor 1
Check C230.
E224
Normal power too low, motor 2
Check C240.
E225
The load guard has been tripped three times in a
row
Obstacle in the way? Mechanical fault preventing closing?
Check the load guard settings.
E318
Error in loop 1
Are the loop and connectors electrically continuous?
For more troubleshooting tips, see the instruction manual
for the vehicle detector
E319
Error in loop 2
E614
Communication error
Correct polarity in communication cables? Break in
communication cable? Correct settings in both automatic
control units? Is the external unit switched on?
E651
No response from frequency converter motor 1
Check the connection and the settings as described in
Instruction Manual for DB409. Address must be set for the
frequency converter.
E652
No response from frequency converter motor 2
Check the connection and the settings as described in
Instruction Manual for DB409. Address must be set for the
frequency converter.
E661
Incorrect value sent to frequency converter motor
1
Contact FAAC Nordic AB
E662
Incorrect value sent to frequency converter motor
2
Contact FAAC Nordic AB
E671
Incorrect response from frequency converter
motor 1
Contact FAAC Nordic AB
E672
Incorrect response from frequency converter
motor 2
Contact FAAC Nordic AB
E901
Extraneous voltage at safety edge input SE.C1
Contact FAAC Nordic AB.
E902
Extraneous voltage at safety edge input SE.C2
Contact FAAC Nordic AB.
E903
Extraneous voltage at safety edge input SE.O1
Contact FAAC Nordic AB.
E904
Extraneous voltage at limit switch input
Contact FAAC Nordic AB.
E905
Extraneous voltage in stop circuit
Contact FAAC Nordic AB.
E906
Extraneous voltage at safety edge input SE.O2
Contact FAAC Nordic AB.
E907
Extraneous voltage on limit switch L.O1
Contact FAAC Nordic AB.
E908
Extraneous voltage on limit switch L.O2
Contact FAAC Nordic AB.
E909
Internal watchdog triggered
Contact FAAC Nordic AB.
E910
Clock monitoring error
Contact FAAC Nordic AB.
E911
Repeated restart attempts
Short circuit in limit switch or stop circuit? After the problem
is corrected, the unit makes a new attempt to restart after 20
seconds.