Effective October, 2000
Page 7
For Top Mounted Sensors Only.
A. Align a 3-Point Terminal Block with each set
of holes in the Sensor Mounting Bracket as
shown. Secure the 3-Point Terminal Blocks to
the Sensor Mounting Bracket using the
(6) .138-32
×
.500" screws and (6) lock
washers supplied.
B. Install a Flexiform Grommet to the edges of
each wire cutout in the Sensor Mounting
Bracket.
C. Insert the three (3) wires exiting the top of the
Sensor through the opening in the Sensor
Mounting Bracket.
D. With the Sensor Nameplate at the top and
facing out, align the threaded holes in the top
of the Sensor with the holes in the Sensor
Mounting Bracket. Secure the Sensor to the
Sensor Mounting Bracket using the (4)
.250-20
×
.500" bolts, (4) lock washers, and
(4) flat washers supplied.
E. Repeat Steps B and C for the remaining
two (2) Sensors.
F. Connection of the Sensor Wires to the 3-Point
Terminal blocks is detailed in the photo. Once
the correct connection point has been
determined, cut each Sensor Wire to an
appropriate length and attach a supplied ring
terminal to each wire.
G. Align the Sensor Mounting Bracket / Sensor
Assembly with the existing holes on the top rear
of the Breaker Back Plate as shown. Secure
using the (2) .500-13
×
1.50" bolts, (4) flat
washers, (2) lock washers, and (2) nuts
supplied.
Black
Red
White
Black
White
Red