Effective October, 2000
Page 19
B. Mount the left-hand (the larger Bracket with
cut-out) and right-hand Trip Unit Mounting
Brackets, as shown, to the Glass Poly Barrier
using the (2) .190-32
×
.500" steel screws,
(2) .190-32
×
.625" nylon screws, (6) steel
flat washers, (2) nylon flat washers, (4) lock
washers, and (4) nuts supplied.
Note: The nylon screws and flat washers
are to be used in the top holes and the
steel screws and flat washers are to be
used in the bottom holes. The screw heads
must be on the Glass Poly Barrier side of
the assembly.
C.
For Kits Supplied with an Auxiliary Switch Only.
Using a pair of diagonals, cut 4" off the end of
the Microswitch Arm. Mount the Microswitch to
the Auxiliary Switch Mounting Bracket, as
shown, using the (2) .138-32
×
1.00" screws,
(4) flat washers, (2) lock washers, and (2) nuts
supplied.
Note: The orientation of the Microswitch is
different for the Frameless versus the
Framed Breakers.
Mount the Auxiliary Switch Assembly to the
bottom of the right-hand Trip Unit Mounting
Bracket Assembly, using the (1) .138-32
×
.375"
screw, (2) flat washers, (1) lock washer, and (1)
nut supplied.
D.
For Kits Supplied with a PT Module Only.
Remove the “L” Mounting Bracket, Warning
Label Plate, and Connector from the Potential
Transformer (PT) Module.
Using the original hardware, reconnect the “L”
Mounting Bracket, New Warning Label Plate,
and the Connector to the side of the PT Module
as shown.
www
. ElectricalPartManuals