Effective October, 2000
Page 23
D. Secure the External Harness to the Trip Unit “L”
shaped Mounting Bracket, as shown, using the
(2) nylon wire clamps and the (2) .138
×
.380"
thread cutting screws supplied.
D. Drill two (2) .164" holes in the right side of the
Breaker Frame. Secure the External Harness to
the holes just drilled using the (2) nylon wire
clamps and the (2) .138
×
.380" thread cutting
screws supplied.
Route the PT Wires to a position suitable for
attachment to the proper Copper Adapters.
Move the PT Wire markers to a position where
they will still be attached to the wires after
cutting. Cut the wires to length, strip each
wire .250", and install a .380" ring terminal
on each wire.
Connect each PT Wire to its corresponding
Copper Connector using the .375" bolts left
loose in Step 3.
B. Plug the Aux. CT Harness into the Aux. CT
Module. Route the Aux. CT Harness up along
the Breaker to the bottom of the Trip Unit then
plug it into the Trip Unit.
C. Connect the External Harness to the Trip Unit.
NOTE: For 510 Basic Kits, the External
Harness is the plug pictured above. It is
to be plugged into the right side of the
Trip Unit.