Effective October, 2000
Page 17
C. Using Drilling Plan “B”, drill two (2) .312" holes
in the bottom of the right front Breaker Bottom
Channel as shown.
Note: Cover the area below the location in
which the holes will be drilled to prevent the
drilling chips from falling into the Breaker.
D. Align the CPT Assembly with the holes just
drilled. Secure the CPT Assembly to the
Breaker using the (2) .250-20
×
.625" bolts,
(4) flat washers, (2) lock washers, and
(2) nuts supplied.
C. Using Drilling Plan “C”, drill two (2) .312" holes
in the left side of the Top Breaker Channel.
Note: Cover the area below the location in
which the holes will be drilled to prevent the
drilling chips from falling into the Breaker.
D. Align the CPT Assembly with the holes just
drilled. Secure the CPT Assembly to the
Breaker using the (2) .250-20
×
.625" bolts,
(4) flat washers, (2) lock washers, and
(2) nuts supplied.
1.00"
0.38"
0.25" Dia. (2)
2.00"
Right Front Breaker
Bottom Mounting
Channel
Face
Plate
Drilling Plan “B”
0.25" Dia. (2)
3.50"
Front of
Breaker
2.00"
0.38"
Drilling Plan “C”
www
. ElectricalPartManuals