Effective October, 2000
Page 9
J. Align the Sensor Mounting Bracket with the
existing holes on the bottom rear of the Breaker
Back Plate as shown. Secure using the (2)
.500-13
×
1.50" bolts, (4) flat washers, (2) lock
washers, and (2) nuts supplied.
K. Following the G. E. AK-50 Series Instruction
Manual originally supplied with the Breaker,
reinstall the original fuses, mounting brackets,
and hardware.
For AKT-2A-50 and AKT-3A-50 2,000 Amp
Breakers Only.
A. Align two (2) Sensor Adapter Brackets with
the holes in the top of the Sensor as shown
(the Sensor Terminals are located on the
bottom of the Sensor). Secure the Sensor
Adapter Brackets to the Sensor using the (2)
.250-20
×
2.75" bolts, (4) flat washers, (2) lock
washers, and (2) nuts supplied.
B. Repeat Step A for the remaining two (2)
Sensors.
C. Align the threaded holes in the Sensor
Adapter Brackets with the holes in the Sensor
Mounting Bracket. Secure the Sensor Assembly
to the Sensor Mounting Bracket using the (4)
.250-20
×
.500" bolts, (2) lock washers, and (2)
flat washers supplied.
D. Repeat Step B for the remaining two (2)
Sensor Assemblies.
E. Align the Sensor Mounting Bracket / Sensor
Assembly with the existing holes on the top
rear of the Breaker Back Plate as shown.
Secure using the (2) .500-13
×
1.50" bolts,
(4) flat washers, (2) lock washers, and (2)
nuts supplied.