Effective October, 2000
Page 13
For Kits Supplied with a PT Module Only.
Refer to Section 7-3, Power Flow Convention, of
the Retrofit Application Data, supplied with the
Retrofit Kit, for additional wiring information and to
verify the Phase Convention used on this Breaker
Application.
F. Connect the “+” wire of the DTA Extension
Harness to the “OP” terminal of the Aux. CT
Module and the unmarked wire to the “ON”
terminal. Route the DTA Extension Harness
inside the Breaker towards the left front corner.
G. Use the nylon wire ties and clamps supplied to
dress all wires to keep them away from any
moving parts within the Breaker.
H. Carefully return the Breaker to its normal,
upright position.
Step 7:
Installing the DTA Assembly
A. With the Breaker in the OPEN position and with
the Breaker Closing Springs DISCHARGED,
mount the Trip Finger on the Breaker Trip Bar,
as shown, using the (1) .250-20
×
.750"
carriage bolt, (1) flat washer, (1) lock washer,
and (1) nut supplied. Do not tighten hardware at
this time. The Trip Finger should be free to move
on the Trip Bar.
www