- 9 -
Cod. 1910000001158 - nv03
3.2 Installation procedure
• Position the gasket.
•
Screw in the heater in the boiler connection indicated by the manufacturer.
Use a reduction if the connection available is of a larger diameter (use
adapter in cast iron or stainless steel, avoid components in brass or copper
or any other material with high conductivity power). Avoid the connection to
be more than 100mm.
• Tighten the heater with a suitable wrench, applying a tightening torque no
greater than 10kg for the tightening , do not apply torsion to the external
case of the heater.
•
Proceed to fill the boiler in such a way as to check the hydraulic seal of
the connection.
• Proceed with electrical connection following the warnings above.
• Adjust the thermostat to the desired temperature.
3.3 Thermostat manual reset
It is advisable to arrange for inspection of the system by qualified personnel
before resetting of the safety thermostat.
ATTENTION: before undertaking any operations, make
sure there is not and cannot there accidentally be power
supply. It is therefore necessary to unplug the power
supply.
1
3
2
4
• Remove the screw located on the protective casing of the electrical
connections and which provides access to the thermostat reset button.
1
2
• Press the thermostat reset button using a tool with an electrically insulated
grip.
3
•
Refit the screw in its seat.
4
4. Operating conditions
Comply with all regulations about the maximum hot water storage
temperature.
The heater must be used within the above stated temperature limits (for
no reason with a temperature higher than 100°C) and exclusively to warm
drinkable water, deprived of any impurity or polluting substances and with
hardness included within 7 and 20°Fr.
WARNING:
In case of water with hardness value >20°F (where 1°F=French
degree=10mg CaCo3/l), to preserve heating element efficiency, it is
necessary to install a suitable system (softener or conditioning agent
dispenser) to reduce the formation of lime scale inside boiler and/
or proceed with a periodic cleaning of the heating element, avoiding
carefully any damage. Damages and malfunctions arising from lime
scale deposits will void product warranty.
In case of impurity, it is required to provide filters at the source of the
accumulation circuit.
Make sure that environment of installation respect the following requirements:
1.
ambient temperature included between 5°C and 45 °C and
humidity ≤ 0.015 kg of water per kg of dry air ( see chart)
2.
heater placed far from heat sources and in areas with good
ventilation.
Temperature
0 °C
20 °C
30 °C
40 °C
50 °C
Max relative
humidity
100%
100%
60%
30%
20%
5. Maintenance
• All installation, wiring and checks must be performed after having
disconnected the power supply.
• In the event of intervention on the safety thermostat, have the system
checked by a skilled operator before manually resetting the thermostat.
•
If a power cable is damaged, it must be replaced by a qualified electrician.
6. Disposal
At the end of technical life cycle of the product, its metallic
components must be given to an authorised metallic materials
collection operator for recycling, while non-metallic components
shall be given to operators authorised for their disposal. Products
must be dealt with, if disposed of by the end user, as assimilable to urban
refuse, therefore in compliance with municipal regulations. It should not in any
case be treated as household waste.
English
MAX: 10 kgm
Ø 60