Technical Data
SP40S Multi-Function Communications System
76
Method of Activation
Description
Strobe
NAC 8-33VDC
Push-to-Talk Microphone
Connected to Mother Board
Auxiliary Input
Remote Microphone or RMX Initiation
IN1
Contact Closure. Activates Message 1 on Digital Voice Section.
IN2
Contact Closure. Activates Message 2 on Digital Voice Section.
IN3
Contact Closure. Activates Message 3 on Digital Voice Section.
IN4
Contact Closure. Activates Message 4 on Digital Voice Section.
IN5
Contact Closure. Activates Message 5 on Digital Voice Section.
IN6
Contact Closure. Activates Message 6 on Digital Voice Section.
IN7
Contact Closure. Activates Message 7 on Digital Voice Section.
IN8
Contact Closure. Activates Message 8 on Digital Voice Section.
Telephone Page
Telephone Page Port
Night Ring
Contact Closure
Background Music
Line Level Signal 2.5V P-P or 300mV RMS at 600 Ohms.
9.3.4 Outputs
Parameter
Description
Visual Notification Appliance Output
1 output circuit. 2.0 amps at 24VDC. Supervised.
Central Amplified Audio Output
1 output circuit.
Selectable 25 or 70.7 Volt RMS output at 40W max.
Supervised.
Trouble Contact
Form C contact normally energized. Contacts transfer
during trouble: 2.0 amps at 24VDC max, resistive load
(see following warning). Non-Supervised.
Alarm Contact
Form C contact normally energized. Contacts transfer
during alarm trouble: 2.0 amps at 24VDC max, resistive
load (see following warning). Non-Supervised.
AC Trouble Contact
Form C contact normally energized. Contacts transfer
during AC trouble: 2.0 amps at 24VDC max, resistive load
(see following warning). Non-Supervised.
WARNING: DO NOT EXCEED THE RATINGS OF THE STATUS CONTACTS.
EXCEEDING THIS RATING MAY CAUSE THE RELAY TO FAIL AND PREVENT A
TROUBLE CONDITION FROM BEING INDICATED.
WARNING: DO NOT EXCEED THE RATINGS OF THE ALARM CONTACTS.
EXCEEDING THIS RATING MAY CAUSE THE RELAY TO FAIL AND PREVENT
THE MESSAGES FROM BEING PLAYED.
Summary of Contents for SP40S Series
Page 2: ...SP40S Multi Function Facility Communications System Revision M 2...
Page 4: ...SP40S Multi Function Communication System Revision M 4...
Page 8: ...SP40S Multi Function Communication System Revision M 8...
Page 10: ...SP40S Multi Function Communication System Revision M 10...
Page 12: ...SP40S Multi Function Communication System Revision M 12...
Page 81: ...Compatible Signaling Appliances SP40S Multi Function Communications System 81...