![Cooper Notification SP40S Series Installation, Testing, Operation And Maintenance Manual Download Page 20](http://html1.mh-extra.com/html/cooper-notification/sp40s-series/sp40s-series_installation-testing-operation-and-maintenance-manual_2664582020.webp)
Overview
SP40S Multi-Function Communications System
20
Digital Voice Section
Capable of playback and record (via 1/8” audio jack).
Digital Voice Message Chip contains the recording program and
memory for eight message sections.
Memory in eight sections with corresponding inputs.
o
A total of four minutes of messages.
o
Each message is 30 seconds in duration.
o
Messages can be combined for longer durations.
Activated by one of eight contact closure inputs (IN1
– IN8) or
manual activation on user interface.
Each CC input (contact closure) can be supervised for an OPEN.
Prealert tones can be chosen for each message (code 3,
continuous, or no pre-tone).
Messages can be selected to have a post-tone that matches the
pre-tone.
Capable of selecting the strobe NAC output for each input.
Feature
Description
Alarm Audio Processing Section
Three Priority ordered audio inputs
Hand-held, push-to-talk (PTT) microphone,
and Priority 1. For live,
emergency voice announcements and instructions. The microphone
overrides (mutes) any voice message or tones in progress.
Auxiliary Input (AUX IN, CC/NAC), Priority 2.
o
CC or NAC initiates AUX IN audio
o
CC is supervised. NAC is not supervised.
o
For use with SAFEPATH
– Remote Microphone Expander
(SP4-RMX) or SAFEPATH
– Remote Microphone (SPRM)
Digital Voice Section inputs (IN1, IN2, IN3, IN4, IN5, IN6, IN7,
IN8).
o
IN1, IN2, IN3, IN4, IN5, IN6, IN7, IN8 have priorities 3, 4, 5,
6, 7, 8, 9, and 10 respectively.
o
IN1
– IN8 are initiated via Contact Closure.
o
IN1, IN2, IN3, IN4, IN5, IN6, IN7, IN8 are supervised for an
OPEN.
o
Messages can also be initiated via user interface.
Non-Alarm Audio Processing
Section
Night Ring (NR), Priority 6.
o
Contact closure activated.
o
Non-alarm.
o
Does not operate if on Battery.
Telephone Page (TEL), Priority 7.
o
Accepts a Telephone Page Port Input.
o
Will not operate if the panel is on Battery.
Background Music (BGM), Priority 8.
o
Line Level Input.
o
Will mute when any other input is used.
o
Will not operate if the panel is on Battery.
Ground Fault Detection Section
Monitors inputs and outputs for 40K Ohms minimum in relation to
ground.
A Dual-Tone Tone Generator with
two field selectable sounds (Code
3 Tone, Slow Whoop) that sound
when there is a Digital Voice
Section Failure in alarm condition.
Provides Code 3 tone or Slow Whoop (user selectable) in the instance
of a Digital Voice failure or system timeout.
Summary of Contents for SP40S Series
Page 2: ...SP40S Multi Function Facility Communications System Revision M 2...
Page 4: ...SP40S Multi Function Communication System Revision M 4...
Page 8: ...SP40S Multi Function Communication System Revision M 8...
Page 10: ...SP40S Multi Function Communication System Revision M 10...
Page 12: ...SP40S Multi Function Communication System Revision M 12...
Page 81: ...Compatible Signaling Appliances SP40S Multi Function Communications System 81...