WARNING: MESSAGES REQUESTED BEFORE AND DURING A TROUBLE
CONDITION MAY NOT BE HEARD, WHICH COULD RESULT IN SERIOUS
INJURY OR DEATH TO YOU AND/OR OTHERS. IF MESSAGES REQUESTED
BEFORE AND DURING A TROUBLE CONDITION ARE STILL NECESSARY,
REPEAT THEM WHEN THE SP40S PANEL IS RETURNED TO NORMAL.
5.3.1 Visual Notification Appliance Output Circuit Supervision
The Visual Notification Appliance Output Circuit uses Class B, Style Y wiring, and is
supervised for open and short circuits when the output is de-energized. Output circuit
supervision requires installation of UL Listed 10K Ohm, ½ W EOLR on the output circuit.
A sensed strobe short circuit trouble illuminates D96 STB SHORT LED. A sensed strobe
open circuit trouble illuminates D97 STB OPEN LED. See Figure 8-1 for LED location.
5.3.2 Audio Notification Appliance Output Circuit Supervision
The Audio Notification Appliance Output Circuit uses Class B, Style Y wiring, and is
supervised for open and short circuits when the output is de-energized. Output circuit
supervision requires installation of UL Listed 10K Ohm, ½ W EOLR on the output circuit.
A sensed open circuit trouble illuminates D1 AUDIO OPEN LED. A sensed strobe short
circuit trouble illuminates D2 AUDIO SHORT LED. See Figure 26 for LED location.
5.3.3 Amplifier Supervision
An inaudible supervisory tone plays through the Amplifier section during standby for
supervision purpose. Any sensed trouble illuminates D5 “AMP” LED steadily. See Figure 8-
1 for LED location.
5.3.4 Ground Fault Supervision
The SP40S Multi-Function Facility Communication System supervises for Ground Fault
conditions on Class B, Style Y field wiring that is not electrically isolated. The supervised
wiring includes contact inputs, visual NAC circuits, audio NAC circuits, amplified speaker
NAC circuits, and trouble audible output circuits. All other wiring is electrically isolated. If
a Ground Fault condition exists, D67 GF LED illuminates. See Figure 26 for LED locations.
5.4
Actions that Initiate Audio Alarms
Table 6 indicates what can initiate an alarm condition and the resulting SP40S Multi-
Function Facility Communication System actions.
Table 6 Audio Alarm Conditions and Results
PRIORITY
OF EVENT
INITIATING
ACTION
RESULT
1
Panel microphone push-to-talk button,
is depressed.
Panel microphone live voice broadcast enabled.
2
Remote Microphone push-to-talk
button is depressed
Remote MIC live voice broadcast is enabled.
3, 4, 5, 6, 7, 8,
9, 10
Digital Voice circuit Contact Closure
inputs. (IN1, IN2, IN3, IN4, IN5, IN6,
IN7, IN8)
Selected Digital Voice enabled. If digital voice is
non-operational, program tone broadcasts.
Summary of Contents for SP40S Series
Page 2: ...SP40S Multi Function Facility Communications System Revision M 2...
Page 4: ...SP40S Multi Function Communication System Revision M 4...
Page 8: ...SP40S Multi Function Communication System Revision M 8...
Page 10: ...SP40S Multi Function Communication System Revision M 10...
Page 12: ...SP40S Multi Function Communication System Revision M 12...
Page 81: ...Compatible Signaling Appliances SP40S Multi Function Communications System 81...