![Cooper Notification SP40S Series Installation, Testing, Operation And Maintenance Manual Download Page 40](http://html1.mh-extra.com/html/cooper-notification/sp40s-series/sp40s-series_installation-testing-operation-and-maintenance-manual_2664582040.webp)
Installation
SP40S Multi-Function Communications System
40
Wire Distance Chart For 25V Speaker Line in feet
Watts
12 AWG
14 AWG
16 AWG
18 AWG
5
2179
1374
865
543
10
1090
687
432
271
15
726
458
288
181
20
545
344
216
136
25
436
275
173
109
30
363
229
144
90
35
311
196
124
78
40
272
172
108
68
Wire Distance Chart For 70V Speaker Line in feet
Watts
12 AWG
14 AWG
16 AWG
18 AWG
5
17087
10775
6780
4256
10
8543
5387
3390
2128
15
5696
3592
2260
1419
20
4272
2694
1695
1064
25
3417
2155
1356
851
30
2848
1796
1130
709
35
2441
1539
969
608
40
2136
1347
847
532
4.4.3 Installing Field Wiring Connections
NOTE:
The terminal blocks on the SP40S Multi-Function Facility Communication System
are removable. To remove a terminal block, pull the block straight up from the circuit
board, as shown in Figure 12. Attach wires to the desired connections, then plug the
terminal block back on the board, being careful to match the pins.
Figure 12 Removable Terminal Block
Summary of Contents for SP40S Series
Page 2: ...SP40S Multi Function Facility Communications System Revision M 2...
Page 4: ...SP40S Multi Function Communication System Revision M 4...
Page 8: ...SP40S Multi Function Communication System Revision M 8...
Page 10: ...SP40S Multi Function Communication System Revision M 10...
Page 12: ...SP40S Multi Function Communication System Revision M 12...
Page 81: ...Compatible Signaling Appliances SP40S Multi Function Communications System 81...