![Cooper Notification SP40S Series Installation, Testing, Operation And Maintenance Manual Download Page 52](http://html1.mh-extra.com/html/cooper-notification/sp40s-series/sp40s-series_installation-testing-operation-and-maintenance-manual_2664582052.webp)
Installation
SP40S Multi-Function Communications System
52
2.
Test the strobe circuit associated with the first message by switching DIP switch
SW3 (DV/Strobe Select), position 1 “ON.” The STB LED on the interface (Red)
turns “ON.” If the strobe circuit is attached to TB11, strobes flash.
3.
Turn OFF message 1 by pressing the top message button again or removing contact
closure from IN1. The message plays to completion at least three times. If DIP
switch SW2 (DV/Strobe Select) position 1 is ON, the strobe circuit is ON until the
message is complete.
4.
Turn DIP switch SW3, position 1 OFF.
5.
Apply contact closure activation to TB7 (IN1) connection (
). The message
should be heard from output speaker circuit. The top message button/LED on the
interface should illuminate steadily to indicate contact closure is present.
6.
Test the strobe circuit associated with the first message switching DIP switch SW3
(DV/Strobe Select), position 1 “ON.” The STB LED (Red) turns “ON.” If the strobe
circuit is attached to TB2, strobes flash.
7.
Remove the contact closure from TB7 (IN1). The message plays to completion at
least three times. If DIP switch SW3 (DV/Strobe Select) position 1 is “ON,” the
strobe circuit is ON until the message is complete. The top message button/LED on
the interface should turn OFF once the contact closure is removed.
8.
Turn DIP switch SW3, position 1 OFF.
9.
Perform Steps 3 through 10 on Messages 2 and 3. Use
Table 5 Digital Voice Message Tests
Message
Number
TB4
Interface Button
SW3 DV/Strobe
Select
Message 1
IN1
Top
Position 1
Message 2
IN2
Second
Position 2
Message 3
IN3
Third
Position 3
Message 4
IN4
Fourth
Position 4
Message 5
IN5
Fifth
Position 5
Message 6
IN6
Sixth
Position 6
Message 7
IN7
Seventh
Position 7
Message 8
IN8
Eighth
Position 8
4.6.2.4 D Strobe Circuit Test
1.
If the Strobe circuit is being used separately, apply 24VDC from TB4 or TB6 to STB
IN connection TB12 (Figure 13). The Strobes on the Strobe Output Circuit should
flash. Also, the SP40 interface Strobe Active LED should illuminate.
2.
Remove the voltage.
Summary of Contents for SP40S Series
Page 2: ...SP40S Multi Function Facility Communications System Revision M 2...
Page 4: ...SP40S Multi Function Communication System Revision M 4...
Page 8: ...SP40S Multi Function Communication System Revision M 8...
Page 10: ...SP40S Multi Function Communication System Revision M 10...
Page 12: ...SP40S Multi Function Communication System Revision M 12...
Page 81: ...Compatible Signaling Appliances SP40S Multi Function Communications System 81...