Overview
SP40S Multi-Function Communications System
31
SW3 (
Strobe Activation)
PIN
FUNCTION
ON
1
DV1 Strobe
STB on when DV1 active
2
DV2 Strobe
STB on when DV2 active
3
DV3 Strobe
STB on when DV3 active
4
DV4 Strobe
STB on when DV4 active
5
DV5 Strobe
STB on when DV5 active
6
DV6 Strobe
STB on when DV6 active
7
DV7 Strobe
STB on when DV7 active
8
DV8 Strobe
STB on when DV8 active
9
MIC Strobe
STB on when MIC active
10
AUX Strobe
STB on when AUX active
SW4
(Tone Types)
PIN
FUNCTION
ON
1
Tone Type - DV1
Code 3 (OFF = continuous)
2
Tone Type - DV2
Code 3 (OFF = continuous)
3
Tone Type - DV3
Code 3 (OFF = continuous)
4
Tone Type - DV4
Code 3 (OFF = continuous)
5
Tone Type - DV5
Code 3 (OFF = continuous)
6
Tone Type - DV6
Code 3 (OFF = continuous)
7
Tone Type - DV7
Code 3 (OFF = continuous)
8
Tone Type - DV8
Code 3 (OFF = continuous)
9
Backup tone
Code3 (OFF = slow whoop)
10
unused
--
SW5
(Pre-tone/Post-tone Enable)
PIN
FUNCTION
ON
1
Pre-tone - DV1
Pre-tone ON for Message 1
2
Pre-tone - DV2
Pre-tone ON for Message 2
3
Pre-tone - DV3
Pre-tone ON for Message 3
4
Pre-tone - DV4
Pre-tone ON for Message 4
5
Pre-tone - DV5
Pre-tone ON for Message 5
6
Pre-tone - DV6
Pre-tone ON for Message 6
7
Pre-tone - DV7
Pre-tone ON for Message 7
8
Pre-tone - DV8
Pre-tone ON for Message 8
9
Post-tone - All
Post-tones enabled (Post-tone Matches Pre-tone)
10
Message Repeat
ON = Message plays a minimum of 3 times
OFF = Message plays a minimum of 1 time*
*NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTIONS AND OTHER
INVOLVED PARTIES:
In order for this product to comply with the requirements in the Standard for
Control Units and Accessories for Fire Alarm Systems, UL 864, Position 10 of SW5 must be kept in the ON
position. UL 864, 9
th
Edition, section 34.2.1.1 requires the alert tone/prerecorded message combination shall
be repeated a minimum of 3 times.
Summary of Contents for SP40S Series
Page 2: ...SP40S Multi Function Facility Communications System Revision M 2...
Page 4: ...SP40S Multi Function Communication System Revision M 4...
Page 8: ...SP40S Multi Function Communication System Revision M 8...
Page 10: ...SP40S Multi Function Communication System Revision M 10...
Page 12: ...SP40S Multi Function Communication System Revision M 12...
Page 81: ...Compatible Signaling Appliances SP40S Multi Function Communications System 81...