![Cooper Notification SP40S Series Installation, Testing, Operation And Maintenance Manual Download Page 37](http://html1.mh-extra.com/html/cooper-notification/sp40s-series/sp40s-series_installation-testing-operation-and-maintenance-manual_2664582037.webp)
Installation
SP40S Multi-Function Communications System
37
TB6
Terminal
Block 6
Section 6,
Auxiliary Input and 24VDC Output Connections (For Connection To SPRM or SP4-RMX)
AUX
Auxiliary Input Audio
Line Level Audio Input, Remote MIC, or SP4-RMX Priority 2.
CC/NAC
Contact Closure/NAC
Contact closure or NAC will initiate AUX IN Audio. CC is supervised.
Connects to RMX or Remote MIC (CC Mode).
24V Out
24VDC, 0.5A output
Regulated, 24 VDC, 0.5A Continuous Output Connection, Power Limited
auxiliary power source. NOTE: Two 24V outputs combine for 0.5A.
Connects to RMX or Remote MIC.
Terminal
Block
Symbol
Alarm Connections
Definitions
TB7
Terminal
Block 7
Section 7
Internal Digital Voice Module Input Connections
IN 1
Input 1
Digital Voice Initiating connection for message #1 (contact closure).
Priority 3.
IN 2
Input 2
Digital Voice Initiating connection for message #2 (contact closure).
Priority 4.
IN 3
Input 3
Digital Voice Initiating connection for message #3 (contact closure).
Priority 5.
IN 4
Input 4
Digital Voice Initiating connection for message #4 (contact closure).
Priority 6.
TB8
Terminal
Block 8
Section 8
Internal Digital Voice Module Input Connections
IN 5
Input 5
Digital Voice Initiating connection for message #5 (contact closure).
Priority 7.
IN 6
Input 6
Digital Voice Initiating connection for message #6 (contact closure).
Priority 8.
IN 7
Input 7
Digital Voice Initiating connection for message #7 (contact closure).
Priority 9.
IN 8
Input 8
Digital Voice Initiating connection for message #8 (contact closure).
Priority 10.
TB9
Terminal
Block 9
Section 9
Primary Power (VAC) Connections
AC
Primary Power (AC)
AC Input Voltage. Make sure Line (L), Neutral (N), and Ground (G) are
connected. Non-power limited. Make sure power cord is run properly (see
wiring diagram Figure 4-13 in Section 4.9.1).
TB10
Terminal
Block 10
Section
10
Secondary Power (Battery) Connections
BAT
Secondary Power (Battery)
24VDC, up to 33 Ah Battery input connection. The enclosure can
accommodate up to 12 Ah. Batteries greater than 12 Amp-Hours (Ah) are
required to be installed in a UL listed battery box. Non-power limited.
TB12
Terminal
Block 12
Section
11
Strobe Connections. See Appendix E for strobe compatibility list.
STB
OUT
Strobe Output
8-33 VDC, Regulated, 2A Maximum Strobe NAC Output Supervised with
UL Listed 10k Ohm, ½ W EOLR. (Power limited).
RET
Return
Strobe Input Return for connecting additional strobe circuits, or UL Listed
10k Ohm, ½ W EOLR.
STB IN
Strobe Input
8-33 VDC, Strobe NAC Input. Triggers strobe in Alarm condition.
NOTE:
All Outputs (Strobe Output, Audio Output, and 24VDC Auxiliary Power Source) are
power limited circuits.
Summary of Contents for SP40S Series
Page 2: ...SP40S Multi Function Facility Communications System Revision M 2...
Page 4: ...SP40S Multi Function Communication System Revision M 4...
Page 8: ...SP40S Multi Function Communication System Revision M 8...
Page 10: ...SP40S Multi Function Communication System Revision M 10...
Page 12: ...SP40S Multi Function Communication System Revision M 12...
Page 81: ...Compatible Signaling Appliances SP40S Multi Function Communications System 81...