![Cooper Notification SP40S Series Installation, Testing, Operation And Maintenance Manual Download Page 30](http://html1.mh-extra.com/html/cooper-notification/sp40s-series/sp40s-series_installation-testing-operation-and-maintenance-manual_2664582030.webp)
Overview
SP40S Multi-Function Communications System
30
Figure 9 Grounding Screws and Grounding Standoff Locations
These 8 parts must be installed and securely fastened.
3.7
User Settings
3.7.1 Switch Descriptions
SW2 (
AC Trouble Settings, Booster Connection Settings)
PIN
FUNCTION
ON
1
Ext. AC Loss Sup.
10k EOLR supervision On For SPB
SUP Contacts
2
AC Loss Delay
170 minute AC Loss Delay
(For Off Premise AC Loss Reporting)
3
Ext AC TRB Mode
Audio Booster AC Trouble Reported
To SP40S Separately